TECHNICAL SPECIFICATION
Supply Voltage
/- 10% 50/ 60 Hz
Switching Capacity
6kW Max.
Ramp On-Time
1 – 5 Seconds
Pedestal Value
0 – 40% (Conduction Angle)
Current Consumption (control circuit)
20mA
Terminals
6.0mm
2
Rising Clamp
Operating Temperature
-20 to 40°C
Protection Rating
IP65
Gland Diameter
Max Cable Entry 2.5mm²
Enclosure Dimensions (W x L x H)
130x130x75 (mm
INTRODUCTION
The Soft Start with contactor is a soft start controller designed to be used on both inductive and resistive loads. The Soft
Start model has a predetermined ramp up time of 1 to 5 seconds. It also has a pedestal which is used to adjust the start
of the sine wave the range of this is 0-40%.
The soft start is used to help eliminate high inrush current. This helps protect the Load from getting damaged and
eliminates nuisance MCB trips.
INSTALLATION
SAFETY FIRST!
Please read these instructions before installing and operating this product.
The Soft start unit should be positioned with the three fixed cable glands facing down and securely fixed via the four
mounting holes accessible from the front of the unit. Round cable is recommended to avoid water ingress. To ease
installation, a mounting template is provided opposite to locate the 4 mounting hole centres.
Содержание SSC-6kW
Страница 4: ...WIRING DIAGRAM ...