PART IV: OPERATION
28
4
make the safety chain enabling the system to start up
5
the combustion cycle starts: the system will show the operating stages
- Prepurging
(program phase no.30)
- Driving to ignition position
(program phase no.36)
- Ignition position
(program phase no.38)
- Fuel
(the fuel solenoid valves open)
- Flame
(the flame lights up)
- Driving to low flame
(the actuator drives to low flame).
NOTE:
the
C
and
A
, on the .
Once the ignition cycle ends, the main page is shown:
Main page
Set point:
temperature set-point
Act value:
actual temperature value
Load:
load percentage (burner output)
Flame:
percentage of flame detection current.
By pressing the ENTER key the display shows the second page:
Second page
Fuel
: it shows (in degrees) the fuel actuator position.
Air
: it shows (in degrees) the air actuator position.
Ax1..3
: auxiliaries.
VSD
: % value on the inverter maximum frequency
O2
: oxygen percentage
Ld
: load percentage (burner output).
Press the ENTER key to go back to the main page.
To access the
main menu
, from the main page, press the ESC key tiwce:
Main menu
By pressing the ESC key once, the
Operational Status
(first item in the main menu) menu is directly shown:
the
Operational Status
menu provides the following items:
Normal operation:
by selecting this item and pressing the ENTER key, the main page is showed; press ESC to go back to the main
Setpoint
80°C
Act.value
78°C
Load
24%
Flame
60%
Fuel
0.0
Air
1.8
Ax
VSD
0.0
Ax
O2
Ax
Ld.
0.0
OperationalStat
Operation
ManualOperation
Params & Display
Normal operation
Status/Reset
Fault History
Lockout History
Содержание E115X
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......