PART III: OPERATION
35
Head adjusting
The combustion head position affects the flame stability.The diffuser position must be set during the commissioning according to the
regulation needs. The diffuser position is factory set as shown in figure ”A” (x = 10 mm). If different settings are required, it is possible
to change the position: loosen the VB screw and slightly move the combustion head backwards, turning clockwise the knob VRT.
Fasten VB screw when the adjustment is accomplished.
Depending on the boiler application, it is possible to act on the holes (figure B) to improve the flame stability and NOx, CO emission
values. If necessary, close/open the holes in figure “B” using the screws kit given with the burner.
CAUTION: perform these adjustments once the burner is turned off and cooled.
Attention! if it is necessary to change the head position, repeat the air and fuel adjustments described above.
“all-ahead” position
“all-backwards” head position
VRT
X
x = 10 mm
A
B
A
B
Содержание C83X
Страница 42: ......
Страница 43: ......
Страница 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023 ...
Страница 52: ...8 Parameters level heating engineer ...
Страница 94: ...50 ERROR CODE TABLE ...
Страница 95: ...51 ...
Страница 96: ...52 ...
Страница 97: ...53 ...
Страница 98: ...54 ...
Страница 99: ...55 ...
Страница 100: ...56 ...
Страница 101: ...57 ...
Страница 102: ...58 ...
Страница 103: ...59 ...
Страница 104: ...60 ...
Страница 105: ...61 ...
Страница 106: ...62 ...
Страница 107: ...63 ...
Страница 108: ...64 ...
Страница 110: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax ...
Страница 113: ......
Страница 114: ......
Страница 115: ......
Страница 117: ...IG FU B ...
Страница 118: ......
Страница 119: ......
Страница 120: ......
Страница 121: ......
Страница 122: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 126: ......
Страница 127: ......