PART I: SPECIFICATIONS
14
POWER REDUCTION WITH REFERENCE TO THE BURNER OPERATING CURVE
Since depowering the burner operating range is equivalent to increasing the burner power by the same percentage, the quickest proce-
dure is described point by point below:
Choosing the burner without taking flue gas recirculation into account
estimate the amount of recirculation (see figure below) required to ensure a certain NOx value as a function of the heat load of the
boiler, for that burner
multiply the required burned power by the depowering factor expressed as follows
multiply the back pressure in the combustion chamber by the depressurisation factor squared (pressure losses vary with the
square of the change in flow rate)
choose the burner considering the new power and back pressure value
if the burner size is insufficient, a larger machine must be selected, the depowering factor must be re-checked and the above pro-
cedure repeated.
Gas pressure
in
comb
usti
on hea
d
K590X M-..
Stm
3
/h
K750X M-..
Stm
3
/h
Ga
s pre
ssu
re
in
co
mb
ust
ion
h
ea
d
K660X M-..
Stm
3
/h
Gas pressure
in
comb
usti
on hea
d
K590X L-..
Stm
3
/h
K750X L-..
Stm
3
/h
Содержание K590X
Страница 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 56: ...8 Parameters level heating engineer...
Страница 98: ...50 ERROR CODE TABLE...
Страница 99: ...51...
Страница 100: ...52...
Страница 101: ...53...
Страница 102: ...54...
Страница 103: ...55...
Страница 104: ...56...
Страница 105: ...57...
Страница 106: ...58...
Страница 107: ...59...
Страница 108: ...60...
Страница 109: ...61...
Страница 110: ...62...
Страница 111: ...63...
Страница 112: ...64...
Страница 114: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 117: ......
Страница 118: ......
Страница 119: ......