![Unipower INV2500-HS Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/unipower/inv2500-hs/inv2500-hs_operating-manual_3901641011.webp)
8
INV2500-HS & INV5000-HS SERIES
OPERATING MANUAL
ENVIRONMENTAL
Operating Temp. Range ...................................... * ............................... 0°C to 70°C ............................... *
Output Current Derating ...................................... * ...................... 2.5%/°C, 50°C to 70°C ...................... *
Storage Temp. Range ......................................... * ............................ -40°C to +85°C ............................ *
Humidity ............................................................... * ................. 0% to 95%, Non-Condensing ................. *
Cooling ................................................................ * .............................. Internal Fans .............................. *
PHYSICAL SPECIFICATIONS
Case Material ...................................................... * ................................ Aluminum ................................ *
Finish, Front Panel & Shelf .................................. * .......................... Powder Coat Gray .......................... *
Dimensions, Inches (mm)
INV2500-HS ............................... 3.32 H x 8.50 W x 12.00 D
(84.3 x 216 x 305)
INVR2U-HS Shelf ................................................................. 3.46 H x 18.32 W x 16.38 D
(87.9 x 465 x 416)
INV5000-HS-230 ..................................................................................................... 3.46 H x 18.32 W x 16.38 D
.............................................................................. (87.9 x 465 x 416)
Rack Mounting Width ...................................... * ............................ 19 or 23 Inches ............................ *
10.0
MECHANICAL DIMENSIONS OF SHELVES
Figure 4 shows the mechanical dimensions for the INVR2U-HS and INV5000-HS
shelves. The shelves are identical at 16.38 inches (416mm) deep; with the rear
plastic cover they are 18.00 inches (457mm) deep.
11.0
SAFETY AND INDUSTRY STANDARDS
11.1
The INV2500-HS and INV5000-HS inverters meet the following safety
certifications:
STANDARD
AGENCY
UL1950
UL
CSA22.2 No.950
CUL
EN60950
DEMKO
11.2
The INV2500-HS and INV5000-HS inverters are CE marked to indicate
conformance to the European Union’s Low Voltage Directive.
11.3
Input conducted EMI meets FCC20780 part 15J Curve A and EN55022
Curve A.
11.4
Input voice band noise is less than 32dBrnC for a single INV2500-HS with a
240 ampere-hour battery or an INV5000-HS or two INV2500-HSs with a 480
ampere-hour battery.