41
Set the air/fuel ratio curvepoints as described on chapter “Programming the LMV2x”
Note:
the other phases are
Ph60 = operation (OP= in modulation)
Ph62 = travelling to shutdown
Ph70 = off but in prepurge after the burntime
Ph72 = travelling to postpurging
Ph74 = postpurge (countdown is displayed)
Press ESC
the parameter “
546
” (Setting the maximum load) is displayed
Then press
to exit the programming mode.
The display will show:
Press
for a second time: the display will show the load percentage the burner is working at.
When the generator reaches the programmed set-point, the burner will be in stand-by: the display will show
Содержание C83X
Страница 42: ......
Страница 43: ......
Страница 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023 ...
Страница 52: ...8 Parameters level heating engineer ...
Страница 94: ...50 ERROR CODE TABLE ...
Страница 95: ...51 ...
Страница 96: ...52 ...
Страница 97: ...53 ...
Страница 98: ...54 ...
Страница 99: ...55 ...
Страница 100: ...56 ...
Страница 101: ...57 ...
Страница 102: ...58 ...
Страница 103: ...59 ...
Страница 104: ...60 ...
Страница 105: ...61 ...
Страница 106: ...62 ...
Страница 107: ...63 ...
Страница 108: ...64 ...
Страница 110: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax ...
Страница 113: ......
Страница 114: ......
Страница 115: ......
Страница 117: ...IG FU B ...
Страница 118: ......
Страница 119: ......
Страница 120: ......
Страница 121: ......
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......