PART IV: MAINTENANCE
43
Center head holes gas flow regulation (natural gas burners)
To adjust the gas flow, partially close the holes, as follows:
1
loosen the three
V
screws that fix the adjusting plate
D
;
2
insert a screwdriver on the adjusting plate notches and let it move CW/CCW as to open/close the holes;
3
once the adjustmet is performed, fasten the
V
screws.
The adjusting plate correct position must be regulated in the plant during the commissioning.
The factory setting depends on the type of fuel for which the burner is designed:
For natural gas burners, plate holes are fully opened
Center head holes gas flow regulation (LPG burners)
To adjust the gas flow, partially close the holes, as follows:
1
loosen the three
V
screws that fix the adjusting plate
D
;
2
insert a screwdriver on the adjusting plate notches and let it move CW/CCW as to open/close the holes;
3
once the adjustmet is performed, fasten the
V
screws.
The adjusting plate correct position must be regulated in the plant during the commissioning.
9xA
series
: 1,5 mm 5xxA
series
: 1,3 mm
Flame detection probe
To clean/replace the detection photocell, proceed as follows:
1
Disconnect the system from the electrical power supply.
2
Shut off the fuel supply;
3
remove the photocell from its slot (see next figure);
4
clean the bulbe if dirty, taking care not to touch it with bare hands;
5
if necessary, replace the bulb;
replace the photocell into its slot.
Removing the combustion head
Remove the cover
C
.
remove the electrodes cables;
unscrew the 3 screws
V
which hold in position the gas manifold
G
and pull out the complete group as shown in the picture below.
Clean the combustion head by a compressed air blow or, in case of scale, scrape it off by a scratchbrush.
Device
Flame detector
Minimum detection signal
Siemens LMV2x/3x
QRA
70 µA (intensity of flame >24%)
Attention:
before adjusting the combustion head, turn the burner off and wait until it gets cold.
V
D
A:
opened holes
B:
closed holes
B
A
V
D
A:
opened holes
B:
closed holes
B
A
QRA... (
)
QRA... (
)
2
X10-06
+
Содержание K590X
Страница 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 56: ...8 Parameters level heating engineer...
Страница 98: ...50 ERROR CODE TABLE...
Страница 99: ...51...
Страница 100: ...52...
Страница 101: ...53...
Страница 102: ...54...
Страница 103: ...55...
Страница 104: ...56...
Страница 105: ...57...
Страница 106: ...58...
Страница 107: ...59...
Страница 108: ...60...
Страница 109: ...61...
Страница 110: ...62...
Страница 111: ...63...
Страница 112: ...64...
Страница 114: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 117: ......
Страница 118: ......
Страница 119: ......