29
B. Parallel model: Compared to single model, parallel model will have one more screen to display parallel
information of UPS unit.
12. Parallel information
P01: Master UPS
P02: Slave UPS
P03: Slave UPS
3-9. Fault Code
Fault code
Fault event
Icon Fault code Fault event
Icon
01
Bus start failure
None
42
DSP communication failure
None
02
Bus over
None
43
Overload
03
Bus under
None
46
Incorrect UPS setting
None
04
Bus unbalance
None
47
MCU communication failure
None
06
Converter over current
None
48
Two DSP firmware versions
are incompatible in parallel
system.
None
11
Inverter soft start failure None
60
Bypass phase short
circuited
12
High inverter voltage
None
61
Bypass SCR short circuited
None
15
Inverter B output(line to
neutral) short circuited
62
Bypass SCR open circuited
None
16
Inverter C output(line to
neutral) short circuited
63
Voltage waveform abnormal
in A phase
None
17
Inverter A-B output (line
to line) short circuited
64
Voltage waveform abnormal
in B phase
None
18
Inverter B-C output (line
to line) short circuited
65
Voltage waveform abnormal
in C phase
None
19
Inverter C-A output (line
to line) short circuited
66
Inverter current detect
abnormal
None
1A
Inverter A negative
power fault
None
67
Bypass O/P short circuited
1B
Inverter B negative
power fault
None
68
Bypass O/P line to line short
circuited
1C
Inverter C negative
power fault
None
69
Inverter SCR short circuited
None
21
Battery SCR short
circuited
None
6C
BUS voltage drops too fast
None
23
Inverter relay circuited
open
None
6D
Current error value detect
None
24
Inverter relay short
circuited
None
6E
SPS power error
None
25
Line wiring fault
None
6F
Battery polarity reverse
None
31
Parallel communication
failure
None
71
PFC IGBT over-current in R
phase
None
32
The host signal failure
None
72
PFC IGBT over-current in S
phase
None
33
Synchronous signal
failure
None
73
PFC IGBT over-current in T
phase
None