UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
35
Revision 2.05
Of 107
12.2.7.3. Screen
Zone Parameters
The screen displays common
zone parameters:
−
Manual call point priority –
where the manual call points
have priority, their response
will force the zone to enter
Fire Condition Phase 2;
where the manual call points
do not have priority, their
response will force the zone
to enter Fire Condition Phase
1, or, in other words, the
manual call point will be
treated as automatic fire
detectors;
−
Coincidence Mode – when
operating in Coincidence
Mode, the zone will enter Fire
Condition Phase 1 upon activation of at least two low priority fire detectors;
−
Time Fire Phase 1 – Phase 2 – this is the time delay before the fire control panel proceeds
from Fire Condition Stage I to Fire Condition Stage II in this particular zone ;
−
Inspection time – time added to the remaining time, by pressing button
, before the zone
proceeds from Fire Condition Stage I to Fire Condition Stage II.
12.2.8. Menu
Device Status
The menu provides information for the current status of the devices. Enter the menu to display:
−
A screen with the message
No integrated devices
, where no devices are present; the only
option is to exit the menu;
−
A screen for the status of the
first device, where some
devices are present:
Buttons
and
seen on the
right panel section appear when
more than one device is available;
the
Go to
field and the digit buttons
appear when more than two devices
are available.
Buttons
and
allow the
user to switch between the next and
the previous device (if available).
When you press a digit button,
the button
appears and the
Go
to
field is activated; then you may
enter a random 3-digit number for the
device. To edit the number press button
, and the last entered digit is deleted.
The devices get numbers according to the following sequence: from the first device in Loop 1 to
the last device in Loop 2; from the first device in Loop 2 to the last device in Loop 2.
С
Mode:DAY
14:22:00
Sat 12 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
List of values
Devices Total: 8
Go to:
Loop01
А
ddr001 Zone001
Point 1.001
Device type: FD7110
Temperature +022
С
Class: A2S
Status: Isolator Off LED Off
0
1
2
3
4
5
6
7
8
9
С
Mode:DAY
12:54:57
Sat 12 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Parameters: Zone 1
Manual call point Priority: Yes
Coincidence
Mode:
No
Time Fire Phase 1 – Phase 2: 120 s
Inspection time: 120 s