C.I.B. UNIGAS - M039134CD
5
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follow.
Technical Specifications
NOTE:
Choosing the nozzle for light oil, consider Hi equal to 42.74MJ/kg.
*NOTE ON THE BURNER WORKING SERVICE:
z
Burners provided with Siemens LOA24 control box: for safety reasons, one controlled shutdown must take place every 24 hours
.
z
Burners provided with Siemens LMO24-44 control box: the control box automatically stops after 24h of continuous working. The
control box immediately starts up, automatically.
WARNING: if fuel used is BIODIESEL, some components must be replaced. Please contact our Technical
Department for further details.
Type
LO400
Model
G-. AB. S.
*
. A.
(1)
(2) (3) (4) (5) (6)
(1) BURNER TYPE
LO550
(2) FUEL
G -
Light oil
A -
Biodiesel
(3) OPERATION(Available versions)
TN -
Single-stage
AB -
Double-stage
(4) BLAST TUBE
S -
Standard
L -
Extended
(5) DESTINATION COUNTRY
* - see data plate
(6) BURNER VERSION
A -
Standard
M -
With hydraulic ram
BURNERS
LO280 G-.TN....
LO280 G-.AB....
Output
min. - max. kW
115 - 310
70 - 310
Fuel
Light oil
Light oil
Light oil rate
min.- max. kg/h -
9.6 - 26
5.8 - 26
Viscosity
cSt @ 40°C
2 - 7.4
Density
kg / m
3
0.84
Power supply
230V 50Hz
Electric motor
kW
0.25
0.25
Total power consumption
W
0.55
0.55
Weight
kg
42
42
Operation
Single stage
Double stage
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermittent
BURNERS
LO400 G-.TN....
LO400 G-.AB....
Output
min.-max.kW
195 - 420
115 - 420
Fuel
Light oil
Light oil
Light oil rate
min. - max. kg/h
16 - 35
10 - 35
Viscosity
cSt @ 40°C
2 - 7.4
Density
kg / m
3
0.84
Power supply
230V 50Hz
Electric motor
kW
0.37
0.37
Total power consumption
W
0.67
0.67
Weight
kg
42
42
Operation
Single stage
Double stage
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermittent
PART I: INSTALLATION