7
D.
Minimum 7-foot (2.13m) clearance from any
grade when adjacent to public walkways.
E. Minimum 2-foot (0.61m) clearance above any
grass, plants, or other combustible materials.
F.
Minimum 3-foot (0.91m) clearance from an
forced air intake of any appliance.
G. Minimum 2-foot (0.61m) clearance below
eves or overhang.
H.
Minimum 1-foot (0.3m) clearance horizontally
from combustible wall.
I.
Must be a minimum of 3 foot (0.091m) above
the roof and 2 foot (0.61m) above the highest
point or the roof within 10 feet (3.05m).
G
VENT TERMINATION CLEARANCES
Determining where to install your new pellet
stove heater. To get the most efficient use of re-
circulated heat, you should consider a room that
is centrally located within your home. Choose a room that is large and open.
It is Extremely Important to maintain proper clearances from any combustible surfaces or materials in the room
where your heater will be located. You can find proper clearance measurements in this manual and on the
rating label of your pellet stove.
The pellet stove can be vented through an exterior wall or into an existing masonry or metal chimney if “PL” or
“L” vent pipe is used throughout existing chimney. Venting can pass through the ceiling and roof if approved
pipe is used. Where passage through a wall, or partition of combustible construction is desired, the installation
must conform to CAN/CSA-B365.
•
DO NOT OBTAIN COMBUSTION AIR FROM THE ATTIC, GARAGE OR ANY OTHER UNVENTILATED AREA. YOU MAY
OBTAIN COMBUSTION AIR FROM A VENTILATED CRAWL SPACE.
•
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
•
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER HEATER, FURNACE OR APPLIANCE.
•
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.
•
ONLY USE APPROVED MATERIAL FOR INSTALLATION, FAILURE TO DO SO MAY RESULT IN PROPERTY DAMAGE,
BODILY INJURY, OR EVEN DEATH.
This appliance is certified for use with listed 3 inch or 4 inch “PL” or “L” pellet venting products. The use of other
components other than stated herein could cause bodily harm, heater damage, and void your warranty.
HORIZONTAL EXHAUST VENT INSTALLATION
1. Locate your pellet stove in a location which meets the requirements of this manual, but in an area where it
does not interfere with the house framing, wiring, etc.
2.
Install a non-combustible hearth pad underneath the pellet stove. This pad should extend at least 6” (152mm)
in front of the unit.
3.
Place the pellet stove approximately 15” (381mm) away from the interior wall.
4.
Locate the center of the exhaust pipe of your unit. This point should then be extended to the interior wall of
your house. Once you have located the center point, on the interior wall, cut a 7” (175mm) diameter hole
through the wall.
5.
The next step is to install the wall thimble, refer to the instructions which come with the wall thimble for this
step.
6. Install the appropriate length of exhaust vent pipe into the wall thimble. See steps 11 and 12 when determining
the correct length of exhaust vent to use.
7. Outside Fresh Air is Mandatory when installing this pellet stove room heater in airtight homes and mobile
homes.
Be sure that the outside air vent has an approved cap on it to prevent rodents from entering. Be sure
to install in location that won’t become blocked with snow, etc.
8.
Connect the exhaust vent pipe to the exhaust outlet of your pellet stove.
9. Secure all vent joint connections with 3 screws. Seal the exhaust vent joint connections with high temperature
silicone sealant.
10.
Push the unit straight back to the interior wall, being sure to maintain the minimum clearances to combustibles
2” (51mm) to the back of the unit. Seal the annular space of the wall thimble and around the vent pipe with
high temperature silicone sealant.
11. The exhaust vent pipe must extend at least 12” (300mm) out past the exterior wall. Seal the annular space of
the wall thimble and around the vent pipe with high temperature silicone sealant.
12. Install an approved horizontal termination cap or if necessary install a 90° elbow and appropriate length of
vertical venting. An approved vertical vent cap is recommended.