pCOWeb 

 

                                                                           

 

Version 1.0 August 2007

 

5

TABLE 1.a – Status LED signals 

 

LED Status 

Meaning 

Notes 

Green flashing (3 times/sec) 

Regular Pco-pCOWeb communication  When running demanding tasks 

(sending a large number of 

notifications), this may be green 

steady for a few seconds 

Red flashing slowly (once every 2 

seconds) 

Pco-pCOWeb communication not 

established 

 

Single red flash and then flashing 

green 

Single Pco-pCOWeb 

communication error, one failed 

response from the Pco or attempt to 

write a variable with an index higher 

than 207. 

After 5 failed responses, the Status 

LED start flashing red until 

communication resumes 

Red steady  

Rescue mode 

 

[Off, then] green-red repeated in 

rapid succession, then green 

steady for 1-2 minutes 

PCOWeb reboot phase 

 

Green steady for 1-2 minutes 

PCOWeb reboot phase 

Wait for the conclusion of the reboot 

Red – Off slow (1second – 1 

second) repeated 3 times 

Recognition of button pressed 

durino the reboot for selecting the 

factory parameters) 

Release the button to confirm. 

Red – Off fast (3 times a second) 

repeated 3 times 

During the reboot, confirms the 

selection of the factory parameters 

by pressing the button 

 

Green-red repeated alternating 

(once a second) 

During the firmware update, writing 

block B to non-volatile memory 

Do not interrupt the power supply 

Red steady followed by green-red a 

number of times 

During the firmware update, writing 

block B to non-volatile memory 

Do not interrupt the power supply 

 

• 

Ethernet LED: displays the status of the physical network connection (Ethernet connection signals), 

regardless of whether the network parameters are correct; usually this must be green and flash when 

the data transits. 

 

TABLE 1.b – Ethernet LED signals 

 

Ethernet LED 

Meaning  

Notes 

Green steady 

Correct Ethernet data connection 

signals 

 

Green flashing 

Correct Ethernet data exchange 

 

Red 

No Ethernet signal detected 

 

 

Содержание PCOWeb

Страница 1: ...Instruction Manual PCOWeb Version 1 0 Date August 2007 Language English...

Страница 2: ...ely The public or private waste collection systems defined by local legislation must be used In addition the equipment can be returned to the distributor at the end of its working life when buying new...

Страница 3: ...ce button and LEDS 4 Installation pCOWeb on the pCO controller 6 Starting for the first time Accessing pCOWeb from a computer 7 Connecting pCOWeb to a PC 7 PC configuration 7 Accessing pCOWeb from a P...

Страница 4: ...d by the network administrator pCOWeb features Figure 1 b a button PUSHBUTTON and two indicator lights STATUS LED and ETHERNET LED Functions of the button When starting up the pCOWeb this is used to s...

Страница 5: ...reboot Red Off slow 1second 1 second repeated 3 times Recognition of button pressed durino the reboot for selecting the factory parameters Release the button to confirm Red Off fast 3 times a second...

Страница 6: ...on the two labels included in the packaging Once installed pCOWeb may however no longer be accessible Therefore during installation use the scissors to separate the two labels supplied and apply one i...

Страница 7: ...Configuration of the PC for direct connection to pCOWeb 2 Connection and start up of pCOWeb to check correct installation 3 Activation of the factory network setting button 4 Access to the pCOWeb fro...

Страница 8: ...the mouse on the Start button left 2 Choose Setting 3 Click Control Panel 4 Double click Network and dial up connections 5 Double click Local area connection 6 Click Properties the windows shown in Fi...

Страница 9: ...abled communication would not be possible 1 Open the Windows Control panel 2 Double click Internet options the windows shown in Figure 3 d above left will be displayed 3 Click Connections Another wind...

Страница 10: ...ing the dots 172 16 0 1 then press ENTER IMPORTANT before pressing ENTER wait for pCOWeb to complete the start up phase check that the Status LED is flashing normally otherwise the required web pages...

Страница 11: ...Configuration and then on the Network file where the following addresses need to be entered in the empty IP Address man and NetMask man files IP Address man network address with the last number chang...

Страница 12: ...ntered in the empty System name and System location like in the following screen At the end accept to click on Submit Having arrived at this point the pCOWeb needs to be reset which can be carried out...

Страница 13: ...he procedure described above has been carried out correctly check that using the address 172 16 0 1 in the Internet Explorer browser does not allow entry into the page Enter the new address given to t...

Страница 14: ...on the Start button left 2 Choose Setting 3 Click Control Panel 4 Double click Network and dial up connections 5 Double click Local area connection 6 Click Properties the windows shown in Figure 4 b...

Страница 15: ...our case for example http 10 0 8 56 1 Open the Windows Control panel 2 Double click Internet options the windows shown in Figure 4 d above left will be displayed 3 Click Connections Another window Fig...

Страница 16: ...eb the default Username and Password are httpadmin fhttpadmin The following examples assume that the current data being used are httpadmin fhttpadmin and the IP address is 10 0 8 56 Figure 4 c SmartFT...

Страница 17: ...pCOWeb Version 1 0 August 2007 17 Insert the web personalized CD the next screen appears Fig 4 g Click on Click Here To Enter in order to pass onto the successive screen Fig 4 h Figure 4 g...

Страница 18: ...1 0 August 2007 18 In below screen in order to select the family TELEPHONE SYSTEM or CONDITIONING Fig 4 h until the last selection Then the files and directory are selected and copied in the pCOWeb me...

Страница 19: ...pCOWeb Version 1 0 August 2007 19 In the screen below select the family Figure 4 i Figure 4 m Figure 4 n...

Страница 20: ...pCOWeb Version 1 0 August 2007 20 The files are copied to the usr local root flash http directory this is the pCOWeb memory Figure 4 o...

Страница 21: ...he operation mode green led or not grey led not lit up of the various resources and the indication of the temperature and relative humidity present in the room In the event of an alarm state a red led...

Страница 22: ...pCOWeb Version 1 0 August 2007 22 NOTE...

Страница 23: ...pCOWeb Version 1 0 August 2007 23 THIS PAGE HAS INTENTIONALLY BEEN LEFT BLANK...

Страница 24: ...rative Headquarters Viale della Tecnica 2 35026 Conselve PD Italy Tel 39 049 5388211 Fax 39 049 5388212 uniflair com info uniflair com P IVA 02160760282 C C I A A di PD R E A 212586 del 21 04 1988 R I...

Отзывы: