background image

10

15

SERVICE HINTS

Do not expect a heater to draw. It is the
chimney that creates the draft. Smoke
spillage into the house or excessive
build-up of water or creosote in the
chimney are warnings that the chimney
is not functioning properly. Possible
causes are:

1.  The connection pipe may be pushed
into the chimney too far, stopping the
draft (Fig. 8).

2.  Two heaters connected into the
same chimney flue.

3.  The same flue being used to ventilate
the cellar or basement. If there is a
cleanout opening at the base of the
chimney, it must be closed tightly and
sealed.

4.  If the flue is too cool, water will
condense in the chimney and run back
into the stove. Creosote formation will
be rapid and may block the chimney.
Operate the heater at a high enough fire
to keep the chimney warm preventing
this condensation.

5.  The chimney top may be lower than
another part of the house or a nearby
tree. The wind blowing over a house or
a tree falls on top of the chimney like
water over a dam, beating down the
smoke. The top of the chimney should
be at least 3 feet higher than any point
of the roof within 10 feet (Fig. 6).

6.  Other chimney/flue inadequacies
covered elsewhere in this manual.

When coal is burned, the products of
combustion combine with moisture to
form a soot residue which accumulates
on the flue lining. When ignited, this soot
makes an extremely hot fire.

The chimney connector should be in-
spected at least twice monthly during
the heating season to determine if a
creosote buildup has occurred.

If creosote has accumulated, it should
be removed. Failure to remove creo-
sote or soot may cause a house fire.
Creosote may be removed by using a
chimney brush or other commonly avail-
able materials.

Chimney fires burn very hot -- up to
2100 degrees F. If you experience a
chimney fire, immediately call the fire
department. They have the professional
means for extinguishing a chimney fire.
Once a chimney fire has occurred, it can
only be extinguished by removing its
sources of oxygen. This can be accom-
plished by shutting any mechanical draft
device such as dampers, discharging a
CO2 (carbon dioxide) or halon fire ex-
tinguisher directly into the stove through
an appropriately placed cleanout. If us-
ing a Halon extinguisher, please re-
member that is totally displaces oxygen
and could become a hazard in itself if
enough were discharged into a living
space.

CAUTION

A chimney fire may cause ignition of wall studs or rafters which you thought

were safe distance from the chimney. If you have a chimney fire, have your

chimney inspected by a qualified person before using again.

NOTE:

A draft reading of .05 to .06 w.c. is suggested for proper burning of this unit

when using bituminous coal as fuel. When using anthracite coal, this draft

readings is a minimum reading.

CHIMNEY MAINTENANCE

CREOSOTE-FORMATION AND NEED FOR REMOVAL

RULES FOR CONNECTOR PIPE INSTALLATION

1.  The crimped end of the stovepipe fits
inside the heater flue collar. Install ad-
ditional pipe and elbow with the
CRIMPED END TOWARD THE
HEATER. This will allow any
condensation in the flue to run back into
the heater.  Smoke will not escape when
installed in this manner.

2.  Slope any horizontal pipe upward
toward the chimney at least 1/4 inch for
each foot of horizontal run.

3.  You must have at least 18 inches of
clearance between any horizontal pip-
ing and the ceiling.

4.  The pipe cannot extend into the
chimney flue. (Fig. 8)

The door knob is mounted inside of the
cabinet door to facilitate shipping and
must be reversed for proper usage.

To get cabinet door open, place hand
under cabinet frame (right hand side
cabinet door side) and push door out.

INSTALLING CABINET DOOR KNOB:

1.  Remove the machine screw and door
knob (Fig. A).

2.  Place door knob on outside of cabinet
door.  Then place machine screw
through hole and into door knob and
tighten (Fig. B).

RIGHT

WRONG

WRONG

Fig. 8

5.  Seal each connector pipe joint with
furnace cement. Also seal the pipe at
the chimney.

6.  Use 3 Sheet Metal screws at each
joint to make the piping rigid.

7.  It is recommended that no more than
two 90 degree bends be used in the
stovepipe installation as more than two
may decrease the amount of draw and
possible, use only corrugated (nonad-
justable) elbows. They are much more
airtight.

8.  The chimney connector must not
pass through an attic or roof space,
closet, or any concealed space, or floor,
ceiling, wall or combustive construc-
tion.

CABINET DOOR CATCH ASSEMBLY

Fig. B

Fig. A

Содержание WONDERCOAL 2847

Страница 1: ...MBER 2 The PART DESCRIPTION 3 The MODEL NUMBER 2847 4 The SERIAL NUMBER ________________ Before installing your heater fill in the serial number of your heater in the space provided above United State...

Страница 2: ...inimum Straight or Corrugated Elbow as required 1 2 Sheet Metal Screws 6 Inside Diameter Underwriters Laboratories UL listed Residential Type and Building Heating Appliance Chimney or lined 6 existing...

Страница 3: ...ion NFPA publica tion Using Coal and Wood Stoves Safely NFPA No HS 10 1978 The address of the NFPA is Battery March Park Quincy MA 02269 Keep the ash pit section free of excess ashes Do not allow ashe...

Страница 4: ...ll If the wall is only faced with brick or stone treat it as a combustible wall CAUTION Keep furnishings and other combustible materials away from the heater 4 21 Fig 3 Fig 2 Fig 4 20 21 16 8 52 1 4 2...

Страница 5: ...NON COMBUSTIBLE WALL FLOOR PROTECTOR FLUE CONNECTION NON COMBUSTIBLE WALL PIPE FLOOR PROTECTOR REFER TO CHIMNEY MANUFACTURERS PARTS AND INSTRUCTIONS 2 FT MIN 10 FT 3 FT MIN Fig 5 Thru the Wall Instal...

Страница 6: ...1 40102 Feed Door Assembly 68605 20 Feed Door 1 40199 21 1 4 20 Kep Nut 2 83250 22 Draft Wheel 1 40056 23 1 4 20x1 Machine Screw 1 83227 24 Door Handle 2 40091 25 Feed Door Rope Gasket 3 75FT 88033 2...

Страница 7: ...engi neer competent mason certified Chim ney Sweep or knowledgeable inspec tor Many prefabricated fireplaces fall into the zero clearancefireplace category This is a factory metal fireplace with multi...

Страница 8: ...on of the stove pipe Seal this airspace with high tem perature caulking or ceramic wool Fi nally be sure to wire the damper closed and apply the same sealant you used at the stovepipe and thimble junc...

Страница 9: ...TER S INITIAL FIRING IS TO INSURE A GOOD SEAL AFTER THE GASKETING SETTLES Fig 11 Fig 11A TYPE A FIREPLACE CONVERSION Fig 7 5 8 FIRECLAY FLUE LINER STOVEPIPE CONNECTOR SEALED AT THIMBLE HORIZONTAL 6 ST...

Страница 10: ...n fire ex tinguisherdirectlyintothestovethrough an appropriately placed cleanout If us ing a Halon extinguisher please re member that is totally displaces oxygen and could become a hazard in itself if...

Страница 11: ...DUCE A DANGEROUS CONDITION AND EVEN CAUSE A HOUSE FIRE IF ANY PORTION OF THE HEATER OR ANY CHIMNEY CONNECTOR GLOWS RED OR DIS COLORS THE HEATER IS BEING OVERFIRED CAUTION DO NOT OPERATE THIS HEATER WI...

Страница 12: ...on will cut the air supply and smother the fire Add a thin layer of coal preferably smaller chunks to the wood fire being careful not to disturb it too much or cut off the draft Then add a second heav...

Отзывы: