PART III: OPERATION
29
AIR FLOW AND FUEL ADJUSTMENT
Adjustments - brief description
The air and fuel rates adjustments must be performed at the maximum ouptput first (“high flame”): see the LMV related manual.
Check that the combustion parameters are in the suggested limits.
Check the flow rate measuring it on the counter or, if it was not possible, verifying the combustion head pressure by means of a dif-
ferential pressure gauge, as described on par. “Measuring the gas pressure in the combustion head”.
Then, adjust the combustion values by setting the “gas/air” ratio” curvepoints (see the LMV related manual).
Set, now, the low flame output (according to the procedure described on the “Siemens LMV manual”) in order to avoid the low
flame output increasing too much or that the flues temperature gets too low to cause condensation in the chimney.
User interface
The AZL2x.. display is shown below:
The keys functions are the following:
WARNING! During commissioning operations, do not let the burner operate with insufficient air flow (danger of
formation of carbon monoxide); if this should happen, make the fuel decrease slowly until the normal combustion
values are achieved.
WARNING! the combustion air excess must be adjusted according to the values in the following chart.
Recommended combustion parameters
Fuel
Recommended (%) CO
2
Recommended (%) O
2
Natural gas
9 ÷ 10
3 ÷ 4.8
LPG
11 ÷ 12
2.8 ÷ 4.3
Key F
Used to adjust the “fuel” actuator position (
F
uel): :
While pressing the
F
key, the “fuel” actuator position can be changed by means of the
+
and
-
keys.
Key A
Used to adjust the “air” actuator position (
A
ir):
While pressing the
A
key, the “air” actuator position can be changed by means of the
+
and
-
keys.
Содержание G258A
Страница 46: ......
Страница 47: ......
Страница 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 3 01 2017...
Страница 56: ...8 Parameters level heating engineer...
Страница 98: ...50 ERROR CODE TABLE...
Страница 99: ...51...
Страница 100: ...52...
Страница 101: ...53...
Страница 102: ...54...
Страница 103: ...55...
Страница 104: ...56...
Страница 105: ...57...
Страница 106: ...58...
Страница 107: ...59...
Страница 108: ...60...
Страница 109: ...61...
Страница 110: ...62...
Страница 111: ...63...
Страница 112: ...64...
Страница 114: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...
Страница 117: ......
Страница 118: ......
Страница 119: ......
Страница 134: ......
Страница 143: ......
Страница 144: ......
Страница 145: ...MANUAL FOR OPERATION AND CALIBRATION MODULATOR SIEMENS RWF 40 M12905CH Rev 07 11 09...
Страница 161: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Страница 176: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Страница 177: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Страница 178: ...M12927CA MOUNTING 2...
Страница 194: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Страница 195: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Страница 216: ......
Страница 217: ...23 Note Specifications and data subject to change Errors and omissions excepted...