REGULATION OF COOLING CAPACITY
The unit’s cooling capacity is regulated by activating the various cooling capacity steps, depending on the
temperature measured by intake water sensor T1.
CHILLER INTAKE
T1
T2
RESERVOIR TANK
CHILLER OUTPUT
EXPANSION TANK
PLATE EXCHANGER
Refrigerant circuit diagram.
Sensor T2 on the chiller output line interrupts compressor function when the temperature drops below the
value set for risk of freezing.
25 % C
0 % Compressors
0 % V
100 % C
100% Fans
50 % C
75 % C
100% Pump
0 % P
Example of regulation as a function of sensor T1 temperature reading.