10
Parameters summarising for RWF50.2x:
Conf
Conf
PArA Opr
Navigation menù
Inp
Cntr diSP
Inp1
Types of probe
SEn1 OFF1
SCL1
SCH1
Unit
SPL
SPH
dECP
Pb. 1 dt
rt
tt
HYS1 (*)
HYS3 (*)
SP1 (*)
Siemens QAE2120…
6
0
needless needless
1
30
95
1
10 80 350 (#)
-5
5
80 °C
Siemens QAM2120..
6
0
needless needless
1
0
80
1
10 80 350 (#)
-2,5
2,5
40°C
Pt1000 (130°C max.)
4
0
needless needless
1
30
95
1
10 80 350 (#)
-5
5
80°C
Pt1000 (350°C max.)
4
0
needless needless
1
0
350
1
10 80 350 (#)
-5
10
80°C
Pt100 (130°C max.)
1
0
needless needless
1
0
95
1
10 80 350 (#)
-5
5
80°C
Pt100 (350°C max)
1
0
needless needless
1
0
350
1
10 80 350 (#)
-5
10
80°C
Probe 4÷20mA / 0÷1,6bar
16
0
0
160
needless
0
160
0
5
20 80 (#)
0
20
100 kPa
Probe 4÷20mA / 0÷3bar
16
0
0
300
needless
0
300
0
5
20 80 (#)
0
20
200 kPa
Probe 4÷20mA / 0÷10bar
16
0
0
1000
needless
0
1000
0
5
20 80 (#)
0
50
600 kPa
Probe 4÷20mA / 0÷16bar
16
0
0
1600
needless
0
1600
0
5
20 80 (#)
0
80
600 kPa
Probe 4÷20mA / 0÷25bar
16
0
0
2500
needless
0
2500
0
5
20 80 (#)
0
125
600 kPa
Probe 4÷20mA / 0÷40bar
16
0
0
4000
needless
0
4000
0
5
20 80 (#)
0
200
600 kPa
Siemens QBE2002 P4
17
0
0
400
needless
0
400
0
5
20 80 (#)
0
20
200 kPa
Siemens QBE2002 P10
17
0
0
1000
needless
0
1000
0
5
20 80 (#)
0
50
600 kPa
Siemens QBE2002 P16
17
0
0
1600
needless
0
1600
0
5
20 80 (#)
0
80
600 kPa
Siemens QBE2002 P25
17
0
0
2500
needless
0
2500
0
5
20 80 (#)
0
125
600 kPa
Siemens QBE2002 P40
17
0
0
4000
needless
0
4000
0
5
20 80 (#)
0
200
600 kPa
Segnale 0÷10V
17
0
to be fixed to be fixed needless to be fixed to be fixed to be fixed
5
20 80 (#) to be fixed to be fixed to be fixed
Segnale 4÷20mA
16
0
to be fixed to be fixed needless to be fixed to be fixed to be fixed
5
20 80 (#) to be fixed to be fixed to be fixed
NOTE
:
(#) tt – servo control run time
SQL33 ; STM30; SQM10; SQM40; SQM50; SQM54 =
30
(secondi) - STA12B3.41; SQN30.251; SQN72.4A4A20 =
12
(secondi)
(*)These values are factory set - values
must be
set during operation at the plant based on the real working temperature/pressure value.
WARNING :
With pressure probes the parameters SP1, SCH, SCL, HYS1, HYS3 must be selected, and visualized in kPa (kilo Pascal). (1bar = 100.000Pa = 100kPa)
Содержание RN510
Страница 39: ......
Страница 54: ......
Страница 63: ......
Страница 64: ......
Страница 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 82: ...M12927CA MOUNTING 2...
Страница 98: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Страница 99: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Страница 120: ......
Страница 121: ...23 Note Specifications and data subject to change Errors and omissions excepted...
Страница 130: ...OFF...
Страница 131: ......
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ......
Страница 136: ......
Страница 137: ......
Страница 138: ......