ADDRESSABLE OPTICAL SMOKE 

DETECTOR

TYPE

 

FD 7130

INSTRUCTION MANUAL 01-7130-

11

-0

5

1293

GENERAL DESCRIPTION

   

FD7130 addressable optical smoke detector is designed provide early warning of a fire condition by 

reacting upon a fixed smoke concentration level in the protected area

.

 

 The principle of functioning is based upon smoke particles entering the optical chamber causing 

distraction of infrared rays within the chamber. The activation specific smoke concentration level (low, 
middle and high) is programmable via Fire Control Panel IFS 7002 through a specialized 
communication protocol  UniTALK.

   

A built-in short circuit isolator is available.

   

The circuit board and the optic chamber (Fig.1, position 4) are mounted within the plastic body (Fig.1, 

position 5). Two LEDs, (Fig.1, position 3), offering 360° visibility, illuminate to indicate the following:

   

-

Duty Mode

 

 both LEDs flash repeatedly every 16 seconds.

   

-

Fire condition

 

 both LEDs illuminate constantly.

   

-

Activated isolator

 

 both LEDs flash repeatedly with 1Hz frequency .

   

-

Short circuit at the remote indicator output

 - both LEDs flash repeatedly with 2Hz frequency.

   -

Necessary service

-

both LEDs flash repeatedly with 2Hz frequency.

TECHNICAL DATA

Supply voltage U

(15-30)V DC

L

Current consumption in quiescent state

< 310µA  

Alarm state current

(2 ± 1) mA

Sensitivity

in accordance with EN 54-7:2000

Protected area

c

ircle with diameter 15m

 

Installation height

up to 16 m 

Degree of protection

IP 43

Operational temperature range

minus 10°C / plus 60°C

Relative humidity resistance

(93 ± 3) % at 40°C

Dimensions (incl. base)

Ø 100

 mm, h 47 mm

Weight (incl. base)

0,100 kg

Wires

two-wire, shielded

2

Cross section of the wires

up to 2.5 mm

SERVICE SCHEDULE

1. Inspection for visible physical damage

- weekly

2. Satisfactory operation test in real conditions

- monthly

3. Check and clean dust contamination

- every 6 months

4. Check and clean base and head contacts and connections 

- Annually

To complete task 3 remove the head(Fig.1, position 6) and the chamber's upper part (Fig.1, position 

7

). 

Clean using a small brush. The chamber's upper part can be detergent washed, rinsed and dried. 

ATTENTION: When locating the optical chamber fix the upper part so that bench marks coincide.

051-5

ТTESTING THE FIRE DETECTOR

   

Test the fire detector after installation, as a part of the site's fire alarm system or after maintenance, in 

accordance with the requirements set in section Service schedule. 

   

To test the fire detector follow the sequence:

   

1. Apply power to the fire detector from the fire alarm control panel IFS 7002 via the fire alarm loop.

   

2. Wait until the fire detector is set to Duty Mode and exert influence on the fire detector by smoke 

generator or another device with aerosol simulator of smoke. Within 40 seconds the fire detector shall 
enter fire condition and the LEDs (Fig.1, position 3) shall illuminate continuously.

   

3. Send a reset command from the fire control panel to the fire detector under testing. The fire 

detector shall restore the Duty Mode.

WARRANTY

   

The warrant period is 36 months from the date of purchase. The manufacturer guarantees the normal 

operation of the unit providing that the requirements set herein have been observed. The manufacturer 
does not bear warranty liabilities for damages caused through accidental mechanical damage, misuse, 
adaptation or modification after production. The manufacturer bears warranty liabilities for damages in 
the fire detector caused through manufacturer's fault only.

INSTALLATION

   

The fire detector type FD7130 operates with bases type 7100. To install the fire detector and its base 

follow the sequence:

   

1. Fix the base on the ceiling of the protected premises using appropriate fixings.

   

2. Complete the wiring as shown on fig. 2 and in accordance with the construction projects of the site.

   

3. Replace the detector head on the base and rotate it in a clockwise direction to reach the base's 

leading channels (Fig.1, position 2). Continue rotating in a clockwise direction to complete location 
(Fig.3

.1

). The bench marks of the head and the base should fully coincide (Fig. 3

.2

). 

   

4. To lock the detector head to the base separate the key from the base (Fig. 

4

, position 

3

) and keep it 

in a safe place, cut the technological edge (Fig. 

4

, position 

1

) of the click (Fig. 

4

, position 

2

) and 

complete the instructions described above. 

   

5. To unlock the detector head insert the key into the slot, according to Fig.4, rotate the fire detector 

anticlockwise until rest, take the key out and continue rotating to release the head. 

Manufacturer: UniPOS Ltd., 114 Grenaderska Street, Pleven 5800, Bulgaria, http://www.unipos-bg.com