35
Checking the detection current
To check the detection current follow the diagram on Fig. 13. If the signal is less than the value indicated, check the position of the de-
tection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
Fig. 13Detection with detector QRI...
Minimum detection signal: 3.5Vdc
Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
1
turn the burner main switch to 0 (Off position)
2
disconnect the power mains
3
close the fuel valve of the supply line
Burner disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.
7719a01E/0502
SIEMENS
QRI
Made in Germany
Landis & Staefa
blue
brown
0...10 V
Ri > 10 M
:
X10-02 / 6
X10-02 / 4
X10-02 / 2
LMV...
+
black