26

Block 500: Air/fuel ratio control

Param.

Descrizione

Description

Password

LM

V20

LM

V27

LM

V26

LM

V37

501

Posizione 

servocomando combustibile

 in 

assenza di fiamma (no-flame)

Indice 0

 = posizione di sosta = 0° 

Indice 1

 = posizione preventilazione = 0° 

Indice 2

 = posizione postventilazione = 15° 

No-flame position fuel actuator

Index 0

 = no-load position = 0°

Index 1

 = prepurge position = 0°

Index 2

 = postpurge position = 15°

OEM / Service

x

x

x

502

Posizione 

servocomando aria

 in assenza di 

fiamma (no-flame)

Indice 0

 = posizione di sosta = 0° 

Indice 1

 = posizione preventilazione = 90° 

Indice 2

 = posizione postventilazione = 45° 

No-flame position air actuator

Index 0

 = no-load position = 0°

Index 1

 = prepurge position = 90°

Index 2

 = postpurge position = 45°

OEM / Service

x

x

x

503

% giri motore con inverter 

0% = ventilatore 

fermo, 100% = ventilatore al massimo della 
velocità 

Indice 0

 = posizione di sosta = 0% 

Indice 1

 = posizione preventilazione = 100% 

Indice 2

 = posizione postventilazione = 50% 

No-flame speeds VSD 
Index 0 = no-load speed = 0% 
Index 1 = prepurge speed  = 100%
Index 2 = postpurge speed = 50%

OEM / Service

x

x

504

Combustibile 1 - Posizione 

servocomando 

combustibile

 in assenza di fiamma (no-

flame)

Indice 0

 = posizione di sosta = 0° 

Indice 1

 = posizione preventilazione = 0° 

Indice 2

 = posizione postventilazione = 15° 

Fuel 1 
No-flame position fuel actuator

Index 0

 = no-load position = 0°

Index 1

 = prepurge position = 0°

Index 2

 = postpurge position = 15°

OEM / Service

x

505

Combustibile 1 - Posizione 

servocomando 

aria

 in assenza di fiamma (no-flame)

Indice 0

 = posizione di sosta = 0° 

Indice 1

 = posizione preventilazione = 90° 

Indice 2

 = posizione postventilazione = 45° 

Fuel 1 
No-flame position air actuator

Index 0

 = no-load position = 0°

Index 1

 = prepurge position = 90°

Index 2

 = postpurge position = 45°

OEM / Service

x

506

Combustibile 1 -

 % giri motore con inverter 

0% = ventilatore fermo, 100% = ventilatore al 
massimo della velocità 

Indice 0

 = posizione di sosta = 0% 

Indice 1

 = posizione preventilazione = 100% 

Indice 2

 = posizione postventilazione = 50% 

Fuel 1 
No-flame speeds VSD 
Index 0 = no-load speed = 0% 
Index 1 = prepurge speed  = 100%
Index 2 = postpurge speed = 50%

OEM / Service

x

522

Tempo rampa di salita inverter

Ramp up

OEM / Service

x

x

523

Tempo rampa di discesa inverter

Ramp down

OEM / Service

x

x

Содержание E150X

Страница 1: ...M039624CA 0 2 09 2022 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES MANUAL OF INSTALLATION USE MAINTENANCE E115X E150X E180X Microprocessor controlled LMV 2x 3x Gas burners...

Страница 2: ...non original components whether spare parts kits accessories and optionals Force majeure Furthermore the manufacturer declines all responsibility for non compliance with this manual Personnel training...

Страница 3: ...rner shut down reser the control box by means of the RESET pushbutton If a second shut down takes place call the Tech nical Service without trying to RESET further The unit shall be operated and servi...

Страница 4: ...UNI EN ISO 12100 2010 Safety of machinery General principles for design Risk assessment and risk reduction For the following information please refer to the data plate Burner type and burner model mu...

Страница 5: ...s according to load curves in order to achieve the correct proportion between fuel and air flows and to optimize flue gas parameters The adjustable combustion head can improve the burner performance b...

Страница 6: ...ast tube aluminium air intake LR Extended blast tube ABS polymer silenced air intake LP Extended blast tube aluminium air intake 5 DESTINATION COUNTRY see data plate 6 BURNER VERSION A Standard Y Spec...

Страница 7: ...Valves size Gas connection 65 2 1 2 DN65 Valves size Gas connection 80 3 DN80 Operating temperature C 10 50 Storage Temperature C 20 60 Working service Intermittent NOx emissions 80 mg kWh Class 3 EN6...

Страница 8: ...634 362 259 280 233 300 453 M10 330 216 250 233 457 130 327 541 608 210 155 50 996 362 472 342 526 65 1080 718 362 562 432 593 292 80 1054 692 362 562 432 565 310 E180X 40 69 1192 1292 403 400 500 758...

Страница 9: ...cessary to the available gas pressure value upstream the burner s gas valve Then subtract the backpressure The result is called pgas Draw a vertical line matching the furnace input value 600kW in the...

Страница 10: ...ne On this diagram the maximum output point is usually reached by adjsuting the combustion head to its MAX position see paragraph Adjusting the combustion head the minimum output point is reached sett...

Страница 11: ...nning of this chapter The values in the diagrams refer to natural gas with a calorific value of 8125 kcal Stm3 15 C 1013 mbar and a density of 0 714 kg Stm3 The values in the diagrams refer to GPL wit...

Страница 12: ...from the boiler s Technical specifications Measuring gas pressure in the combustion head In order to measure the pressure in the combustion head insert the pressure gauge probes one into the combustio...

Страница 13: ...alified personnel All handling operations must be carried out with appropriate resources and qualified personnel ATTENTION Use intact and correctly dimensioned hoisting equipment conforms to the local...

Страница 14: ...mensions are described in the diagram In case the burner must be coupled with boilers with a combustion chamber smaller in dia meter or shorter than those described in the diagram please contact the s...

Страница 15: ...age pressure switch PGCP 1 Filter 6 Butterfly valve 2 Pressure switch PGMIN 7 Pressure transducer 3 Safety valve with built in gas governor 8 Main burner 4 Proving system pressure switch PGCP 9 Antivi...

Страница 16: ...unt the gas train proceed as follows NOTE the bellows unit the manual cutoff valve and the gaskets are not part of the standard supply WARNING before executing the connections to the gas pipe network...

Страница 17: ...Insert MB DLE note position of O rings 3 Remove MultiBloc between the threaded flanges 4 After installation perform leakage and functional test 5 Disassembly in reverse order Keys 1 Gasket 2 Gas filt...

Страница 18: ...UCIATORE 185 501939 PGMAX PGCP PGMI EV1 EV2 S EV2 EV1 PGMAX PGMIN VD R PGCP VD V VD V VD R PS PS pressure sensor Gas filter Example of gas train MBE A A C B B C 1 Mount flange into pipe systems Use ap...

Страница 19: ...ressure sensor includes a vent limiter according to UL 353 and ANSI Z21 18 CSA 6 3 No venting required in loca tions where vent limiters are accepted by the jurisdiction 4 Only PS pressure sensors spe...

Страница 20: ...a suitable replacement Siemens VGD VRD SKPx5 Auxiliary optional micro switch Gas valve Caution the SKP2 diaphragm D must be vertical WARNING removing the four screws BS causes the device to be unserv...

Страница 21: ...PART II INSTALLATION 21 Speed Sensor AGG 5 310 is a speed sensor kit used to monitor the speed of a motor This kit is used to mount the speed sensor directly on the motor casing...

Страница 22: ...with fan motor driven by inverter in addition to the air and fuel adjustment curves also have a fan motor speed adjustment curve Generally the curve of the inverter goes from 50 to 100 of the engine...

Страница 23: ...RC circuit Siemens between the terminal 2 terminal X3 04 4 in case of LMV2x LMV3x LMV5x LME7x of the base and the earth terminal RC466890660 For LMV5 control box please refer to the clabeling recomme...

Страница 24: ...NOMALIES THAT REQUIRED A SHUT DOWN OF THE BURNER IT S POSSIBLE TO ACT ON THE AUXILIARY LINE SWITCH LOCATED ON THE BURNER FRONT PANEL IN CASE OF A BURNER SHUT DOWN RESET THE CONTROL BOX BY MEANS OF THE...

Страница 25: ...s after the gas valves opening the ignition transformer is de energised and light B4 turns to off The burner operates in the low flame stage few seconds later the two stages operation begins and the b...

Страница 26: ...on is correct 9 Open the manual shut off valves slowly in order to prevent any water hammers that might seriously damage valves and pressure regulator 10 Check the sense of rotation of the electrical...

Страница 27: ...fo mode 3 Parametere setting mode 4 Plant heat request 5 Oil pre heater energised 6 Fan motor energised 7 Ignition transformers energised 8 Open valves 9 Flame 10 Lock unlock codes 11 Closing actuator...

Страница 28: ...rge time Ph36 Verso posizione accensione Traveling to the ignition position Ph38 t3 tempo preaccensione t3 preignition time Ph40 TSA1 primo tempo sicurezza trasformatore accensione ON TSA1 primo tempo...

Страница 29: ...ed By pressing or it is possible to scroll up or down the parameter list 4 If a dot line is shown on the right there is no enough room for complete visualisation press enter again the data will be com...

Страница 30: ...age will flash 10 Press InFo for more than three seconds or for more than three seconds orto return to the normal display If a message like the one below is shown during operation it means that the bu...

Страница 31: ...on number and lock codes 1 the first parameter will be 954 the percentage of flame is shown on the right By pressinf or it is possible to scroll up down the parameter list 2 Once the last parameter is...

Страница 32: ...essure stabilizer is adjusted by operating the screw VS located under the cover C By screwing down the pressure is increased and by unscrewing it is reduced Note the screw VSB must be removed only in...

Страница 33: ...ustments do not exceed a value that creates a hazardous condition to the burner Adjusting output pressure for positive pressure systems requires PS 10 40 or PS 50 200 Outlet pressure MIN 10 25 50 75 M...

Страница 34: ...he position loosen the VB screw and slightly move the combustion head backwards turning clockwise the knob VRT Fasten VB screw when the adjustment is accomplished Depending on the boiler application i...

Страница 35: ...er increase the regulation pressure by slowly turning the control knob clockwise until the burner stops taking care it does not go into lockout and the display shows the error Err c20 d0 As for the ga...

Страница 36: ...condition of the burner boiler gasket Eventually substitute it Check the fan s motor no specific maintenance is needed In case of anomalous noises when running check the condition of the bearings and...

Страница 37: ...filter if the pressure difference between pressure connection 1 and 3 Fig 1 Fig 3 is twice as high compared to the last check You can change the filter without removing the fitting 1 Interrupt the gas...

Страница 38: ...proper position taking care to place it inbetween the guides as not to hamper the cap replacement 4 be sure to replace the O ring into its place C and replace the cover fastening by the proper screws...

Страница 39: ...quotes shown othe next picture E150X E180X M ATTENTION avoid the ignition and detection electrodes to contact metallic parts blast tube head etc other wise the boiler s operation would be compromised...

Страница 40: ...23 24 25 26 28 29 27 A A B B C C D D E E 0 1 2 3 4 5 6 7 35 34 33 32 31 30 8 15 14 9 10 11 12 13 17 18 19 20 16 21 22 23 24 25 26 28 29 27 30 mg 36 Holes 27 Open air holes 50 80 mg 36 Holes 9 Open air...

Страница 41: ...continue using it due to non compliance with safety requirements or a decrease in performance The owner makes the decision whether to finish using the burner or replacing and disposing of it based on...

Страница 42: ...itch functions and links Burner control damaged Replace burner control BURNER LOCKS OUT WITHOUT ANY GAS FLOW Gas valves don t open Check voltage on valves if necessary replace valve or the burner cont...

Страница 43: ......

Страница 44: ...a L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors an...

Страница 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...

Страница 46: ...900 Process data 32 Actuators references 33 Gas proving system 33 Air fuel curve points 33 COMMISSIONING THE BURNER 34 Warm setting 38 Cold setting 39 BURNER STARTUP WITH LMV2x ALREADY PROGRAMMED 40...

Страница 47: ...CTIONS FOR BURNERS z The burner should be installed in a suitable room with ventilation openings complying with the requirements of the regulations in force and sufficient for good combustion z Only b...

Страница 48: ...ditions such as the development of toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 2009 142 EC Gas Appliances Directive 2006 95 EC on low voltage Directi...

Страница 49: ...apparatus EN 50165 Electrical equipment of non electric appliances for household and similar purposes Safety requirements UNI EN 746 2 Industrial thermoprocessing equipment Burner data plate For the...

Страница 50: ...forms all the burner control functions and of the Siemens AZL local programming unit that interfaces the system with the user Keys 1 Burner 2 AZL2 3 Air actuator 4 Fuel actuator 5 LMV2 User interface...

Страница 51: ...ice mode Info and Enter keys Used for Info and Service menues Used as Enter key in the setting modes Used as Reset key in the burner operation mode Used to enter a lower level menu Key Used to decreas...

Страница 52: ...8 Parameters level heating engineer...

Страница 53: ...ription Password 000 Internal parameters OEM Service 100 Informazioni generali General OEM Service Info 200 Controllo bruciatore Burner control OEM Service 300 Controllo bruciatore solo LMV26 Burner c...

Страница 54: ...kup data set Service Info Param Descrizione Description Password LMV20 LMV27 LMV26 LMV37 102 Data produzione in gg mm aa Identification date yy mm dd Service Info x x x 103 Numero identificativ Identi...

Страница 55: ...ed OEM Service x x 145 Indirizzo dispositivo per Modbus Device address for Modbus OEM Service x x 146 Velocit di trasmissione per Modbus Baud rate for Modbus OEM Service x x 147 Parit per Modbus Parit...

Страница 56: ...erci zio azzerabile da Service Fuel 1 Operation hours resettable Service Info x 174 Fuel 1 secondo combustibile Numero di partenze azzerabile da Service Fuel 1 Number of startups resettable Service In...

Страница 57: ...e fuel train modula ting multistage actuators etc __ undefined delete curves 1 gas direct ignition G mod 2 ignition by gas pilot connected between the two gas solenoid valves EV1 EV2 Gp1 mod 3 ignitio...

Страница 58: ...x x x 210 Allarme impedimento avviamento 0 non attivo 1 attivo Alarm in the event of start prevention 0 deactivated 1 activated OEM Service x x x 211 Tempo aumento giri ventilatore valore fab brica 2...

Страница 59: ...nge impostazione 20s 60min Gas Prepurge time default value 20s range 20s 60min OEM Service x x x 226 Gas tempo di preaccensione valore fab brica 2s range impostazione 0 2s 60min Gas Preignition time d...

Страница 60: ...ivo 1 esso modificabile solo su LMV37 Dal punto di vista della sicurezza il funzionamento continuo valido esclusiva mente per bruciatori di gas con elettrodo di rilevazione Gas Forced intermittent ope...

Страница 61: ...Postpurge time 3 abortion with load controller LR ON OEM Service x x x 261 Olio sonda rilevazione fiamma attivo valore fabbrica 0 0 QRB QRC 1 ION QRA Oil active detector flame evaluation default value...

Страница 62: ...0 inactive 1 active from phase 38 2 active from safety time TSA OEM Service x x 277 Olio Pressostato olio di massima ingresso POC 0 inattivo 1 pressostato olio di massima 2 POC Oil Pressure switch max...

Страница 63: ...lvole EV1 EV2 del gas regolazione pneumatica Gp1 mod pneu 9 accensione tramite pilota gas con attacco a monte dell elettrovalvola EV1 del gas regolazione pneumatica Gp2 mod pneu 10 olio modulante con...

Страница 64: ...ore fabbrica 1 0 QRB QRC 1 ION QRA Fuel 1 Gas active detector flame evalua tion default value 1 0 QRB QRC 1 ION QRA OEM Service x 322 Combustibile 1 Gas Preventilazione valore fabbrica 1 1 attivo 0 no...

Страница 65: ...Intervallo 2 valore fabbrica 2s range impostazione 0 2s 60min Fuel 1 Gas Interval 2 default value 2s range 0 2s 60min OEM Service x 333 Combustibile 1 Gas Tempo postcombu stione valore fabbrica 8s ra...

Страница 66: ...t filling time default value 3s range 0 2s 10s OEM x 345 Combustibile 1 Gas tempo test pressione gas valore fabbrica 10s range imposta zione 0 2s 60s Fuel 1 Gas proving test time gas pres sure default...

Страница 67: ...mbustibile 1 Olio tempo di risposta a cadute di pressione entro TSA1 e TSA2 valore fabbrica 1 8s range imposta zione 0 2s 14 8s Fuel 1 Oil time to respond to pressure faults in TSA1 and TSA2 default v...

Страница 68: ...censione corta Ph38 fase pro gramma 38 1 preaccensione lunga con ventilatore Ph22 fase programma 22 Fuel 1 Oil time oil ignition default value 1 0 short preignition Ph38 progr phase 38 1 long preignit...

Страница 69: ...ting the cur ves OEM Service x x x 403 Curve controllo inverter F A si accede alla lista dei punti da impostare da P0 a P9 con sultare paragrafo Impostazione curve Ratio control curves VSD curve setti...

Страница 70: ...repurge speed 100 Index 2 postpurge speed 50 OEM Service x x 504 Combustibile 1 Posizione servocomando combustibile in assenza di fiamma no flame Indice 0 posizione di sosta 0 Indice 1 posizione preve...

Страница 71: ...di carico per modulazione valore fabbrica n d range imposta zione 20 100 Lower load limit default value n d range 20 100 OEM Service x x x 546 Percentuale massima di carico per modula zione valore fa...

Страница 72: ...0 combustibile Indice 1 aria Tolerance limit of position monitoring 0 1 Index 0 fuel Index 1 air OEM Service x x x 608 Combustibile 1 Impostazione punto di riferi mento Indice 0 combustibile Indice 1...

Страница 73: ...top SQN1 3 both OEM x 613 Tipo di servocomando Indice 0 combustibile Indice 1 aria 0 5s 90 1Nm 1 2Nm 3Nm 1 10s 90 6Nm 2 17s 90 10Nm Type of actuator Index 0 fuel Index 1 air 0 5 s 90 1Nm 1 2Nm 3Nm 1 1...

Страница 74: ...tion of analog output default value 0 0 DC 0 10 V 1 DC 2 10 V 2 DC 0 2 10 V OEM Service LMV27 x x ATTENTION as for SQM3x actuators set the direction according to the acutator function As far as SQN1x...

Страница 75: ...ror history 701 725 02 diagnostic code Service Info Storico errori 701 725 03 classe errore Error history 701 725 03 error class Service Info Storico errori 701 725 04 fase Error history 701 725 04 ph...

Страница 76: ...Active load source OEM Service 945 Solo con LMV26 Combustibile attuale 0 combustibile 0 1 combustibile 1 Actual fuel 0 fuel 0 1 fuel 1 Service Info 947 Risultato interrogazione contatti codifica bit...

Страница 77: ...a leakage test designed to detect leaking gas valves and if necessary to pre vent the valves from opening or ignition from being switched on Lockout is initiated When performing valve proving the gas...

Страница 78: ...2x already programmed At the first LMV startup the AZL display will show It means that the unit was never set or that no mode was chisen or that some parameters have to be set furthert Push F fuel and...

Страница 79: ...l elettrov EV1 del gas Gp2 mod 4 accensione a gasolio modul Lo mod 5 accens a gasolio bistadio Lo 2 stage 6 accens a gasolio tristadio Lo 3 stage Burner operating mode fuel train mod multi stage actua...

Страница 80: ...e fuel actuator 0F until the requested value is reached for example 12 15 see below for the ignition point or press F and to decrease the angle To set the air damper opening angle 0A in the ignition p...

Страница 81: ...er is operating warm setting by pressing the ENTER InFo or while the burner is in stand by mode cold setting by pressing ENTER CAUTION at the first burner adjustment it is recommended to set the maxim...

Страница 82: ...ugh the flue analyser Keep the air excess inside normal figures from 3 to 7 residual O2 operating by means for the air damper servomotor Keep increasing the air damper opening and then the gas throttl...

Страница 83: ...t before end by pressing ESC or for a faulty shutdown the message OFF UPr Start preven tion will be diplayed until all the curvepoints will be set Note2 if the gas flow rate at high flame point maximu...

Страница 84: ...e than 5 seconds to process the curve downwards The curve is then a straight line go on checking the combustion values point by point change them if necessary and in case linearise the curve again Bef...

Страница 85: ...e burntime Ph72 travelling to postpurging Ph74 postpurge countdown is displayed Press ESC the parameter 546 Setting the maximum load is displayed Then press to exit the programming mode The display wi...

Страница 86: ...n Longer or shorter pushes on the button do not produce a reset so that the system maintains the lockout position Timeout for menu operation The time for automatically leaving the parameter setting le...

Страница 87: ...levels By means of a proper use of the keys it is possible to enter the various level parameters as shown in the following flow chart The burner and consequently the LMV2x are factory set the air and...

Страница 88: ...nd go back to the flashing number The Info level shows some basic parameters as 5 Example choose parameter 102 to show the date the display shows parameter 102 flashing on the left and characters _ _...

Страница 89: ...h another message Diagnostic code in the example diagnostic code 3 Record the codes and find out the fault in the Error table To perform the reset press InFo for one second The unit displays an event...

Страница 90: ...ht By pressinf or it is possible to scroll up down the parameter list 2 Once the last parameter is accessed 143 by pressing the End message will blink 3 Press InFo for more than three seconds or for m...

Страница 91: ...ignition time OFF Ph44 t44 intervallo 1 t44 interval 1 Ph50 TSA2 secondo tempo sicurezza TSA2 2nd safety time Ph52 t52 intervallo 2 t52 interval 2 Ph60 Funzionamento 1 stazionario Operation 1 stationa...

Страница 92: ...ess ENTER until the display will show with the button go to the group 000 of the parameters and press with the buttons and go to 050 parameter press the disply show press again with the button select...

Страница 93: ...uttons by pressing enter to confirm iWith the buttons go to the group 000 of the parameters press end select the 050 parameter press the disply show with the button the display shows press again with...

Страница 94: ...50 ERROR CODE TABLE...

Страница 95: ...51...

Страница 96: ...52...

Страница 97: ...53...

Страница 98: ...54...

Страница 99: ...55...

Страница 100: ...56...

Страница 101: ...57...

Страница 102: ...58...

Страница 103: ...59...

Страница 104: ...60...

Страница 105: ...61...

Страница 106: ...62...

Страница 107: ...63...

Страница 108: ...64...

Страница 109: ...L PE QRB C N ION QRB C X75 1 X10 05 1 X10 06 1 X3 02 1 PLUFT FLAMME P L PE N L 2 3 L X5 03 1 X8 04 1 X8 02 1 X5 03 X10 05 X7 01 X8 04 X8 02 X75 X10 06 X3 02 X3 04 N PE L 1 1 1 1 1 1 1 1 1 QRA QRA QRA...

Страница 110: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...

Страница 111: ...tion speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply 4 Feedback signal 3 PWM Pulse Width Modulation speed output 2 GND signal reference 1 External supply 24V DC ConnectorX75 Con...

Страница 112: ...dulation speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply ConnectorX75 ConnectorX64 ConnectorX74 2 Fuel meter input 1 Supply fuel meter ConnectorX5 02 Connections Pmax 4 Feedback...

Страница 113: ......

Страница 114: ......

Страница 115: ......

Страница 116: ...and data subject to change Errors and omissions excepted C I B UNIGAS S p A Via L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail...

Отзывы: