Page 12
DPBF1U & DPGF1U SERIES
OPERATING MANUAL
P O W E R I N G T E C H N O L O G Y
Document Number: DPBF-DPGF-MAN Rev. 5
dpbf_dpgf-man-Rev5-0719.indd
9.3
Crimp Type Lugs.
A list of compatible crimp type lugs is shown in the following table
for AWG wire sizes from no. 1 to 8 and one- or two- hole lugs. These lugs can be ordered
directly from the manufacturer, Panduit Corp., using the model numbers shown in table 4.
A standard kit of four two-hole crimp type lugs for no. 6 AWG copper wire is available from
UNIPOWER. Order kit no. 775-1434-0000.
WIRE
AWG
.25DIA.
HOLES
PANDUIT CORP.
PART NUMBER
UNIPOWER
PART NUMBER
8
1
2
LCA8-14-L
LCD8-14A-L
625-1665-0010
625-1665-0110
6
1
2
LCA6-14-L
LCD6-14A-L
625-1665-0020
625-1665-0120
4
1
2
LCA4-14-L
LCD4-14A-L
625-1665-0030
625-1665-0130
2
1
2
LCA2-14-Q
LCD2-14A-Q
625-1665-0040
625-1665-0140
1
1
2
LCA1-14-E
LCD1-14A-E
625-1665-0050
625-1665-0150
Table 4. Input Cable Lug Sizes & Types
9.4
Output Connections.
Output connections for A and B loads are shown in Figure 6. There
are 10 sets of barrier terminal strip connections for each side, A and B. The connections
are numbered to correspond with the numbers of the front panel breakers. The upper strip
connections are from the battery through the breakers; the lower strip connections are the
returns. Side B is on the left and side A on the right, as shown.
Each terminal is a no. 6-32 screw and is rated at 30 amperes. Wire sizes from no. 10 AWG
up to no. 22 AWG may be used for connections. Figure 7 below shows detailed spacing of
the terminals.
When DPBF1U is fitted with either 40A or 50A breakers the additional load rating is
accomodated by fitting adaptors that bridge two barrier strip terminals and provide a single
#10-32 screw. Minimum wire size for these connections is 8 AWG.
A maximum of two high current breakers is allowed on each bus.
1 2
3 4 5 6 7 8 9 10
40-50A
LOADS
#10-32
1A to 30A
LOADS
#6-32
0.75
(19.1)
0.5
(12.7)
0.378
(9.60)
Figure 6. Output Barrier Strip Detail