PART I: INSTALLATION
15
SETTINGS LO280
Oil rate adjustment - Single stage burners
Priming the pump
Before carrying out the adjustment it is necessary to start up the fuel pump, proceeding as follows:
Prior to start up the burner, make sure that the return pipe to the tank is not obstructed. Any obstruction would
cause the pump seal to break.
Start the burner, light up the photoresistor after the opening of the solenoid valve and escape the air from the pressure port.
The fuel flow rate is set choosing a properly dimensioned nozzle and setting the inlet pressure on the pump (see the hydraulic
diagram in Fig. 34
To choose the correct nozzle refer to table Tab. 1; for setting of the pump pressure, see pag. 23.
Choosing oil nozzles
Tab. 1 - Choice of the oil nozzle - Single stage burners
Note: all pumps are set to 12 bar. The nozzle rate must be higher than the rate referred to the minimum burner
output.
Key
EVG Light oil solenoid valve
M
Manometer
P
Pump (see chapter “LIGHT OIL PUMPS”)
Fig. 34
NOZZLE
PUMP PRESSURE
(bar)
6
7
8
9
10
11
12
13
14
G.P.H.
kg/h
1,35
3,97
4,29
4,59
4,86
5,13
5,38
5,62
5,85
6,07
1,50
4,41
4,77
5,10
5,41
5,70
5,98
6,24
6,50
6,74
1,65
4,85
5,24
5,61
5,95
6,27
6,57
6,87
7,15
7,42
1,75
5,15
5,56
5,95
6,31
6,65
6,97
7,28
7,58
7,87
2,00
5,88
6,36
6,80
7,21
7,60
7,97
8,32
8,66
8,99
2,25
6,62
7,15
7,64
8,11
8,55
8,96
9,36
9,74
10,11
2,50
7,36
7,95
8,49
9,01
9,50
9,96
10,40
10,83
11,24
3,00
8,83
9,53
10,19
10,81
11,40
11,95
12,48
12,99
13,48
3,50
10,30
11,12
11,89
12,61
13,29
13,94
14,56
15,16
15,73
4,00
11,77
12,71
13,59
14,41
15,19
15,94
16,64
17,32
17,98
4,50
13,24
14,30
15,29
16,22
17,09
17,93
18,72
19,49
20,23
5,00
14,71
15,89
16,99
18,02
18,99
19,92
20,81
21,65
22,47
5,50
16,18
17,48
18,69
19,82
20,89
21,91
22,89
23,82
24,72
6,00
17,65
19,07
20,39
21,62
22,79
23,90
24,97
25,99
26,97
6,50
19,13
20,66
22,08
23,42
24,69
25,90
27,05
28,15
29,21
EVG
M
P
Содержание IDEA Series
Страница 27: ...PART III MAINTENANCE MANUAL 27 Fig 51 Fig 52 Fig 53 Fig 54 Fig 55 TA CA1 CA2 V1 V2 V3 V4 CE FR...
Страница 33: ...PART III MAINTENANCE MANUAL 33 WIRING DIAGRAMS Wiring diagram 04 743 LO280 Single stage burners...
Страница 34: ...PART III MAINTENANCE MANUAL 34...
Страница 35: ...PART III MAINTENANCE MANUAL 35 Wiring diagram 18 116 LO280 Double stage burners...
Страница 36: ...PART III MAINTENANCE MANUAL 36...
Страница 38: ...PART III MAINTENANCE MANUAL 38 Wiring diagram 18 049 LO400 Single stage burners...
Страница 39: ...PART III MAINTENANCE MANUAL 39 Single stage burners 18 049 LO400 Double stage burners...
Страница 40: ...PART III MAINTENANCE MANUAL 40 Connectors layout on printed board...
Страница 42: ...PART III MAINTENANCE MANUAL 42...
Страница 47: ...APPENDIX COMPONENTS SPECIFICATIONS 47...
Страница 48: ......