background image

268882-UIM-A-0407

14

Unitary Products Group

VENT CLEARANCES

A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

††

12 inches (30 cm) up from the bottom edge of the structure for Two-pipe (direct vent) applications per ANSI Z223.1 / NFPA 54, National Gas Code.

‡ 

Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and the distance between the top of the vent termina-

tion and the underside of the veranda, porch, or deck is greater than 1 foot (30 cm) as specified in CSA B149.1-00.
A vent shall not terminate less than 1 foot (30 cm) above a grade level.
Any fresh air or make up inlet for dryer or furnace area is considered to be forced air inlet.
Avoid areas where condensate drippage may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
A terminus of a vent shall be fitted with a cap in accordance with the vent manufacturer’s installation instructions, or in accordance with the installation instructions for a 
special venting system.
IMPORTANT: Consideration must be given for degradation of building materials by flue gases. Sidewall termination may require sealing or shielding of building surfaces 
with a corrosion resistant material to protect against combustion product corrosion. Consideration must be given to wind direction in order to prevent flue products and/or 
condensate from being blown against the building surfaces. If a metal shield is used it must be a stainless steel material at a minimum dimension of 20 inches. It is rec-
ommended that a retaining type collar be used that is attached to the building surface to prevent movement of the vent pipe.
Responsibility for the provision of proper adequate venting and air supply for application shall rest with the installer.
Vent shall extend high enough above building, or a neighboring obstruction, so that wind from any direction will not create a positive pressure in the vicinity of the vent.

 FIGURE 15:  

Home Layout

L

E

D

B

V

V

V

X

V

B

V

J

X

B

B

B

V

V

F

V

C

B

X

V

I

V

G

H

A

M

K

OPERABLE

FIXED
CLOSED

VENT TERMINAL

AIR SUPPLY

AREA WHERE TERMINAL IS NOT PERMITTED

FIXED
CLOSED

Direct Vent Terminal Clearances

Canadian Installations

1,3

US Installation

2,3

A. Clearance above grade, veranda, porch, deck, or

balcony

12 inches (30 cm)

12 inches (30 cm)

B. Clearance to window or door that may be opened

12 inches (30 cm) for models 

100,000 BTUH (30 kW), 

36 inches (91 cm) for models >100,000 BTUH (30 kW)

Two-pipe (direct vent) applications: 9 inches (23 cm) 
for models <50,000 BTUH (15 kW), 12 inches (30 cm) 
for models >50,000 BTUH (15 kW). ††

C. Clearance to permanently closed window

12 inches (30 cm)

12 inches (30 cm)

D. Vertical clearance to ventilated soffit located 

above the terminal within a horizontal distance 
of 2 feet (61 cm) from the center line of the terminal

12 inches (30 cm) or in accordance with local
installation codes and the requirements of the gas
supplier.

12 inches (30 cm) or in accordance with local 
installation codes and the requirements of the gas sup-
plier

E. Clearance to unventilated soffit

12 inches (30 cm) or in accordance with local
installation codes and the requirements of the gas
supplier

12 inches (30 cm) or in accordance with local
installation codes and the requirements of the gas
supplier

F. Clearance to outside corner 

12 inches (30 cm) or in accordance with local
installation codes and the requirements of the gas
supplier

12 inches (30 cm) or in accordance with local
installation codes and the requirements of the gas
supplier

G. Clearance to inside corner

3 feet (91 cm)

3 feet (91 cm)

H. Clearance to each side of center line 

extended above meter/regulator assembly

Above a meter/regulator assembly within 3 feet (91 cm) 
horizontally of the vertical center-line of the regulator 
vent outlet to a maximum vertical distance of 15 feet 
(4.5 cm) above the meter/regulator assembly.

Above a meter/regulator assembly within 3 feet (91 
cm) horizontally of the vertical center-line of the regula-
tor vent outlet to a maximum vertical distance of 15 
feet (4.5 cm) above the meter/regulator assembly.

I.

Clearance to service regulator vent outlet

3 feet (91 cm)

3 feet (91 cm) or in accordance with local installation 
codes and the requirements of the gas supplier.

J. Clearance to nonmechanical air supply inlet to

building or the combustion air inlet to any other
appliance

12 inches (30 cm) for models 

100,000 BTUH (30 kW), 

36 inches (91 cm) for models >100,000 BTUH (30 kW)

Two-pipe (direct vent) applications: 9 inches (23 cm) 
for models <50,000 BTUH (15 kW), 12 inches (30 cm) 
for models >50,000 BTUH (15 kW).

K. Clearance to a mechanical supply inlet

6 feet (1.83 m)

3 feet (91 cm) above if within 10 feet (3 cm) 
horizontally

L. Clearance above paved sidewalk or paved 

driveway located on public property

7 feet (2.13 m)†

7 feet (2.13 m) or in accordance with local installation 
codes and the requirements of the gas supplier.

M. Clearance under veranda, porch, deck, or balcony

12 inches (30 cm)‡

12 inches (30 cm) or in accordance with local installa-

tion codes and the requirements of the gas supplier

.

1.

In accordance with the current CSA B149.1-00, Natural Gas and Propane Installation Code.

2.

In accordance with the current ANSI Z223.1 / NFPA 54, National Gas Code.

3.

In accordance with the current ANSI Z21.47 * CSA 2.3 American National Standard.

Содержание DGAD

Страница 1: ...START UP AND ADJUSTMENTS 20 WIRING DIAGRAM 28 LIST OF FIGURES Combustible Floor Base Accessory 5 Transition Kit Assembly 6 Attachment to Structure 6 Blend Air Bracket 6 Dimensions 7 Mobile Home Filte...

Страница 2: ...ration has the combustion air pipe connected to the burner box and terminating in an attic or crawl space The vent pipe terminates external to the building The vent pipe and combustion air pipe will n...

Страница 3: ...the side wall exhaust vent termination is less than seven 7 feet above finished grade in the area of the venting including but not limited to decks and porches the following require ments shall be sat...

Страница 4: ...t 0 635 cm m so that condensate will flow towards the drain 4 If this unit is installed in an unconditioned space and an extended power failure occurs there will be potential damage to the conden sate...

Страница 5: ...be the same dimensional size as the rectangu lar opening in the base of the furnace The duct system is a very important part of the installation If the duct system is improperly sized the furnace will...

Страница 6: ...rnace with screws The fur nace and the transition kit are then placed on the cooling coil cab inet and secured with screws IMPORTANT The furnace transition kit when used and the cooling coil cabinet M...

Страница 7: ...return air duct and plenum are not required by state local or regional codes then the filter can be attached to the top of the fur nace as shown in Figure 6 IMPORTANT When replacing an existing the fu...

Страница 8: ...PORTANT Plan your gas supply before determining the correct gas pipe entry Use 90 degree service elbow s or short nipples and con ventional 90 degree elbow s to enter through the cabinet access holes...

Страница 9: ...e placed on the octagon hub located on the gas inlet side of the valve Placing a wrench to the body of the gas valve will damage the valve causing improper oper ation and or the valve to leak The gas...

Страница 10: ...e leads into the box using a protective bushing where the wires pass through the furnace panel After making the wiring con nections replace the wiring box cover and screws Refer to Figure 10 3 The fur...

Страница 11: ...ion that can be installed in a Manufactured Mobile Home Rubber couplings and hose clamps may be used to provide a secure connection between the furnace PVC pipe and ABS pipe The rubber couplings can b...

Страница 12: ...less than the 90 foot maximum equivalent length of 3 pipe allowed for that model and is thus acceptable Dimensions are those required in Standard ASTM D 3311 NOTE Sidewall vent terminal may be used f...

Страница 13: ...ons Primer and cement must conform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight and watertight seal NOTE Be sure to visually check each pipe connec...

Страница 14: ...ons 9 inches 23 cm for models 50 000 BTUH 15 kW 12 inches 30 cm for models 50 000 BTUH 15 kW C Clearance to permanently closed window 12 inches 30 cm 12 inches 30 cm D Vertical clearance to ventilated...

Страница 15: ...ly on the 2 5 1 cm 45 PVC street elbow as shown in Figure 16 3 Locate the rubber condensate hose in front of the blower access panel 4 Slide the hose through the hole in the top cover and insert the h...

Страница 16: ...ir intake pipe should be located either through the wall horizontal or side vent or through the roof vertical vent Care should be taken to locate side vented systems where trees or shrubs will not blo...

Страница 17: ...lar Home Installations Only GABLE VENT GAS VENT SOFFIT VENT VENTILATED ATTIC TOP ABOVE INSULATION OPTIONAL INLET a OUTLET AIR a VENTILATED CRAWL SPACE GAS WATER HEATER VENTILATED ATTIC TOP ABOVE INSUL...

Страница 18: ...4 5 of these instructions Ventilated Combustion Air Modular Home Installations Only The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirement...

Страница 19: ...028 15158 000 9 Drain tube Vent system Horizontal RT Before Tee Horizontal LT 028 15168 000 3 Drain tube Inducer Down flow 028 15169 002 5 Drain tube After Tee Down flow 028 15175 000 4 Drain tube Rai...

Страница 20: ...air blower heat exchanger or a blocked vent pipe connection Corrective action is required These are manual reset controls that must be reset before operation can continue PRESSURE SWITCHES This furna...

Страница 21: ...l start and come up to speed Shortly after inducer start up the hot surface igniter will glow for about 17 seconds b After this warm up the ignition module will energize open the main gas valve c Afte...

Страница 22: ...0 then divided by the time it took to measure 0 10 m3 of gas from the gas meter For Propane LP Gas multiply the Heat content of the gas MJ m3 or Default 93 15 times 0 10 m3 of gas measured at the gas...

Страница 23: ...erence atmo spheric pressure Refer to Figure 39 for connection details IMPORTANT The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw Loosening or tighten...

Страница 24: ...must be long enough to adequately cool the furnace but not so long that cold air is blown into the heated space The fan off timing may be adjusted by positioning the jumper on two of the four pins WIT...

Страница 25: ...as valve dirty or faulty flame sensor faulty hot surface ignitor or burner problem may cause this The furnace will lock out for one hour and then restart 8 RED FLASHES This fault is indicated if the f...

Страница 26: ...20 Low 752 745 731 718 698 652 602 580 536 496 21 21 21 20 20 18 17 16 15 14 80 High 2071 2026 1981 1935 1864 1796 1713 1625 1532 1401 59 57 56 55 53 51 48 46 43 40 Med High 1583 1590 1569 1554 1532...

Страница 27: ...s Obtain the airflow values at 0 50 w c 0 124 Pa 0 60 w c 0 149 kPa ESP Airflow 0 50 2034 CFM 58 m3 min Airflow 0 60 1924 CFM 54 m3 min Subtract the airflow 0 50 w c 0 124 kPa from the airflow 0 60 w...

Страница 28: ...rinted in U S A 268882 UIM A 0407 Copyright by York International Corp 2007 All rights reserved Supersedes 167809 UIM C 0506 Unitary P O WIchita Products Box KS Group 19014 67204 9014 SECTION X WIRING...

Отзывы: