11. INSTALLINg DUCT WORK

Install  all  duct-work  to  meet  current 

standard:

• ASHRAE/NFPA  90,  Standard  for  Installation  of 

Warm air Heating and air Systems.

• State, provincial, and local codes Failure to follow 

these standards could reduce air flow or increase 

air leakage, resulting in reduced system perfor-

mance or equipment damage. Properly size duct 

work based on heat loss and heat gain calcula-

tions. Doing so assures:

• Good heating and cooling installations;
• Delivery of required circulating air. 

   Design duct systems within the maximum external 

static pressure limits indicated in Table 1.

0.1

0.2

0.3

0.4

0.5

0.6

0.7

HIgH

560

530

500

460

415

355

295

MED-HI

450

425

400

370

335

300

-

MED-LO

365

350

330

310

270

-

-

LOW

315

290

275

-

-

-

-

HIgH

705

375

635

585

535

470

405

MEDIUM

650

620

585

540

485

425

-

LOW

520

510

490

465

430

-

-

HIgH

920

880

840

800

750

700

640

MEDIUM

775

760

735

705

665

625

-

LOW

580

565

550

530

-

-

-

HIgH

1060

1020

980

935

885

830

770

MEDIUM

840

825

810

790

765

730

-

LOW

735

725

715

700

-

-

-

SWaC02412

SWaC03012

SWaC01212

EXTERNAL STATIC PRESSURE (in. wg.)

SWaC01812

UNIT MODEL

SPEED TAP

LD13530

TABLE 1 -

 SWaC FaN PERFORMaNCE

SUPPLY AIR DUCT WORK

Duct  attaching  hardware  must  only  be  used  on  the 

supply air outlet flanges. Refrigeration tubing is located 

under the top panel near these flanges. Do not drill or 

use screws in this area.

Supply  air  duct  (plenum)  connection 

must be at least the same size as the 

furnace supply air opening. Seal supply 

air duct work to furnace casing, walls, 

ceilings or floors.

RETURN AIR DUCT WORK & FILTERS

All return air entering the unit must be filtered. Refer to 

Section 15 for filter size and instructions on installing the 

filter rack. The return air filter must be supplied by the 

installing contractor. The return duct should be sealed 

to the unit casing and terminate outside the space con-

taining the furnace.

Содержание SWAC-R22

Страница 1: ...its Supersedes 145 26 IOM1 708 Form 145 26 IOM1 908 UNIT MODEL SWAC R22 Hot Water Heating Electric Cooling INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS Cooling Capacities 12 000 18 000 24 000 30 00...

Страница 2: ...It is essential that prior to performing any task on this equipment this individual shall have read and understood this document and any referenced materials This individual shall also be familiar wit...

Страница 3: ...uld expose the worker the equipment and the building and its inhabitants to the risk of injury or property damage The instructions are written assuming the individual who will perform this work is a f...

Страница 4: ...atic Wiring Diagram 17 Warranty Policy 19 SWAC models provide a complete air conditioning and heating system as an all in one package Specifically de signed for convenient through the wall installatio...

Страница 5: ...ep this equipment Pass these documents on to later purchases or Users Throughout this Installer s Information Manual we frequently use the word you when referring to the person responsible for applica...

Страница 6: ...ce over any instructions in this manual Be sure to consult Authorities having jurisdiction over air conditioning and heating installations Local code authorities for information on electrical wiring 4...

Страница 7: ...which must mate with the back of the unit are perfectly vertical Correct this if necessary or the unit will not seal properly against the wall sleeve A roll of 1 inch wide x inch thick self adhesive r...

Страница 8: ...JOHNSON CONTROLS 8 FORM 145 26 IOM1 908 LD13530 FIG 1 Wall Sleeve Assembly...

Страница 9: ...lf drilling sheet metal screws through the flange standing up at the back of the unit top These two screws will screw into the wall sleeve Recommend Lintel where required on wall opening gasket INSTAL...

Страница 10: ...10 490 465 430 HIgH 920 880 840 800 750 700 640 MEDIUM 775 760 735 705 665 625 LOW 580 565 550 530 HIgH 1060 1020 980 935 885 830 770 MEDIUM 840 825 810 790 765 730 LOW 735 725 715 700 SWaC02412 SWaC0...

Страница 11: ...entire filter frame and trim off any burrs left where the opening was snipped out BOTTOM RETURN PLENUMS When a bottom return plenum is used snip out the pre punched 11 x 20 inch opening in the bottom...

Страница 12: ...in lower connection water out upper connection The coil design is self draining and self venting provision for draining the water supply line and venting the water return line must be field supplied T...

Страница 13: ...10 0 47 0 0 17 1 2 0 17 1 1 14 8 20 SWAC02412 208 230 1 60 1 13 2 59 0 0 17 1 2 0 25 1 5 19 2 30 SWAC03012 208 230 1 60 1 15 7 69 0 0 25 1 5 0 33 1 9 23 03 35 16 INSTALLING ELECTRICAL WIRING Provide...

Страница 14: ...f these questions 1 Is the unit level 2 Have you cleared away all loose construction and insulation materials 3 Is unit installed within proper clearances to com bustible materials See Section 6 4 Doe...

Страница 15: ...lure to seal holes could result in reduced system performance LOCK ALL ELECTRICAL POWER SUP PLY SWITCHES IN THE OFF POSITION BEFORE SERVICING THE UNIT FAIL URE TO DISCONNECT POWER SUPPLY MAY RESULT IN...

Страница 16: ...require oiling 4 Inspect evaporator and condenser coils for accu mulations of dirt and debris and clean as required If the coils appear dirty clean them using mild detergent or a commercial coil clea...

Страница 17: ...8 17 Johnson Controls Unit Cooling Capacity BTU HR R 22 Refrigerant Charge SWaC 1212 2 lb 14 oz SWaC 1812 3 lb 14 oz SWaC 2412 4 lb 8 oz SWaC 3012 4 lb 14 oz FIG 4 SCHEMATIC WIRING DIAGRAM LD13535 22...

Страница 18: ...JOHNSON CONTROLS 18 FORM 145 26 IOM1 908 NOTES...

Страница 19: ...eat exchanger will be furnished or at our sole option a credit for the replacement heat exchanger may be allowed Labor and other expenses involved in replacing the heat exchanger are not covered by th...

Страница 20: ...without notice Printed in U S A Copyright 2008 by Unitary Products Group All rights reserved Form 145 25 IOM1 908 Supersedes 145 25 IOM1 708 York PA 17405 P O Box 1592 York PA 17405 Engineered System...

Отзывы: