PART IV: MAINTENANCE
58
TROUBLESHOOTNG GUIDE - Gas operation
BURNER DOESN'T LIGHT
* No electric power supply
* Wait until power supply is back
* Main switch open
* Close the switch
* Thermostats open
* Check set points and thermostat connections
* Bad thermostat set point or broken thermostat
* Set or replace the thermostat
* No gas pressure
* Restore gas pressure
* Safety devices (manually operated safety
thermostat or pressure switch and so on) open
* Restore safety devices; wait that boiler reaches its temperature
then check safety device functionality.
* Broken fuses
* Replace fuses. Check current absorption
* Fan thermal contacts open (only three phases)
* Reset contacts and check current absorption
* Burner control locked out
* Reset and check its functionality
* Burner control damaged
* Replace burner control
GAS LEAKAGE: BURNER LOCKS OUT (NO FLAME)
* Gas flow too low
* Increase the gas flow
* Check gas filter cleanness
* Check butterfly valve opening when burner is starting (only
Hi-Low flame and progressive)
* Ignition electrodes discharge to ground because
dirty or broken
* Clean or replace electrodes
* Bad electrodes setting
* Check electrodes position referring to instruction manual
* Electrical ignition cables damaged
* Replace cables
* Bad position of cables in the ignition transformer
or into the electrodes
* Improve the installation
* Ignition transformer damaged
* Replace the transformer
BURNER LOCKS OUT WITH FLAME PRESENCE
* Bad flame detector set
* Flame detector damaged
* Replace or adjust flame detector
* Bad cables of flame detector
* Check cables
* Burner control damaged
* Replace burner control
* Phase and neutral inverted
* Adjust connections
* Ground missing or damaged
* Check ground continuity
* Voltage on neutral
* Take off tension on neutral
* Too small flame (due to not much gas)
* Adjust gas flow
* Check gas filter cleanness
* Too much combustion air
* Adjust air flow rate
BURNER CONTINUES TO PERFORM PRE-PURGE
* Burner control damaged
* Replace burner control
* Air servomotor damaged
* Replace servomotor
BURNER CONTINUES TO PERFORM ALL ITS FEA-
TURES WITHOUT IGNITING THE BURNER
* Air pressure switch damaged or bad links
* Check air pressure switch functions and links
* Burner control damaged
* Replace burner control
BURNER LOCKS OUT WITHOUT ANY GAS FLOW
* Gas valves don’t open
* Check voltage on valves; if necessary replace valve or the
burner control
* Check if the gas pressure is so high that the valve cannot open
* Gas valves completely closed
* Open valves
* Pressure governor too closed
* Adjust the pressure governor
* Butterfly valve too closed
* Open the butterfly valve
* Maximum pressure switch (if installed ) open.
* Check connection and functionality
* Air pressure switch doesn’t close the NO contact * Check connections
* Check pressure switch functionality
BURNER LOCKS OUT AND THE CONTROL WIN-
DOW SHOWS A P (SIEMENS & STAEFA ONLY)
* Air pressure switch damaged (it keeps the
stand-by position or badly set
* Check air pressure switch functionality
* Reset air pressure switch
* Air pressure switch connections wrong
* Check connections
* Air fan damaged
* Replace motor
* No power supply
* Reset power supply
* Air damper too closed
* Adjust air damper position
BURNER LOCKS OUT DURING NORMAL RUNNING
* Flame detector circuit interrupted
* Check wiring
* Check photocell
* Burner control damaged
* Replace burner control
* Maximum gas pressure switch damaged or
badly set
* Reset pressure switch or replace it
WHEN STARTING THE BURNER OPENS FOR A
WHILE THE VALVES AND THEN REPEATS FROM
THE BEGINNINGTHE CYCLE FROM PRE-PURGE
* Gas pressure switch badly set
* Reset the pressure switch
* Gas filter dirty
* Clean gas filter
* Gas governor too low or damaged
* Reset or replace the governor
BURNER STANDS WHILE RUNNING WITHOUT ANY
SWITCHING OF THERMOSTATS
* Thermal contacts of fan motor open
* Reset contacts and check values
* Check current absorption
FAN MOTOR DOESN'T START
* Internal motor wiring broken
* Replace wiring or complete motor
* Fan motor starter broken
* Replace starter
* Fuses broken (three phases only)
* Replace fuses and check current absorption
BURNER DOESN'T SWITCH TO HIGH FLAME
* Hi-low flame thermostat badly set or damaged
* Reset or replace thermostat
* Servomotor cam badly set
* Reset servomotor cam
SOMETIMES THE SERVOMOTOR RUNS IN THE
WRONG WAY
* Servomotor capacitor damaged
* Replace capacitor
Содержание HRX92R-FGR
Страница 46: ...PART III OPERATION 46 Fig 25...
Страница 47: ...PART III OPERATION 47...
Страница 61: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Страница 68: ...8 Parameters level heating engineer...
Страница 110: ...50 ERROR CODE TABLE...
Страница 111: ...51...
Страница 112: ...52...
Страница 113: ...53...
Страница 114: ...54...
Страница 115: ...55...
Страница 116: ...56...
Страница 117: ...57...
Страница 118: ...58...
Страница 119: ...59...
Страница 120: ...60...
Страница 121: ...61...
Страница 122: ...62...
Страница 123: ...63...
Страница 124: ...64...
Страница 126: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 129: ......
Страница 130: ......
Страница 131: ......