UNIPOWER
UP-2210R/P Hardware installation and configuration manual
50
8.1
INSTALLATION
The GPS adapter connects to the UP-2210 via the
Display Port
(RJ45 connector) via a special DIN-
mounted GPS adapter, or via the RS232 port. The following sections will describe the different
connection methods in detail.
8.1.1
GPS communication configuration
Connect to the unit with PQ Online and go to the Tools-Status Tab. Select the appropriate connection
method for the GPS (RS-232 or Display port), and set the baud rate according to the baud rate
configured in the GPS (default values are normally 4800, 9600 or 19200). Then press Apply.
Figure 42 - GPS configuration
This is all that Is needed to configure the UP2210 to use GPS synchronization. If everything is
connected correctly and the GPS finds enough satellites, the “Sync” led on the UP2210 will start to
flash rapidly (0.05s On and 0.9s Off).
8.2
IRIG-B
The UP2210R supports time synchronization via IRIG-B connections. To use IRIG-B, connect the
time synchronization instrument to the Data port and the GND port as shown in
Fel! Hittar inte
referenskälla.
. Then connect to the unit with PQ Online and chose IRIG-B for synchronization
method and chose the baud rate configured in the synchronization instrument. Then press Apply. (see
8.1.1).
Figure 43
8.3
Useful information regarding GPS
When in GPS mode (i.e. the GPS sends valid information to the meter) the meter will not accept time
setting information from either manual operation by PQ Online or automatic setting by PQ Schedule.