UPS471-02-00 PW9000DPA User Manual UK Dated 06/08/14
3
2: General Description
2.2
PowerWave 9000 Model range
The PowerWave 9000 UPS is based on a range of 30kVA to 50kVA plug-in power modules fitted into one of three
purpose-designed cabinets. Each power module is a self-contained UPS comprising a rectifier, battery charger, inverter
and static switch; and when two or more modules are fitted into a cabinet they effectively operate as a parallel UPS
system. The available cabinets can contain up to one, three or five power modules as shown below in Figure 2.1.
The PowerWave 9000 cabinets are identified as CLASSIC DPA-50, TRIPLE DPA-150 and UPGRADE DPA-250 – where
the model number represents the maximum kVA output available when the cabinet is fully populated with 50 kVA power
modules. Figure 2.1 shows that the DPA-50 and DPA-150 cabinets include shelves for housing the UPS batteries;
however the DPA-250 cabinet has no internal battery mounting facilities and requires an external battery cabinet. A range
of matching battery cabinets is available which are installed adjacent to the UPS cabinet in the majority of installations. An
additional (external) battery cabinet can also be connected to the DPA-50 and DPA-150 models to extended the overall
system autonomy time if desired.
Figure 2.1 PowerWave 9000 Cabinets (frames)
Figure 2.2 PowerWave 9000 UPS Power Modules
Key Point:
All the modules fitted within a cabinet must be of the same rating – for example, it is not possible to
mix 30kVA and 50kVA modules in the same cabinet.
CLASSIC
DPA-50
TRIPLE
DPA-150
UPGRADE
DPA-250
Power module capacity
Max.
1 module (30-50kVA)
280 x 7/9Ah batteries
3 modules (30-50kVA)
240x 7/9Ah batteries
5 modules (30-50kVA)
External batteries
Maximum power connection
kVA
50
150
250
Dimensions (WxHxD)
mm
730x1650x800
730x1975x800
730x1975x800
Weight of empty frame
kg
262
239
205
Weight of frame with modules fitted
(but without batteries)
kg
305 - 309
(with 1 Module)
368 - 379
(with 3 Modules)
420 - 439
(with 5 Modules)
Colours
Front: RAL 9007 + black (inlets). Sidewalls: Graphite grey
DPA 30 Module
DPA 40 Module
DPA 50 Module
Output Apparent Power
KVA
30
40
50*
Output Active Power
KW
24
32
40
Output Power (PF=1)
KVA / KW
24 / 24
32 / 32
40 /40
Number of 12V Battery Blocks
No.
40-50
40-50
40-50
Dimensions (WxHxD)
mm
663 x 225 x 720
Weight UPS Module
kg
43.1
45.3
46.8
Colours
Front: Graphite grey
* On Inverter mode 50 KVA/40kW on Bypass mode 45 KVA/40kW