2
INSTALLATION & CONNECTION
20
INSTALLATION & CONN
ECTION
Chapter
2
■
Voltage
・
Current Connection
・
Voltage input
・
Current input
*1
Use two-core shield twisted-pair wire to connect F377A to Voltage
・
Current out put
device.
*2
Vin+ to Iin+ should be short-circuited with the jumper wire attached when current input is
done. (Set
「
Analog Input Sel.
」
in calibration when you use it by current input.)
*3,4
F377A and the device connected should be grounded when you use them. (Usually, one
side of shield wire should be connected to avoid the cause of faulty operation by forming
ground loop. However, when high frequency noise affects the operation, it will be
improved by connecting both sides of the shield wire.)
*5
Usually, there is no need to wire A. GND, but it causes the fluctuation of the indicated
value when the potential difference between A. GND terminal and A. GND terminal of
the device connected is produced .
In this case, the symptom may be improved by connecting A. GND to AGND of the
device connected.
*6
F377A is a high resolution type indicator which can perform A/D conversion at supper-
high speed. The wiring between F377A and device connected should be in the short
distance to eliminate the effects of induction noise. Moreover, the connection should be
apart from AC power source and wiring of large volume current. Conduct adequate
checking before the operation.
in
-
A.GND
SHIELD
1
2
3
4
F377A
5
Two-core shield
※
3
+
-
Voltage output
Vin
+
Iin
+
A.GND
SHIELD
G
G
※
1
※
4
※
5
※
3
twisted-pair wire
device
+
※
2
※
1
in
-
A.GND
SHIELD
1
2
3
4
F377A
5
※
3
-
Vin
+
Iin
+
A.GND
SHIELD
G
G
※
4
※
5
※
3
Current output
device
Two-core shield
twisted-pair wire
Содержание F377A
Страница 1: ...18JUL2012REV 3 06 DIGITAL INDICATOR F377A OPERATION MANUAL ...
Страница 5: ...What is RoHS 4 M E M O ...
Страница 12: ...11 11 STANDARD ...
Страница 13: ...12 12 M E M O ...
Страница 84: ...7 SPECIFICATIONS 83 SPECIFICATIONS Chapter 7 Equipped with Device Net interface option Unit mm ...
Страница 94: ...93 93 EXPANSION ...
Страница 95: ...94 94 M E M O ...
Страница 97: ...Expansion Function 96 M E M O ...
Страница 152: ......