UNIT INSTALLATION
Install the unit using the following procedures Consideration
must be taken for proper condensate drain installation Slight
elevation of the VariCool unit may be required for installation
of the condensate drain Methods for elevating the VariCool
units are support rails, concrete pad(s), or spring isolators
1�
Once the unit’s sections have been moved to the
location of installation, locate the factory provided
mounting hardware, which has been pre-installed in the
holes where the sections will be connected together
2�
Using the appropriate size wrenches, remove the
mounting hardware and set in a safe location for
connecting the sections together during installation
Vibration Absorbers
When installing the VariCool on a concrete pad, support
rails, or other methods other then spring isolation, use of
vibration absorbers is recommended to prevent transmission
of possible vibration
3�
Figure 3 – Vibration Pads shows the recommended
points for vibration absorbent pads (field provided). We
recommend the use of a minimum 1” thick Neoprene
vibration absorbent pad under each point shown in
Figure 3 Models AV*09 through AV*16 only require the
pads under the corners only
FIGURE 3 – Vibration Pads
4�
Place each vibration isolator into positions shown in
Figure 3, and then move the compressor and cooling
coil section into the location of installation being careful
not to damage the quick connect refrigerant piping
5�
Fasten the cooling coil section bottom half to the
compressor section using the mounting hardware
removed in Step 2
6�
Allow the hardware to remain only hand tight until the
Blower Section is installed
INFORMATION
IMPORTANT: Before proceeding with
the installation of the Supply Air Blower
Section, we recommend connecting the
refrigerant quick connect connections
otherwise it may be difficult to make the
connections
Refrigerant Connections
The DX Cooling Coil section refrigerant circuit is connected
to the compressor/condenser section using quick-connect
refrigerant connections If the VariCool unit is a split system
with a Remote Air Cooled Condenser, refer to the section on
Split Systems If the VariCool was ordered as a packaged
system, connecting refrigerant tubing will be fairly simple
The quick connect fittings are self-sealing so they do not
permit refrigerant flow until they are completely tight. Follow
these steps for a packaged system:
7�
Remove the caps on the quick connect refrigerant
lines
8�
Using a small amount of National 150 or 3G brand
refrigerant oil, lightly lubricate the threads of the
quick connect fittings. (5 to 6 droplets of oil are
recommended)
9�
Align each quick connect fitting and hand thread the
Female Quick Connect fittings onto the Male Quick
Connect fittings as shown in Figure 4 – Quick Connect.