C.I.B. UNIGAS
- M03993CH
23
Heavy oil pumps
The pump provided with the burner must be installed according to the hydraulic diagram.
Cucchi FMG25 pumps
Capacity 1500l/h
Power consumption: 0.75kW
Speed: 1400 rpm
Max outlet pressure: 10bar
Max inlet pressure: 2bar
Min inlet pressure: -0.4bar
For further details see the manifacturer documentation.
Suntec TV Pressure governor
About the use of fuel pumps
z
Do not use fuel with additives to avoid the possible formation over time of compounds which may deposit between the gear teeth,
thus obstructing them.
z
After filling the tank, wait before starting the burner. This will give any suspended impurities time to deposit on the bottom of the
tank, thus avoiding the possibility that they might be sucked into the pump.
z
On initial commissioning a "dry" operation is foreseen for a considerable length of time (for example, when there is a long suction
line to bleed). To avoid damages inject some lubrication oil into the vacuum inlet.
z
Care must be taken when installing the pump not to force the pump shaft along its axis or laterally to avoid excessive wear on the
joint, noise and overloading the gears.
z
Pipes should not contain air pockets. Rapid attachment joint should therefore be avoided and threaded or mechanical seal junc-
tions preferred. Junction threads, elbow joints and couplings should be sealed with removable sg component. The number of junc-
tions should be kept to a minimum as they are a possible source of leakage.
z
Do not use PTFE tape on the suction and return line pipes to avoid the possibility that particles enter circulation. These could depo-
sit on the pump filter or the nozzle, reducing efficiency. Always use O-Rings or mechanical seal (copper or aluminium gaskets) jun-
ctions if possible.
z
An external filter should always be installed in the suction line upstream of the fuel unit.
Pressure adjustment
Remove cap-nut 1 and the gasket 2, unscrew the lock nut 4. To increase pressure,
twist adjusting screw 3 clockwise.
To decrease the pressure, twist screw counterclockwise. Tight the lock nut 4, refit the
gasket 2 and the cap nut 1.
Key
1
Cap nut
2
Gasket
3
Adjusting screw
4
Lock nut
5
Gasket
Fig. 16