45
10 Press
InFo
for more than three seconds or for more than three seconds orto return to the normal display.
If a message like the one below is shown during operation,
it means that the burner is locked out and the Errore code is shown (in the example “error code:4”); this message is alternating with
another message
Diagnostic code (in the example “diagnostic code:3”). Record the codes and find out the fault in the Error table
To perform the reset, press InFo for one second:
The unit displays an event which does not lead to shutdown.
The display shows current error code
c:
alternating with diagnostic code
d
:
.
Press
InFo
to return to the display of phases.
Example: Error code
111
/ diagnostic code 0
To reset, press InFo for a second. Record the codes and check the Error List to find the type of faults.
Содержание P75R
Страница 53: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 60: ...8 Parameters level heating engineer...
Страница 102: ...50 ERROR CODE TABLE...
Страница 103: ...51...
Страница 104: ...52...
Страница 105: ...53...
Страница 106: ...54...
Страница 107: ...55...
Страница 108: ...56...
Страница 109: ...57...
Страница 110: ...58...
Страница 111: ...59...
Страница 112: ...60...
Страница 113: ...61...
Страница 114: ...62...
Страница 115: ...63...
Страница 116: ...64...
Страница 118: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 121: ......
Страница 122: ......
Страница 123: ......
Страница 125: ...IG FU B...
Страница 126: ......
Страница 127: ......
Страница 128: ......
Страница 129: ......
Страница 130: ......
Страница 131: ......
Страница 132: ......
Страница 133: ......
Страница 134: ......
Страница 135: ......