PART IV: MAINTENANCE
43
6.8 Checking the detection current (natural gas)
To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
6.9 Checking the detection current (L.P.G.)
To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
6.10 Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
1
turn the burner main switch to 0 (Off position)
2
disconnect the power mains
3
close the fuel valve of the supply line
6.11 Burner disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.
Device
Flame detector
Minimum detection signal
Siemens LMV2x/3x
Ionization probe
4 µA (values on display: 30%)
Device
Flame detector
Minimum detection signal
Siemens LMV2x/3x
QRA
70 µA (intensity of flame >24%)
Protective earth PE
Ionization probe (ION)
QRB.../ QRC... signal voltage
QRB... GND
1
2
3
4
5
L
X10-05
QRA... (-)
QRA... (+)
1
2
X10-06
+