21 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL 

1K 

1KL 

1.5K 

1.5KL 

2K 

2KL 

3K 

3KL 

Capacity 

VA/W 

1000 VA / 900 W 

1500 VA / 1350 W 

2000 VA / 1800 W 

3000 VA / 2700 W 

INPUT 

Voltage 
Range 

Low Line 
Transfer 

80 VAC/70 VAC/60 VAC/55 VAC ±  5 % or 160 VAC/140 VAC/120 VAC/110 VAC ±  5 % 

(based on load percentage 100%-80% / 80%-70% / 70%-60% / 60%-0)   

Low Line 
Comeback 

85 VAC/75 VAC/65 VAC/60 VAC ±  5 % or 170 VAC / 150 VAC / 130 VAC / 120 VAC ±  5 % 

High Line 
Transfer 

150 VAC ±  5 % or 300 VAC ±  5 % 

High Line 
Comeback 

140 VAC ±  5 % or 290 VAC ±  5 % 

Frequency Range 

40Hz ~ 70Hz 

Power Factor 

0.99 @normal voltage 

OUTPUT 

Output Voltage 

100*/110*/115*/120/127 VAC or 200/208/220/230/240 VAC 

AC Voltage Regulation   

±  1% 

Frequency Range       

47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range) 

Frequency Range                     

50Hz 

 0.5% or 60Hz 

 0.5% (Bat. Mode) 

Current Crest Ratio (CF) 

5:1 (max.) 

Harmonic Distortion 
(THDU) 

 2% THD (Linear load)   

 4% THD (Non-linear load) 

Transfer 
Time 

AC to DC 

Zero 

Inverter to 
Bypass 

4 ms (Typical) 

Waveform (Batt. Mode) 

Pure Sinewave 

EFFICIENCY 

AC Mode 

87% 

88% 

88% 

89% 

Battery Mode 

85% 

86% 

86% 

87% 

ECO Mode 

94% 

95% 

95% 

97% 

BATTERY 

Battery Type 

12V/9Ah 

Depending 

on 

application 

12V/9Ah 

Depending 

on 

application 

12V/9Ah 

Depending 

on 

application 

12V/9Ah 

Depending 

on 

application 

Numbers 

Typical Recharge Time 

4 hours recover to 90% capacity (for standard model only) 

Charging Current 

(max.)

 

1 A   

1A/2A/ 

4A/8A 

1 A 

1A/2A/ 

4A/8A 

1 A 

1A/2A/ 

4A/8A 

1 A 

1A/2A/ 

4A/8A 

Charging Voltage 

27.4 VDC ±  1% 

41.1 VDC ±  1% 

54.7 VDC ±  1% 

82.1VDC ±  1% 

INDICATORS 

LCD   

UPS status, Load level, Battery level, Input/Output/battery info, Discharge time and Fault indicators 

ALARM 

Battery Mode 

Sounding every 4 seconds 

Low Battery 

Sounding every second 

Overload 

Sounding twice every second 

Fault 

Continuously sounding 

PHYSICAL 

Dimension,

 DxWxH (mm)

 

380 x 438 x 88 

480 x 438 x 88 

480 x 438 x 88 

600 x 438 x 88 

Net Weight (kgs) 

12.9 

8.6 

17.6 

10.7 

20.6 

11.3 

28 

13.8 

ENVIRONMENT 

Humidity 

20-90 % RH @ 0- 40°C (non-condensing) 

Noise Level 

Less than 50dBA @ 1 Meter 

MANAGEMENT 

Smart RS-232/USB 

Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

*Derate capacity to 95% when the output voltage is adjusted to 115VAC. Derate capacity to 90% when the output voltage is adjusted to 
110VAC and derate capacity to 80% when the output voltage is adjusted to 100VAC/200VAC/208VAC. 
 

6. Specifications 

Содержание Online UPS 1K

Страница 1: ...Rack Tower Online UPS 1K 1 5K 2K 3K Uninterruptible Power Supply System Version 1 2 User Manual...

Страница 2: ...view 3 2 2 Install the UPS 4 2 3 Setup the UPS 5 2 4 Battery Replacement 6 2 5 Battery Kit Assembly option 7 3 Operations 10 3 1 Button operation 10 3 2 LCD Panel 10 3 3 Audible Alarm 12 3 4 LCD disp...

Страница 3: ...over them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...al package in a safe place for future use NOTE There are two different types of online UPS standard and long run models Please refer to the following model table Model No Type Model No Type 1K Standar...

Страница 6: ...ong run models 11 Input terminal 12 Output circuit breaker 2 2 Install the UPS For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS plea...

Страница 7: ...port Intelligent slot To allow for unattended UPS shutdown start up and status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your...

Страница 8: ...m 2 Click ViewPower software icon and then choose your required OS to download the software 3 Follow the on screen instructions to install the software 4 When your computer restarts the monitoring sof...

Страница 9: ...the unit 2 5 Battery Kit Assembly option NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit procedure below to assemble it 2 battery kit Ste...

Страница 10: ...battery packs on one side of plastic shells and insert one more defect battery on the space Step 4 Cover the other side of plastic shell as below chart Then battery kit is assembly well 4 battery kit...

Страница 11: ...ow chart Then battery kit is assembly well 6 battery kit Step 1 Remove adhesive tapes Step 2 Connect all battery terminals by following below chart Step 3 Put assembled battery packs on one side of pl...

Страница 12: ...e if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the...

Страница 13: ...voltage Hz frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuited UPS status Indicates that progr...

Страница 14: ...D display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape RAC Rack display TOE Tower display B L Low Battery O L Overload N C Battery is not connected O C Overcha...

Страница 15: ...127 VAC models you may choose the following output voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage...

Страница 16: ...isable Interface Setting ENA Advanced ECO mode enable DIS Advanced ECO mode disable 06 Bypass mode enable disable Interface Setting ENA Bypass mode enable DIS Bypass mode disable 07 Programmable outle...

Страница 17: ...the following Acceptable input voltage range 110 300 alternating flashing acceptable input voltage range is from 110V to 300V 160 260 alternating flashing acceptable input voltage range is 160V to 26...

Страница 18: ...y Corrective Optimizer When the input voltage is within setting range 3 Vo max UPS will bypass voltage to output for energy saving PFC and INVERTER are off at this mode Frequency Converter mode When i...

Страница 19: ...nder 03 x Battery voltage too high 27 x Bus unbalance 04 x Battery voltage too low 28 Inverter soft start fail 11 x Over temperature 41 x High Inverter voltage 12 x Overload 43 3 8 Warning indicator W...

Страница 20: ...hing on LCD display and alarm is sounding every second The external or internal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon is lig...

Страница 21: ...ring and if connected devices are in short circuit status Fault code is shown as 01 02 03 04 11 12 13 and 41 on LCD display and alarm is continuously sounding A UPS internal fault has occurred There a...

Страница 22: ...ealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperat...

Страница 23: ...12V 9Ah Depending on application 12V 9Ah Depending on application 12V 9Ah Depending on application Numbers 2 3 4 6 Typical Recharge Time 4 hours recover to 90 capacity for standard model only Charging...