560.20-N1Y
035-16734-000
4
Unitary Products Group
7.
These units should be installed in accordance with:
a.
Regulations of National Board of Fire Underwriters,
local utility or other authorities having jurisdiction.
b.
Standards for air conditioning systems, National Fire
Association Pamphlet # 90.
c.
National Warm Air Heating and Air Conditioning
Association Manuals, which ever is applicable.
d.
Wiring must conform to provisions of National Elec-
trical Code (NFPE Pamphlet # 70) and local ordi-
nances.
INSTALLATION
ACCESSORIES
Refer to the following instructions for installation of accesso-
ries:
•
Form 550.13-N10.1U Electric Heat
•
Form 550.13-N10.2U Supply Air Plenum
•
Form 550.13-N10.3U Return Air Grille
•
Form 550.12-N10.7U Hot Water Coil and Non-Freeze
Steam Coil
•
Form 560.20-N1.5 Water Regulating Valve
TABLE 1: APPLICATION DATA
LIMITATION
MINIMUM
1
MAXIMUM
1
P
OWER
S
UPPLY
, V
OLTS
208/230-1-60
187
252
208/230-3-60
187
252
460-3-60
432
504
S
UPPLY
A
IR
, CFM
C2ED060
1600
2400
C2ED090
2400
3600
C2ED120
3200
4800
C2ED180
4800
7200
A
IR
T
EMPERATURE
E
NTERING
C
OOLING
C
OIL
°F
Wet Bulb
57
72
Dry Bulb
65
95
C
ONDENSER
W
ATER
, GPM
C2ED060
4
20
C2ED090
6
30
C2ED120
8
40
C2ED180
12
60
C
ONDENSER
W
ATER
-S
IDE
W
ORKING
P
RESSURE
, PSIG
20
2
150
3
L
EAVING
C
ONDENSER
W
ATER
T
EMPERATURE
4
, °F
60
115
1.
Utilization Range “A” in accordance with ARI Standard 110.
2.
The water pressure must be great enough to overcome the pressure drop of the condenser and the condenser water piping.
3.
Although the water side is only leak tested for 150psig, the maximum water-side working pressure of the condenser is 450 psig.
Class 150 fittings in the unit’s condenser water piping are good for 300 psig. For 300 psig applications, a sealing material (Lock-
tite or equivalent) must be applied to all threaded connections to assure a leak-tight installation. The water regulating valve acces-
sories are limited to a maximum 150 psig.
4.
The limitation for entering condenser water temperature will vary with condenser water GPM.
THIS PRODUCT MUST BE INSTALLED IN
STRICT COMPLIANCE WITH THE ENCLOSED
INSTALLATION INSTRUCTIONS AND ANY
APPLICABLE LOCAL, STATE, AND NATIONAL
CODES INCLUDING BUT NOT LIMITED TO,
BUILDING, ELECTRICAL AND MECHANICAL
CODES.