21
Once the throttle valve is completely opened, acting on the pressure stabiliser of the valves group, adjust the
gas flow rate in the high
flame stage
as to meet the values requested by the boiler/utilisation:
Gas valves Siemens VGD - Version with SKP2. (provided with pressure stabilizer).
Start-up procedure
1
Turn the burner on.
2
the LMV control box starts the system test cycle: the AZL display shows the
System Test
message; at the end of the test, it shows
the main page and the system stops (the safety chain is open) waiting for the startup enabling signal (standby - Program phase no.
12)
Main page
3
check the fan motor rotation (see related paragraph).
4
make the safety chain enabling the system to start up
5
the combustion cycle starts: the system will show the operating stages
- Prepurging
(program phase no.30)
- Driving to ignition position
(program phase no.36)
- Ignition position
(program phase no.38)
- Fuel
(the fuel solenoid valves open)
- Flame
(the flame lights up)
- Driving to low flame
(the actuator drives to low flame).
NOTE:
the
C
and
A
, on the .
Once the ignition cycle ends, the main page is shown:
Main page
Set point:
temperature set-point
Act value:
actual temperature value
Load:
load percentage (burner output)
Flame:
percentage of flame detection current.
By pressing the ENTER key the display shows the second page:
To increase or decrease gas pressure, and therefore gas flow rate, remove the cap
T
and use a screwdriver to adjust the regulating screw
VR
. Turn clockwise to increase
the flow rate, counterclockwise to reduce it.
Setpoint
80°C
Act.value
78°C
Fuel
GAS
Standby
12
Setpoint
80°C
Act.value
78°C
Load
24%
Flame
60%
VR
T
Содержание TP1030
Страница 38: ......
Страница 39: ......
Страница 41: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 48: ...8...
Страница 49: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 52: ...12 2 2 LMV5x program structure...
Страница 79: ...39...
Страница 86: ......
Страница 87: ......
Страница 88: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 90: ...Annex1 Example for motor cable...
Страница 91: ......
Страница 92: ...Annex 2 Example for sensor cable...
Страница 93: ......
Страница 94: ......
Страница 98: ......