PART III: MAINTENANCE
44
Flame detection probe
To clean/replace the detection photocell, proceed as follows:
1
Disconnect the system from the electrical power supply.
2
Shut off the fuel supply;
3
remove the photocell from its slot (see next figure);
4
clean the bulbe if dirty, taking care not to touch it with bare hands;
5
if necessary, replace the bulb;
replace the photocell into its slot.
Checking the detection current
To check the detection signal follow the scheme in the picture below. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
Burner service term
- In optimal operating conditions, and with preventive maintenance, the burner can last up to 20 years.
- Upon expiry of the burner service term, it is necessary to carry out a technical diagnosis and, if necessary, an overall repair.
- The burner status is considered to be at its limit if it is technically impossible to continue using it due to non-compliance with safety
requirements or a decrease in performance.
- The owner makes the decision whether to finish using the burner, or replacing and disposing of it based on the actual state of the
appliance and any repair costs.
- The use of the burner for other purposes after the expiry of the terms of use is strictly prohibited.
Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
1
turn the burner’s main switch to 0 (Off position)
2
disconnect the power mains
3
close the fuel cock of the supply line
Burner disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.
WIRING DIAGRAMS
Refer to the attached wiring diagrams.
WARNING
1 - Electrical supply 230V / 400V 50Hz 3N a.c.
2 - Do not reverse phase with neutral
3 - Ensure burner is properly earthed
Fig. 15: Detection by photocell QRA..
Control box
Minimum detection signal
Siemens LME7...
70µA (with UV detector)
Содержание HTLX 1025.1
Страница 47: ...PART III MAINTENANCE 47...
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......