PART I: SPECIFICATIONS
8
* NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
1.3 Country and usefulness gas categories
1.4 Fuel
BURNER TYPE
HR512A LG..
HR515A LG..
HR520A LG..
HR525A...50
LG..
HR525A...xx
LG..
Output
min. - max. kW
600 - 4500
770 - 5200
1000 - 6400
2000 - 6700
2000 - 8000
Fuel
L.P.G. - Light oil
Category
I
3B/P
Gas rate-
LPG
min.- max. (Stm
3
/h)
22 - 167
28 - 194
37 - 238
74 - 250
74 - 300
Gas pressure
mbar
(
see Note 2
)
Light oil rate
min.-max. kg/h
50 - 379
65 - 438
84 - 539
168 - 564
168 - 674
Oil viscosity
2 - 7.4 cSt @ 40°C
Oil density
kg/m
3
840
Light oil train inlet pressure
bar max
2
Power supply
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
10.8
13
17
22
22
Electric motor
kW
9.2
11
15
18.5
18.5
Pump motor
kW
1.1
1.5
1.5
3
3
Protection
IP40
Operation
Progressive - Fully modulating
Gas train 50
Valves size / Gas connection
50 / Rp2
50 / Rp2
50 / Rp2
50 / Rp2
Gas train 65
Valves size / Gas connection
65 / DN65
65 / DN65
65 / DN65
-
65 / DN65
Gas train 80
Valves size / Gas connection
80 / DN80
80 / DN80
80 / DN80
-
80 / DN80
Gas train 100
Valves size / Gas connection
100 / DN100
100 / DN100
100 / DN100
-
100 / DN100
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service (*)
Intermitent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
); for L.P.G. (net calorific value H
i
= 93.5 MJ/Stm
3
)
Note2:
Maximum gas pressure = 500mbar (with
Siemens VGD)
Minimum gas pressure = see gas curves.
GAS
CATEGORY
COUNTRY
I
2H
AT ES GR SE
FI
IE
HU
IS
NO CZ DK GB
IT
PT CY EE LV
SI
MT SK BG LT RO TR CH
I
2E
LU
PL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2E( R ) B
BE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2L
NL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2ELL
DE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2Er
FR
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ATTENTION! The burner must be used only with the fuel specified in the burner data
plate .
Type --
Model
--
Year --
S.Number --
Output --
Oil Flow
--
Fuel
--
Category --
Gas Pressure
--
Viscosity --
El.Supply --
El.Consump. --
Содержание HR91A
Страница 42: ...PART III OPERATION 42 Fig 18...
Страница 51: ...PART IV MAINTENANCE 51 12 0 BURNER EXPLODED VIEW...
Страница 53: ......
Страница 54: ......
Страница 55: ......