SETTING THE SAFETY DEVICES
The function parameter values set on the microprocessor control are given in the enclosed instruction
manual. The table below gives the settings of the safety devices; these are also on the data plate on the unit.
Component
Setting
Differential
Re-set
Refrigerant circuit (R22 – R407C)
High pressure pressostat (
AP1-AP2
)
27.5 bar
--
manual
Low pressure pressostat (
BP1-BP2
)
1
2.6 bar
1.4 bar
4.0 bar
Anti-freeze protection
1
4 °C
4 °C
Refrigerant safety valve (
VSA1-VSA2
) -
Models 0152…0302
32.0 bar
--
--
Refrigerant safety valve (
VSA1-VSA2
) -
Models 0403…0504
28.0 bar
--
--
Water circuit
Flow gauge
2
105 mbar
80 mbar
Water side safety valve
3.0 bar
1
Values refer to standard version with pure water.
2
With optional pump group.
Setting of safety devices.