background image

17

8

FIREPLACE INSTALLATION

Connection of the stovepipe directly into
the existing masonry chimney over the
fireplace opening is the only approved
method. This installation performs bet-
ter, yielding easy to clean and inspect
for creosote. Before beginning this type
of installation plan carefully; a high de-
gree of skill is required to insure safety.

An entry port for the stovepipe must be
cut through the chimney with minimum
damage to the fire clay liner. Some
involved measurements may be required
to locate the flue liner exactly. Before
cutting, take time to mark the size and
position of the entry port. Position the
entry port so that at least 8 inches of the
flue liner remains below the port.

Keep in mind that mantels and
combustible trim around the fireplace
must have adequate clearances from
the heater and stovepipe or must be
protected in an approved manner. Also,
be sure to leave at least 24" clearance
between the top of the stovepipe and
the combustible ceiling or other com-
bustibles. Placing the center of the entry
port 2 feet below the ceiling will insure
proper clearance for 6 inch, 8 inch, and
10 inch stovepipes. Next, install a fire
clay (at least 5/8 in. thick) or metal
thimble, being sure that the thimble is
flush with the inner flue lining.  Secure
the thimble in place with refractory mor-
tar. The thimble should be surrounded
on all sides with 8 inches of brickwork
(solid masonry units) or 24 inches of
stone.

Install the stovepipe as far as possible
into the thimble, but not past the inside
of the flue lining. There should be a
small airspace (approximately 1/2 inch)
between the stovepipe and thimble,
allowing for expansion of the stove-
pipe. Seal this airspace with high-tem-
perature caulking or ceramic wool. Fi-
nally, be sure to wire the damper closed
and apply the same sealant you used at
the stovepipe and thimble junction.

Do not use the Type B installation (not
illustrated in this manual), that is, vent-
ing up through the fireplace opening,
regardless of whether the fireplace
opening is closed.

MASONRY CHIMNEY have several
positive attributes: If properly built, they
are quite durable, and most
homeowners consider them more at-
tractive perhaps than a non-enclosed
factory built chimney.
And, if the chimney is located within the
confines of the house (that is, not at-
tached to an exterior wall), its mass
alone will store heat longer and con-
tinue to release the heat long after the
fire has died. Masonry chimneys have
many disadvantages though.

Masonry chimneys constructed on an
exterior wall are exposed to cold out-
door temperatures, promoting greater
heater loss, higher accumulations of
creosote, and reduced draft which leads
to poorer heater or furnace perfor-
mance.

Concrete block chimneys (when not
protected by a brick veneer) are inher-
ently unsafe, result in poor draft, and are
subject to rapid deterioration. They do
not meet code and are not recom-
mended.

REPAIR PARTS

AUTOMATIC COAL BURNING CIRCULATOR HEATER

MODEL NUMBER 2847

(SEE PAGE 18)

KEY NO.

PART NO.

DESCRIPTION

QTY.

1

89062

Door Knob

1

2

83005

10-24x1/2" Machine Screw

2

3

83033

8-32x1/4" PH Screw

1

4

83093

Spring Latch

1

5

83244

10-24 Kep Nut

1

6

67968

Cabinet Door Frame

1

7

86191

Thermostat Linkage Adjuster

1

8

85381C

Control Panel Plate

1

9

89142

Thermostat Knob

1

10

67725

Cabinet Front

1

11

67967

Cabinet Left Side

1

12

24240

Flue Collar Ring

1

13

68350

Cabinet Top

1

14

67743

Thermostat Assembly

1

15

68505

Cabinet Back

1

16

89065

Door Hinge

2

17

67969

Cabinet Door

1

REPAIR PARTS LIST

Содержание WONDERCOAL 2847

Страница 1: ...MBER 2 The PART DESCRIPTION 3 The MODEL NUMBER 2847 4 The SERIAL NUMBER ________________ Before installing your heater fill in the serial number of your heater in the space provided above United State...

Страница 2: ...inimum Straight or Corrugated Elbow as required 1 2 Sheet Metal Screws 6 Inside Diameter Underwriters Laboratories UL listed Residential Type and Building Heating Appliance Chimney or lined 6 existing...

Страница 3: ...ion NFPA publica tion Using Coal and Wood Stoves Safely NFPA No HS 10 1978 The address of the NFPA is Battery March Park Quincy MA 02269 Keep the ash pit section free of excess ashes Do not allow ashe...

Страница 4: ...ll If the wall is only faced with brick or stone treat it as a combustible wall CAUTION Keep furnishings and other combustible materials away from the heater 4 21 Fig 3 Fig 2 Fig 4 20 21 16 8 52 1 4 2...

Страница 5: ...NON COMBUSTIBLE WALL FLOOR PROTECTOR FLUE CONNECTION NON COMBUSTIBLE WALL PIPE FLOOR PROTECTOR REFER TO CHIMNEY MANUFACTURERS PARTS AND INSTRUCTIONS 2 FT MIN 10 FT 3 FT MIN Fig 5 Thru the Wall Instal...

Страница 6: ...1 40102 Feed Door Assembly 68605 20 Feed Door 1 40199 21 1 4 20 Kep Nut 2 83250 22 Draft Wheel 1 40056 23 1 4 20x1 Machine Screw 1 83227 24 Door Handle 2 40091 25 Feed Door Rope Gasket 3 75FT 88033 2...

Страница 7: ...engi neer competent mason certified Chim ney Sweep or knowledgeable inspec tor Many prefabricated fireplaces fall into the zero clearancefireplace category This is a factory metal fireplace with multi...

Страница 8: ...on of the stove pipe Seal this airspace with high tem perature caulking or ceramic wool Fi nally be sure to wire the damper closed and apply the same sealant you used at the stovepipe and thimble junc...

Страница 9: ...TER S INITIAL FIRING IS TO INSURE A GOOD SEAL AFTER THE GASKETING SETTLES Fig 11 Fig 11A TYPE A FIREPLACE CONVERSION Fig 7 5 8 FIRECLAY FLUE LINER STOVEPIPE CONNECTOR SEALED AT THIMBLE HORIZONTAL 6 ST...

Страница 10: ...n fire ex tinguisherdirectlyintothestovethrough an appropriately placed cleanout If us ing a Halon extinguisher please re member that is totally displaces oxygen and could become a hazard in itself if...

Страница 11: ...DUCE A DANGEROUS CONDITION AND EVEN CAUSE A HOUSE FIRE IF ANY PORTION OF THE HEATER OR ANY CHIMNEY CONNECTOR GLOWS RED OR DIS COLORS THE HEATER IS BEING OVERFIRED CAUTION DO NOT OPERATE THIS HEATER WI...

Страница 12: ...on will cut the air supply and smother the fire Add a thin layer of coal preferably smaller chunks to the wood fire being careful not to disturb it too much or cut off the draft Then add a second heav...

Отзывы: