background image

Model No. : UT-1407

PAGE : 6

Parameter

Description

Range

Default Value

CONFIGURATION MODE PARAMETER

Password for Parameter Setting

Values between

000

Password for Configuration Parameter

000

to

999

Scroll the digit by

key, increase by

key

1.

CONFIGURATION MODE

non

1tY

PAr

000

Ent
pas

Temperature Alarm-1 type

To Activate Buzzer on this value.

Change the type by

key or

key.

Lo

AL1

tmp

-

: Active in Low

Lo

Lo

: Active in Very Low

vLo

: Active in Very High

vH1

: Active in High

H1

: Disabled

dsb

Temperature Alarm-2 type

To Activate Buzzer on this value.

HI

AL2

tmp

-

: Active in Low

H

I

Lo

: Active in Very Low

vLo

: Active in Very High

vH1

: Active in High

H1

: Disabled

dsb

Humidity Alarm-1 type

To Activate Buzzer on this value.

Lo

AL1

rH

: Active in Low

Lo

Lo

: Active in Very Low

vLo

: Active in Very High

vH1

: Active in High

H1

: Disabled

dsb

Humidity Alarm-2 type

To Activate Buzzer on this value.

HI

AL2

rH

: Active in Low

HI

Lo

: Active in Very Low

vLo

: Active in Very High

vH1

: Active in High

H1

: Disabled

dsb

Pressure Diff. Alarm-1 type

To Activate Buzzer on this value.

Lo

AL1

prs

: Active in Low

Lo

Lo

: Active in Very Low

vLo

: Active in Very High

vH1

: Active in High

H1

: Disabled

dsb

Pressure Diff. Alarm-2 type

To Activate Buzzer on this value.

HI

AL2

prs

: Active in Low

HI

Lo

: Active in Very Low

vLo

: Active in Very High

vH1

: Active in High

H1

: Disabled

dsb

01

Add

nod

Node Address

Node address for Communication.

Scroll the digit by

key, increase by

key

Values between

01

00

to

99

Baud Rate.

Baud Rate for Communication.

Change the Value by

key or

key

rAt

bud

96

Change the type by

key or

key.

Change the type by

key or

key.

Change the type by

key or

key.

Change the type by

key or

key.

Change the type by

key or

key.

48

96

192

: Baud rate 4800
: Baud rate 9600
: Baud rate 19200

96

Parity

Parity for Communication.

Change the Value by

key or

key

Evn

odd

non

: Even Parity
: Odd Parity
: None

non

+91 94273 01436

Sales:

www.utplindia.in

Website:

Sure for service with hi-end

versal

nology

Uni

Tech

Sure for service with hi-end

versal

nology

Uni

Tech

E-mail :

[email protected]

Add.-78/1/Z/3, Makarpura GIDC, Makarpura, Vadodara

Ph

:

+91 7046223333

Содержание UT-1407

Страница 1: ...TEMP HUMIDITY P AND TIME INDICATOR 91 94273 01436 Sales www utplindia in Website Sure for service with hi end versal nology Uni Tech Sure for service with hi end versal nology Uni Tech E mail sales u...

Страница 2: ...LEDs with High and Low alarm led outputs and are settable using programm ing modes Unitech Instrument s Clean Room Indicator is designed to display Temperature Humidity and Room Pressure Difference i...

Страница 3: ...Mode ACK BUZZER UP INCREMENT Press to change Temp Set point in Normal Mode and increase selected digit or value in Programming Mode ENTER Press to change Set point in Normal Mode and dP to accept mod...

Страница 4: ...occes value decimal point Hi Low set point Programmable parameter Modbus RTU RS 485 Isolated communications Baud rate Parity Node address stop bit Communication Protocol Full range as per input select...

Страница 5: ...ch E mail sales utplindia in Add 78 1 Z 3 Makarpura GIDC Makarpura Vadodara Ph 91 7046223333 CAUTION WIRING CONSIDERATION SHIELDED TWISTED PAIR WIRE IS USED FOR ALL ANALOG I P PROCESS SENSORS RTD THER...

Страница 6: ...as 200 sp1 tmp tmp sp2 Prs sp2 sp1 Prs 400 200 sp1 rH rH sp2 400 020 050 UP Password Protected 1br MOD CAL 000 Ent pas Lo Prs prs H1 Password Protected Press key Press key Press key Press key no FCt S...

Страница 7: ...vH1 Active in High H1 Disabled dsb Pressure Diff Alarm 1 type To Activate Buzzer on this value Lo AL1 prs Active in Low Lo Lo Active in Very Low vLo Active in Very High vH1 Active in High H1 Disabled...

Страница 8: ...the current time in MINUTE Clock second setting parameter Change the value by key or key Set the current time in SECONDS Clock format setting parameter Change the value by key or key Set the current...

Страница 9: ...m 2 Set point Values between Set point for buzzer activation 000 to 999 Scroll the digit by key increase by key 050 sp2 prs 020 050 oFF tm 000 Temperature Offset Values between Offset to Temp value 00...

Страница 10: ...lues between 000 to 999 New Desired Password Old Password 000 Scroll the digit by key increase by key Values between 000 to 999 Existing Password As reqd 000 Pas oLd 91 94273 01436 Sales www utplindia...

Страница 11: ...TION DETAILS z z BAUD RATE PARITY DATABIT NODE ADDRESS STOP BIT 9600 NONE 8 1 1 REGISTER ADDRESS FOR MODBUS RTU PROTOCOL z z SR NO PARAMETERS ABSOLUTE ADDRESS ACCESS TYPE 1 TEMPERATURE VALUE 40001 REA...

Страница 12: ......

Отзывы: