manualshive.com logo in svg
background image

560.20-N1Y

035-16734-000

16

Unitary Products Group

2.

A movable flange with one set screw

After the movable flange has been rotated to the proper num-
ber of “turns open”; the setscrew should be tightened against
the flat on the barrel to lock the movable flange in place.  If
the pulley includes a locking collar, the locking collar must be
loosened to adjust the setting of the movable flange.

Note the following:

1.

The supply air CFM must be within the limitations shown 
in Table 1.

2.

All pulleys can be adjusted in half turn increments.

3.

The tension of the belt should be adjusted for a deflec-
tion of 3/16 of an inch per foot of belt span with and 
applied force of 2 to 3 pounds.  Moving the blower motor 
mounting plate makes this adjustment.   Refer to Figure 
8 turning the adjustment bolt (B) moves the motor 

mounting plate up or down.

Two hex nuts (A) have to be loosened to move the 
mounting plate and retighten after the mounting plate 
has been moved to the proper position.

4.

All pulleys are factory aligned.

5.

All supply air motor pulleys are factory set at 2 “turns 
open”.

After the supply air blower motor is operating, adjust the
resistances in both the supply and the return duct systems to
balance the supply and the return duct system to balance the
air distribution throughout the conditioned space.  The job
specifications may required that this balancing be done by
someone other than the equipment installer.

To check the supply air CFM after the initial balancing has
been completed:

1.

Drill two 5/16-inch holes in the side panel as shown in 
Figure 9.

2.

Insert at least 8” of 1/4 inch tubing into each of these 
holes for sufficient penetration into the airflow on both 
sides of the evaporator coil.

NOTE:The tubes must be inserted and held in a position per-
pendicular to the air flow so velocity pressure will not affect
the static pressure readings.  Filters must be removed on the
CED060 to get accurate readings.

3.

Using an inclined manometer, determine the pressure 
drop across a dry evaporator coil.  Since the moisture on 
an evaporator coil may vary greatly, measuring the pres-
sure drop across a wet coil under field conditions would 
be inaccurate.  To assure a dry coil, The refrigeration 
system should be de-activated while the test is being 
run.

4.

Knowing the pressure drop across a dry coil, the actual 
CFM through the unit can be determined from the curve 
in Figure 10.

If the CFM is above or below the specified value, the supply
air motor pulley may have to be re-adjusted.  After on hour of

TABLE 12: SUPPLY AIR BLOWER MOTOR PULLEY 

ADJUSTMENT

TURNS

OPEN

1

1.

Pulleys can be adjusted in half-turn increments.

BLOWER RPM

DRIVE RPM RANGE AND UNIT SIZE

CED060

810-110

RPM

CED190

655-880

RPM

CED120

700-950

RPM

CED180

625-810

RPM

0

1110

880

950

810

1

1050

835

900

773

2

990

790

850

736

3

930

745

800

699

4

870

700

750

662

5

810

655

700

625

NEVER LOOSEN THE TWO NUTS (C OF FIG-
URE 8) THIS COULD CAUSE THE MOTOR 
MOUNT TO LOOSEN AND BREAK THE BELT.

 FIGURE 8 :  TYPICAL MOTOR MOUNTING 

ASSEMBLY

A

M O T O R

M O U N T

B

C   ( D O   N O T   L O O S E N )

M O T O R

Содержание C*ED060A Series

Страница 1: ...N 3 LIMITATIONS 3 INSTALLATION 4 OPERATION 23 A Complete Table of Contents on Following Page INSTALLATION INSTRUCTION SAVE THIS MANUAL SINGLE PACKAGE WATER COOLED AIR CONDITIONERS EMBASSSY SERIES MODE...

Страница 2: ...ANGE CED060 090 120 15 6 BLOWER ARRANGE CED180 1 15 7 BLOWER ARRANGE CED180 2 3 4 15 8 TYPICAL MOTOR MOUNTING ASSEMBLY 16 9 PROBE LOCATIONS 17 10 CFM CURVE 17 11 SUPPLY AIR DUCT CONNECTION 18 12 COILS...

Страница 3: ...utions are given to prevent equipment damage Warnings are given to alert the installer that personal injury and or equipment damage may result if the installation procedure is not handled properly INS...

Страница 4: ...00 4800 C2ED180 4800 7200 AIR TEMPERATURE ENTERING COOLING COIL F Wet Bulb 57 72 Dry Bulb 65 95 CONDENSER WATER GPM C2ED060 4 20 C2ED090 6 30 C2ED120 8 40 C2ED180 12 60 CONDENSER WATER SIDE WORKING PR...

Страница 5: ...ned with sound absorbing material c Support the unit on a separate floor structure form that of the conditioned space d Place a non deteriorating sound isolation pad under the entire unit base CLEARAN...

Страница 6: ...8 3 8 1 2 Fins Aluminum per inch 13 13 13 12 CENTRIFUGAL BLOWER FORWARD CURVE Diameter x Width inches 10 x 10 15 x 15 15 x 15 18 x 18 MOTORS 2 Nominal HP Rating 3 4 1 460 3 60 1 1 2 2 3 FILTERS THROWA...

Страница 7: ...67 94 65 6 0 10 2 89 63 6 4 9 9 74 62 86 62 5 8 9 4 81 61 6 2 9 1 68 57 77 60 5 7 8 6 73 59 6 1 8 4 120 3000 86 72 30 139 93 8 4 11 2 132 90 9 0 10 8 80 67 128 90 8 2 10 5 121 87 8 8 10 1 74 62 118 8...

Страница 8: ...80 67 84 61 6 8 9 5 78 58 7 3 9 1 74 62 76 59 6 6 8 8 71 56 7 1 8 4 68 57 68 57 6 5 8 1 64 55 7 0 7 8 120 3000 86 72 30 124 87 9 6 10 4 116 85 10 3 10 0 80 67 114 84 9 4 9 7 106 81 10 0 9 3 74 62 103...

Страница 9: ...1 00 1 03 1 05 Sensible Capacity 0 85 0 94 1 00 1 04 1 07 0 95 0 98 1 00 1 01 1 02 Compressor kW 0 97 0 99 1 00 1 01 1 02 1 10 1 04 1 00 0 97 0 95 TABLE 7 CONDENSER WATER PRESSURE DROP MODEL CONDENSE...

Страница 10: ...0 34 1 17 1 09 0 14 1 33 1 24 800 0 84 1 25 1 16 0 71 1 42 1 32 0 53 1 60 1 48 0 30 1 80 1 64 900 1 18 1 48 1 38 1 06 1 70 1 57 0 91 1 92 1 75 0 70 2 18 1 99 0 43 2 45 2 24 950 1 37 1 61 1 50 1 26 1...

Страница 11: ...i n a l b l o c k 2 2 2 3 2 2 1 3 8 A C C E S S P A N E L T O C O M P R E S S O R A N D E L E C T R I C A L B O X 2 1 3 8 1 2 0 D U C T F L A N G E 2 1 4 1 1 5 8 1 3 3 2 K N O C K O U T P O W E R W I...

Страница 12: ...B O X 1 3 3 2 K N O C K O U T P O W E R S U P P L Y B o t h S i d e s o f U n i t 1 1 4 N P T I W A T E R O U T L E T 1 1 4 N P T I W A T E R I N L E T 2 K N O C K O U T S B o t h S i d e s o f U n i...

Страница 13: ...4 1 3 3 2 K N O C K O U T P O W E R W I R I N G 1 1 2 N P T I W A T E R I N L E T 2 5 8 K N O C K O U T S B o t h S i d e s o f U n i t 1 1 2 N P T I W A T E R O U T L E T A C C E S S P A N E L T O C...

Страница 14: ...2 3 Bottom 4 1 Overall dimension of the unit will vary if an electric heater or a supply air plenum is used 2 Although no clearance is required for service and operation some clearance may be required...

Страница 15: ...nd on the required CFM the unit accessories and the static resistances of both the supply and the return air duct systems With this informa tion the RPM for supply air blower can be determined from th...

Страница 16: ...he supply air CFM after the initial balancing has been completed 1 Drill two 5 16 inch holes in the side panel as shown in Figure 9 2 Insert at least 8 of 1 4 inch tubing into each of these holes for...

Страница 17: ...LOCATIONS MODEL DIMENSION A B C D CED060 9 1 2 2 1 4 19 10 1 4 CED090 3 3 14 12 CED120 3 3 14 12 CED180 7 1 3 4 18 13 3 4 5 1 6 H O L E A B C D 5 1 6 H O L E C O I L S E C T I O N F I L T E R S E V A...

Страница 18: ...46 1 1 2 208 230 3 60 460 3 60 655 880 2 8 3 8 7 8 7 5 1 A36 37 3 CED120 25 46 2 208 230 3 60 460 3 60 700 950 2 8 3 8 7 8 7 0 1 A36 37 3 CED180 25 46 3 208 230 3 60 625 810 3 4 4 4 7 8 9 5 1 A57 58...

Страница 19: ...connections if desired Supply and return elbow connections may be rotated to provide for left hand connections Inlet water must always enter at the lower connection of the con denser See Figure 12 3 W...

Страница 20: ...and are equipped with crankcase heaters 6 Schrader type access valves are provided in the suction and discharge lines for field use 7 The inlet joints or the liquid line strainer dryers are sol dered...

Страница 21: ...er is not plentiful an out door or indoor forced or induced draft cooling tower is recom mend for condenser water Typical piping and wiring arrangements for installing one or more units with pump and...

Страница 22: ...I T C 2 E D 0 6 0 u n i t s o n l y h a v e o n e c o o l i n g s t a g e a n d c a n u s e t h e f o l l o w i n g T h e r m o s t a t S u b B a s e 2 T H 1 3 7 0 0 4 2 4 2 T B 0 8 7 0 0 1 2 4 U N I...

Страница 23: ...removed for unit installation and operation check 10 Set room thermostat at desired space temperature Unit will continue to cycle as required to maintain conditions 11 If electric heat is installed o...

Страница 24: ...n the power spring FIGURE 17 COOLING TOWER WATER PIPING T O D R A I N B L E E D V A L V E S T R A I N E R O V E R F L O W C O O L I N G T O W E R M A K E U P S U P P L Y P U M P B Y P A S S T O A D D...

Отзывы: