![Unigas HR512A Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/unigas/hr512a/hr512a_manual-of-installation-use-and-maintenance_842296046.webp)
PART IV: MAINTENANCE
46
9.2 Replacing the spring in the gas valve group
9.3 Light oil filter maintenance
9.4 Removing the combustion head
1
Remove the top
H
.
2
Remove the
UV
detector out of its housing: disconnect electrode cables and the light oil flexible hoses.
3
Loosen the screws
V
holding the gas manifold
G
, loosen the connectors
E
.
4
Some models are provided with the
T
baffle. Move the gas manifold ahead and remove the baffle.
5
Pull out the complete group as shown in the picture below.
6
Clean the combustion head by means of a vacuum cleaner; scrape off the scale by means of a metallic brush.
Note:
to replace the combustion head, reverse the operations described above.
9.5 Electrodes Adjustment
To replace the spring in the gas valve group,proceed as follows:
1
Carefully twist the protection cap 1 and the O-ring 2.
2
remove the “set value” spring 3 from housing 4.
3
Replace spring 3.
4
Carefully insert the new “set value” spring. Pay attention to mount properly.
First insert the spring part with smaller diameter in the housing.
5
Place O-ring 2 in protective cap 1. Screw in the protective cap with the O-
ring in it.
6
Stick the adhesive label for spring identification on the type plate.
For correct and proper servicing, proceed as follows:
1
cutoff the required pipe section;
2
unscrew the filter cup;
3
remove the filtering cartridge, wash it with gasoline; if necessary, replace it; check the tightening
O-rings and replace them if necessary;
4
replace the cup and restore the pipe line.
1
3
SKP Siemens actuator
E
V
H
G
T
G
Содержание HR512A
Страница 42: ...PART III OPERATION 42 Fig 18 ...
Страница 51: ...PART IV MAINTENANCE 51 12 0 BURNER EXPLODED VIEW ...
Страница 53: ......
Страница 54: ......
Страница 55: ......