PART I: SPECIFICATIONS
6
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Fuel
The burner technical specifications, described in this manual, refer to natural gas (calorific net value Hi = 9.45 kWh/Stm
3
, density
ρ
=
0.717 Kg/Stm
3
) and LPG (calorific net value Hi = 26.79 kWh/Stm
3
, density
ρ
= 2.151 Kg/Stm
3
). For different fuel such as town gas and
biogas, multiply the values of flow and pressure by th corrective factors shown in the table below.
For example, to obtain the flow and pressure values for the biogas:
Type
E115X
Model
M-.
MD. SR.
*.
A. 1.
80.
ES
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
1 BURNER TYPE
E115X, E1450X, E180X
2 FUEL
M - Natural gas
L - LPG
B - Biogas
C - Town gas
3 OPERATION (Available versions)
PR - Progressive
MD - Fully modulating
4
BLAST TUBE AND AIR INLET CONFIGURA-
TION
(see the figure on page 5)
SR = Standard blast tube + ABS polymer (silenced) air intake
SP = Standard blast tube + aluminium air intake
LR = Extended blast tube + ABS polymer (silenced) air intake
LP = Extended blast tube + aluminium air intake
5 DESTINATION COUNTRY
* - see data plate
6 BURNER VERSION
A - Standard
Y - Special
7 EQUIPMENT
0 = 2 gas valves
1 = 2 gas gas proving system
7 = 2 gas maximum gas pressure switch
8 = 2 gas gas proving maximum gas pressure switch
8
GAS CONNECTION
see Specifications
32 = Rp1 1/4, 40 = Rp1 1/2, 50 = Rp2, 65 = DN65, 80 = DN80 100
= DN100
9 MICRO-PROCESSOR CONTROL
ES = with no O
2
trim control, with no VSD control
EO = with O
2
trim control, with no VSD control
Fuel
Hi
(KWh/Stm
3
)
ρ
(kg/Stm
3
)
f
Q
f
p
Town gas
4,88
0,6023
1,936
3,3
Biogas
6,395
1,1472
1,478
3,5
LPG
26,79
2,151
0,353
0,4
ATTENTION! The combustion head type and the settings depend on the fuel. The burner must be used only for its
intended purpose specified in the burner data plate .
ATTENTION: the corrective factors in the above table depend on the gas composition, so on the calorifc value and
the density of the gas. The above value can be taken only as reference.
Q
biogas
Q
naturalGas
1 478
=
p
biogas
p
naturalGas
3 5
=
Содержание E115X
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......