background image

11

FLOOR PROTECTOR

The stove must be placed on solid concrete, solid masonry, or when installed on a combustible 

fl

 oor, on a Type 2 

fl

 oor protector listed to standard 

UL 1618 with a minimum R value of 3.0 and a minimum thickness of 1” or equivalent. The 

fl

 oor protector is required to provide heat, live ember, and 

ash protection and must be of a non-combustible, continuous solid surface to protect against in

fi

 ltration of live embers and ash. For UL Listed 

fl

 oor 

protectors, refer to manufacturers  instructions for installation directions. Manufacturers of listed 

fl

 oor protectors include Imperial Metal Products and 

Hy-C among others. To calculate R-Values for alternative methods, see below for calculation methods.

Alternate materials may be rated with C-factor (Thermal Conductance) or k-factor (Thermal Conductivity) ratings which must be converted to R-value 
to determine if the alternate material meets the tested requirements. The following instructions provide the proper information and formulas for 
conversion to R-value.

To determine if alternate materials are acceptable follow this sequence.

1.  Convert material speci

fi

 cations to R-value:

 

a. R-value given — no conversion necessary

 

b. k-factor is given with a required thickness (T) in inches: R = 1/k x T

 

c. C-factor is given: R = 1/C

2.  Determine the R-value of proposed alternate 

fl

 oor protector:

 

a. Use formulas in step 1 above to calculate R-value of proposed material(s).

 

b. For multiple layers, add R-values of each layer to determine overall R-value.

3.  If the overall R-value of the 

fl

 oor protector system is equal to or greater than the 

fl

 oor protector speci

fi

 cations given, the alternate is acceptable.

De

fi

 nitions:

 

Thermal conductance (C) = 

 

=

 

Thermal conductivity (k) =  

 

 

=

 

Thermal resistance (R) =   

 

=

Example:

The specs of 

fl

 oor protector material should be 3/4-inch thick material with a k-factor of 0.84. The proposed alternative material is 4” brick with a 

C-factor of 1.25 over 1/8-inch mineral board with a k-factor of 0.29.

Step 1: 

Convert specs to R-value.

R = 1/k x T = 1/0.84 x 0.75 = 0.893 System must have a R-value of 0.893 = Rspecs

Step 2: 

Calculate R-value of individual components

4” Brick with C-factor = 1.25. R = 1/C = 1/1.25 = 0.80 = Rbrick

1/8-inch (0.125”) mineral board with k-factor = 0.29. R = 1/0.29 x 0.125 = 0.431 = Rmin.brd.

Step 3: 

Add R-values of components to get total R-value of system

Rmin.brd = 0.80 + 0.431 = 1.231 = Rsystem

Step 4: 

Compare Rsystem to Rspecs

Rsystem = 1.231 is larger than Rspecs of 0.893. System R-value exceeds the required speci

fi

 cations and therefore is an acceptable alternative.

BTU

(hr)(ft²)(°F)

W

(m²)(°K)

(Btu)(inch)

(hr)(ft²)(°F)

W

(m²)(°K)

BTU

(hr)(ft²)(°F)

(hr)(ft²)(°F)

BTU

(m²)(°K)

W

Содержание Logwood 2421

Страница 1: ...ME OR TRAILER SAVE THIS MANUAL FOR FUTURE REFERENCE THIS MANUAL WILL HELP YOU TO OBTAIN EFFICIENT DEPENDABLE SERVICE FROM THE HEATER AND ENABLE YOU TO ORDER REPAIR PARTS CORRECTLY KEEP IN A SAFE PLACE...

Страница 2: ...Dia For Sheet Metal Screws Adjustable Wrench Screw Driver Blade Type Gloves Safety Glasses MATERIALS 6 Elbow Collar and Thimble As Required 24 gauge min 1 2 Sheet Metal Screws No 10A x 1 2 6 Diameter...

Страница 3: ...this heater who is unfamiliar with the correct operation of the heater 9 For further information on using your heater safely obtain a copy of the National Fire Protection Association NFPA publication...

Страница 4: ...secure with screw in slot 7 After consulting the installation instructions for minimumclearancestocombustibles locateyourfloor protector accordingly and carefully place the stove in your selected loc...

Страница 5: ...ot pass through an attic roof space floor ceiling or similar concealed space Where pas sage through a wall or partition of combustible construction is desired the installation must conform with NFPA 2...

Страница 6: ...connected to a masonry chimney by passing through a combustible wall NFPA Standard 211 allows the following wall pass through systems 6 MASONRY CHIMNEY CONSTRUCTED TO NFPA 211 AIRTIGHT CLEANOUT DOOR...

Страница 7: ...opening in the combustible wall shall be covered and the chimney section supported on both sides with sheet steel supports which are at least 24 gauge 0 024 in thickness The sheet steel supports shall...

Страница 8: ...INIMUM FACTORY BUILT CHIMNEY LENGTH MINIMUM CHIMNEY CLEARANCES FROM MASONRY TO SHEET STEEL SUPPORTS AND COMBUSTIBLES 2 IN CHIMNEY LENGTH FLUSH WITH INSIDE OF FLUE NONSOLUBLE REFACTORY CEMENT MASONRY C...

Страница 9: ...inlet air control and pour a large quantity of coarse salt baking soda or cool ashes on top of the fire in the firebox CAU TION A chimney fire may cause ignition of wall studs or rafters which you tho...

Страница 10: ...RTH PLATE SLIDING DRAFT PLATE DOOR FRAME DOOR MAIN TOP LID LID SUPPORT LID LIFTER FLUE COLLAR SOLID FLUE DAMPER DOOR PINS DRAFT CONTROL KNOB HANDLE LATCH NUTS HANDLE EXTENSION HANDLE BRACKET OWNERS MA...

Страница 11: ...given with a required thickness T in inches R 1 k x T c C factor is given R 1 C 2 Determine the R value of proposed alternate floor protector a Use formulas in step 1 above to calculate R value of pro...

Страница 12: ...N WRITING ALWAYS GIVE THE FULL MODEL NUMBER WHICH IS ON THE NAME PLATE ATTACHED TO THE BACK OF THE HEATER WHEN ORDERING REPAIR PARTS ALWAYS GIVE THE FOLLOWING INFORMATION AS SHOWN IN THIS LIST 1 The P...

Отзывы: