T8-S / T8-X Initial Confi guration
11
T8 Con
fi
guration Code Chart
Code 1
: Jet-1 Button Con
fi
guration
Option 1: Jet-1 button operates Hi-Speed Pump-1
Option 2: Jet-1 button operates Lo-Speed and Hi-Speed Pump-1 *
Code 2
: Jet-2 Button Con
fi
guration
Option 1: Jet-2 button operates Lo-Speed Pump-1
Option 2: Jet-2 button operates Hi-Speed Pump-2
Option 3: Jet-2 button operates Lo-Speed and Hi-Speed Pump-2
Code 3
: T8-S / T8-X Decal & Jets-3 Button Con
fi
guration
Option 1: T8-S Decal (No Jets-3 / Air Blower)
Option 2: T8-X Decal, Aux button operates Air Blower
Option 3: T8-X Decal, Aux button operates Hi-Speed Pump-3
Code 4
: Power (Amperage) Con
fi
guration
Option 1: 50A Operation (No heat with Aux)
Option 2: 60A Operation (No power restriction)
Option 3: 50A Operation (No heat with P-2)
Option 4: 40A Operation (No heat with P-2, and Aux)
Option 5: 20A 120V Operation or 30A 240V Operation
(No heat with anything other then P-1 Lo-Speed)
Code 5
: Heater Operation
Option 1: Electric Heater operates with Lo-Speed Pump-1
Option 2: Electric Heater operates with Circulation Pump
Option 3: External Gas Heater operates with Lo-Speed Pump-1
Option 4: Electric Heater operates with Timed Circulation Pump **
Option 5: Electric Heater operates with Circulation Pump but uses
low-speed Pump-1 for the
fi
ltration cycle.
** - Code 1 should only be set to Option 2 if there is a second jet pump in the spa. If there
is only one jet pump, the default should be left so the unit operates as described later in
this manual, where the Jet-1 button operates Hi-Speed, and the Jet-2 button operates
Lo-Speed (avoiding ‘unused’ buttons).
** - When setting Code 5 to Option 4 it is important to make sure that Pump-1 is wired as
a single speed (Hi-Speed) pump - and not connected to the red (Lo-Speed) wire. In
addition the Circulation Pump cord will need to be recon
fi
gured to use the receptacles
red wire for the power line going to the circulation pump.