background image

Installation, Operation and Maintenance Manual

VariCool EZ-Fit

25

Subject to change without notice.

Maintenance Procedures

To  keep  the  unit  operating  safely  and  efficiently,  it  is 

recommended that a qualified service technician check the 

entire system at least once a year Check the system more 

frequently depending on use and surrounding conditions

Filters

To  keep  the  system  operating  as  efficiently  as  possible, 

change the air filters as required Be sure to inspect them 

at least one time per month when the system is in constant 

operation The unit is equipped with pleated throwaway air 

filters Make sure to replace them with the same type and 

size

NOTE: Do not attempt to clean throwaway air filters.

On units that have return air ductwork, remove the screws 

to the hinged filter access door (either side) Slide the filters 

out Replace the filters and slide back into position Reinstall 

the screws on the filter access door
On units that do not have return air ductwork, the filters can 

simply be lifted up to clear the lower frame edge and pulled 

towards you for removal
The filters are directionally specific for air flow, reinsert the 

new filter in the correct air flow direction

ELECTRICAL HAZARD

Turn  OFF  power  and  lockout  service 

before conducting any maintenance Keep 

hands, clothing and tools clear of electrical 

terminals

WARNING

Make  sure  to  keep  hands  and  clothing 

clear  of  any  moving  belts,  blowers  and 

motors while performing any maintenance 

Failure  to  do  so  could  result  in  death  or 

serious bodily injury

CAUTION

Any  maintenance  should  be  conducted 

by qualified HVAC service personnel only 

Potentially  hazardous  situations  may 

result  in  personal  injury,  equipment  or 

property damage

Lubrication

Belt Driven (DWDI)

The evaporator blowers have Pillow Block bearings which 

must be lubricated Lubricate the bearings using high quality 

lithium grease Each Pillow Block Bearing has a Zerk fitting 

to connect the grease gun to, for adding the grease  It is 

preferable  to  add  grease  to  the  blower  bearings  while 

rotating the shaft to ensure that grease forces the air pockets 

from  the  bearing,  allowing  a  grease  seal  throughout  the 

entire volume of the bearing Grease should be added until 

it slightly exudes through the bearing seals When enough 

grease is added, beads will form at the seals Once these 

beads are slightly visible, it indicates the bearing is full of 

grease Do not continue adding grease once these beads 

are visible

CAUTION

Over lubricating will cause the bearing to 

overheat and could cause the grease seal 

to blow out

Both excessive or inadequate grease may cause premature 

failure  Provided  there  is  some  grease  in  the  bearings  for 

lubrication, under lubrication is better than over lubrication 

as  grease  can  easily  be  added  but  not  removed Always 

allow a slight bead around the circumference of the seals to 

protect the bearing from foreign matter and helps flush out 

the bearing as well
Frequency of Lubrication depends on operating conditions 

Lubrication  should  be  checked  every  1-2  months  when 

blower is operating constantly

DWDI Blowers

Check that the blower wheel is tight on the shaft and does 

not contact the blower housing (DWDI type)
Check for restrictions or foreign material in the air circuit

Содержание VariCool EZ-Fit Series

Страница 1: ...VariCool EZ Fit Series Installation Operation and Maintenance Manual Effective March 2023 Variable Air Volume Water Cooled Water Source Heat Pump...

Страница 2: ......

Страница 3: ...ments 19 Water Piping 20 Electrical and Controls 21 Power Wiring 21 Transformer 22 Voltage Unbalance 22 High Duct Static Pressure Switch 22 Low Voltage Control Devices 22 Wall Display 22 BMS Applicati...

Страница 4: ...w unitedcoolair com website Scroll down to the Serial Search box and enter the unit serial number The serial number is a combination of the year month and sequential order of build date This will retu...

Страница 5: ...s IMPORTANT and INFORMATION will be used in areas where there is important information but not hazard related These instructions local codes and ordinances and applicable standards that apply to pipin...

Страница 6: ...litate handling most units or modules are shipped on a wooden skid Use caution when moving the unit or modules so that damage does not occur when moving each piece to the final installation location w...

Страница 7: ...apply to all air path configurations b Service clearances apply to all size units SERVICE ACCESS TOP VIEW Additional Clearance required for ECM DDP Fans Only SERVICE ACCESS SERVICE ACCESS FILTER ACCES...

Страница 8: ...fficient depth in water column to permit the condensate to flow from the drain pan Failure to have a sufficient drain trap will cause the condensate to overflow the drain pan or to cause the unit to s...

Страница 9: ...5 3 6 14x24 25x25 6 14 2 27 Dual Module Nominal Tons Blower Type Filter Size Evap Coil Compressor R 410A ECM iDDP DWDI Qty Size in Rows FPI Qty Lbs Ckt 30 8 4 15x20 20x20 4 14 4 7 40 12 18x25 4 14 4 1...

Страница 10: ...8 6280 6280 N A 35 77 1 2 60 1 8 105 1 8 3660 3780 N A 70 153 58 5 8 105 1 8 7320 7560 N A 40 45 77 59 1 2 112 4220 4350 N A 80 90 152 1 2 58 112 8440 8700 N A Single Module Nominal Tons Condensing Se...

Страница 11: ...8 3 4 60 1 8 34 460 80 90 2 77 34 1 2 78 1850 2 77 25 78 1450 4 38 1 2 59 1 2 34 460 1 Dimension in includes hardware 2 Dimension in does not include depth of removeable Filter Rack Filter rack depth...

Страница 12: ...notice that the middle beam supports the mid section of the unit Field supplied spring vibration isolators are to be installed on each corner of each frame per module 2 Channel Steel with Waffle Pads...

Страница 13: ...Z Fit 13 Subject to change without notice Figure 3C Base Option 2 Channel Steel with Waffle Pads Bottom View Figure 3D Base Option 2 Unit View Single Module Figure 3F Base Option Unit View Single Modu...

Страница 14: ...ide opposite the filters Each section is also alphabetically labeled so that each section can be mated properly Set the sections so that point A aligns to A B aligns to B C aligns to C Evaporator Sect...

Страница 15: ...flow between the evaporator and compressor condensing section For shipping purposes the refrigerant fittings are held in place to the cabinet using vinyl coated hangers and a mounting bracket These a...

Страница 16: ...they ensure perfect alignment of the mating section surfaces Once adjacent sections have been put into place use the included hardware to pull sections together until the curved surfaces of the 3D Int...

Страница 17: ...Installation Operation and Maintenance Manual VariCool EZ Fit 17 Subject to change without notice Figure 5A Single Module TYPICAL 8 PLACES...

Страница 18: ...Installation Operation and Maintenance Manual VariCool EZ Fit 18 Subject to change without notice Figure 5B Dual Module TYPICAL 16 PLACES...

Страница 19: ...or local codes Typically these units are installed using the mechanical room as the return air plenum However return ductwork can be applied Sufficient duct flange area exists on the filter frame for...

Страница 20: ...in case temperature approaches too close to the freezing point INFORMATION Do not reduce the water inlet or outlet connection size as this will restrict water flow and increase water pressure drop CA...

Страница 21: ...accordance with NEC National Electrical Code and NFPA National Fire Protection Agency most current versions as well as any applicable state or local codes INFORMATION The correct phase sequence of th...

Страница 22: ...ted and resolved for the unit power supply the building manager or owner should be notified of the issue to get the proper power supplied to the unit High Duct Static Pressure Switch A high duct stati...

Страница 23: ...lled shipped loose item The return air temp sensor should be placed in an area that can properly average all of the return air preferably right before the filters if possible For maintenance room plen...

Страница 24: ...pipe feeding condenser water to the unit A reduction of water flow from the unit head pressure control valve operation may cause nuisance trips Water flow switch trips will cause loss of water flow al...

Страница 25: ...jury CAUTION Any maintenance should be conducted by qualified HVAC service personnel only Potentially hazardous situations may result in personal injury equipment or property damage Lubrication Belt D...

Страница 26: ...nsioning below Figure 8 Belt Tensioning For proper tensioning use the following equation Deflection Belt Span 64 Belt span is in inches from center pulley to center pulley see Figure 8 Belt tension is...

Страница 27: ...higher operating costs or occupant discomfort The finned coils in a unit should be checked at least every six 6 months or more frequently based on experience of the specific application Before cleani...

Страница 28: ...rigerant system glass If the color of this indicator is green or blue the refrigerant is normal When the indicator is yellow an abnormal condition exists such as moisture within the refrigerant circui...

Страница 29: ...operating parameters to obtain the CFM 3 Water balance verification Ensure that the unit has 3 gpm per ton available to it at all times if a pump is of variable speed it must be able to ramp up its sp...

Страница 30: ...enser 5 Resolve incoming voltage issue 6 Resolve alarm condition Note Compressor internal overload may require an extended period of time 1 hour or more to reset Compressor short cycles 1 Reduced air...

Страница 31: ...mal expansion valve bulb is tight on suction line 5 Confirm thermal expansion valve bulb is located properly on suction line 6 Replace thermal expansion valve 7 Replace filter drier 8 Check filters an...

Страница 32: ...rly 2 Control wiring issue 3 Controls in an alarm condition 4 High or low pressure switch open 5 Compressor thermal overload open 1 Turn on and set controller for desired operation 2 Check wiring conn...

Страница 33: ...es due to i failure to install operate or maintain deliverables as directed in any instruction manual provided or under applicable law or regulation ii misuse abuse neglect or modification of a delive...

Страница 34: ...eliverable by Seller whichever occurs first Except as set forth in these terms Seller makes no representation or warranty of any type express or implied including any warranty of merchantability warra...

Страница 35: ...been adjusted to the voltage being applied Yes No 11 Has overcurrent protection breakers fuses been installed to match the unit nameplate requirement Yes No 12 Do all fans rotate freely Yes No 13 Does...

Страница 36: ...in the correct direction three phase units only NOTE If the evaporator blower motor runs backwards shut off all power to the unit Switch any two of the incoming power leads at the unit main power ter...

Страница 37: ...nce between the liquid line temperature and the saturation temperature corresponding to the liquid line pressure 11 Record the Amps for the evaporator blower motor and each compressor If the system is...

Страница 38: ...lters are in place clean usable Yes ____________ No ____________ Three Phase Measured Voltage L1 L2_____________ L2 L3_ ____________ L1 L3__________ Evaporator Blower Motor Rotation OK Yes ___________...

Страница 39: ...________ Suction Superheat _ ________ _ ________ _ ________ _ ________ Liquid Line Pressure psi________ psi________ psi________ psi________ Saturation Temperature Liquid Line Temperature F_________ F_...

Страница 40: ...in Tons Single Module 30 40 50 60 70 80 or 90 Nominal Cooling Capacity in Tons Dual Module e G Common to all f 3 208 230 3 60 4 460 3 60 g A Two Compressors D Four Compressors h T Traditional Cabinet...

Страница 41: ...7 00 PM Eastern Standard Time Saturday 8 00 AM 4 00 PM Call 717 843 4311 and Dial extension 165 This log must be kept with the unit It is the responsibility of the owner and or maintenance service con...

Страница 42: ...Installation Operation and Maintenance Manual VariCool EZ Fit 42 Subject to change without notice NOTES...

Страница 43: ...ITED WARRANTY United CoolAir Units are backed by a 1 year limited warranty on parts and a 5 year limited warranty on the compressor labor not included Maintenance items such as filters and belts are e...

Отзывы: