PART I: SPECIFICATIONS
7
* NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
1.3 Country and usefulness gas categories
1.4 Fuel
1.5
BURNER TYPE
R75A M-..
R75A L-..
Output
min. - max. kW
320 - 2050
Fuel
Natural gas
LPG
Category
see next paragraph
I
3B/P
Gas flow rate
min.-max. Stm
3
/h
34 - 217
12 - 77
Gas pressure
min.-max. mbar
(see Note 2)
Electric supply
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
3.5
Fan motor
kW
3
Protection
IP40
Weight
kg
90
Operation
Double stages - Progressive - Fully modulating
Valves size/Gas connection - 50
2"
/
Rp2
Valves size/Gas connection - 65
2"
1/2
/
DN65
Valves size/Gas connection - 80
3"
/
DN80
Valves size/Gas connection - 100
DN100
Operating temperature
°C
-10 ÷ +50
Storage TemperatureStorage Temperature
°C
-20 ÷ +60
Working service*
Intermittent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
);
Note2:
Maximum gas pressure = 360mbar (with
Dungs MBDLE)
Maximum gas pressure = 500mbar (with
Siemens VGD)
Minimum gas pressure = see gas curves.
GAS
CATEGORY
COUNTRY
I
2H
AT ES GR SE FI
IE HU IS NO CZ DK GB IT PT CY EE LV SI MT SK BG LT RO TR CH
I
2E
LU PL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2E( R ) B
BE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2L
NL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2ELL
DE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2Er
FR
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ATTENTION! The burner must be used only with the fuel specified in the burner data
plate .
Type --
Model
--
Year --
S.Number --
Output --
Oil Flow
--
Fuel
--
Category --
Gas Pressure
--
Viscosity --
El.Supply --
El.Consump. --