background image

Two Negative Samples:

 Connect higher negative sample to

L

,lower negative sample to 

H

.

Two Positive Samples: 

Connect higher positive sample  to

H

, lower positive sample to 

L

.

One Negative and One Positive Sample:

 Connect positive

sample line to 

H

, negative sample line to 

L

.

For each right angle bend, add four feet to the computed line
length in order to determine correct pipe or  tubing size. If
either sample line connector is vented to the atmosphere, at-
tach an elbow to it so that the open end of the connector points
downward. This will help protect the switch from contamina-
tion.

ELECTRICAL CONNECTIONS

Five numbered terminals are provided for field wiring. Ter-
minals are pressure clamp screw type.

SEQUENCE OF OPERATION

Before pressure and power are applied to the 

AFS-953

, the

SPDT switch contacts are in the normally closed position as
shown in 

Figure 2

 (“shelf” condition); relay contacts T-T

(TD-1) and 3-4 (TD-2) are open . When the sample lines are
connected  as shown in 

Figure 1

, and power is applied to

terminals 1 and 2, the following sequence occurs.

The pre-purge period (20 seconds) commences: the red lamp
is off. The TD1 time delay is energized. The 20-second timing
sequence commences.

At the end of the 20-second timing sequence, T-T contacts
close.

If, at the end of the 20-second timing sequence the switch is
below set point, the SPDT contacts are in NC position, the
red light comes on, the relay contacts 3 and 4 remain open,
and T-T contacts remain closed. This condition is “alarm
mode.”

If, at the end of the 20-second timing sequence the switch is
above set point, the SPDT contacts are in NO position, the
red light does not come on, the TD2 time delay is energized
and the 8-second  timing cycle commences. Relay contacts
3 and 4 remain open during the 8-second cycle. After the 8-sec-
ond cycle is completed, contacts 3 and 4 close. T-T contacts
remain closed. This condition is “operating mode.”

Whenever differential pressure drops below the set point, the
SPDT switch contacts change to NC immediately, turning the
red lamp on, and de-energizing the TD2 time delay, which
starts the 8-second timing sequence. The relay contacts 3 and
4 remain closed unless the 8-second timing sequence is com-
pleted: differential pressure must remain below set point for
8 seconds continuously to complete the sequence. After this
8-second period,  TD-2 relay contacts 3 and 4 open: the switch
is in “alarm mode.”

When the differential pressure becomes greater than set point,
the SPDT switch contacts change to NO immediately, turning
the red lamp off, and energizing the TD2 time delay. The dif-
ferential pressure must remain greater than set point for 8 sec-
onds continuously before the TD2 time delay closes contacts
3 and 4, returning the switch to normal “operating mode.”

FIELD ADJUSTMENTS

For the standard NEMA-1 enclosure, field adjustments to the
operating set point are made by removing the protective plug
button on the side of the enclosure and inserting a standard
blade-type screwdriver, at least 3 inches long. For the NEMA-4
and NEMA-7/9 enclosures, it is necessary to open the enclo-

AFS-953 Contact Configurations

T - T

(TD-1)

3 - 4
(TD-2)

Red
Light

1. On Shelf Contact Positions  

before power is applied

Figure 2

 shows 

AFS-953

 in "on shelf"

condition: before power is applied  to  the
circuit and before pressure  is applied to
diaphragm.

open

open

off

2. Pre-purge Contact Positions

During initial 20-second period after power is applied: contacts TT stay
open. (TD-1)

Power Applied; Differential Pressure
below Set Point (Immediate).

open

open

off

Power Applied; Differential Pressure
above Set Point  (Immediate).

open

open

off

During initial 20-second period after power is applied: contacts 3-4 also
stay open., even after 8-seconds have elapsed (TD-2) .

Power Applied; Differential Pressure
below Set Point (After 8 seconds).

open

open

off

Power Applied; Differential Pressure
above Set Point (After 8 seconds).

open

open

off

3. Purged Contact Positions

After 20 seconds with power applied  contacts TT (TD-1 ) close, and
remain closed unless power is interrupted.

Differential Pressure below Set Point
(Immediate).

closed

open

on

Differential Pressure above SetPoint
(Immediate).

closed

open

off

After 8 seconds (a total of 28 seconds of uninterrupted operation),
contacts 3-4 (TD-2)  can change state.

Differential Pressure below Set Point
(after 8 seconds.)

closed

open

on

Differential Pressure above Set Point
(after 8 seconds.)

closed

closed

off

Power interrupted.

Prepurge cycle repeats.

s u r e   t o   m a k e   a d j u s t m e n t s .   T h e   a d j u s t m e n t   r a n g e   i s

0.05±.02" w.c. to 12.0" w.c.

 To adjust the set point, turn the

adjusting screw counterclockwise until motion has stopped.
Next, turn the adjusting screw 

4  complete turns

 in a clock-

wise direction to engage the spring. For the 

next 10 turns,

each full turn represents  approximately 1.2" w.c.   

At higher

operating pressures, there is a slight increase in the switching
differential.

 Please note:  

To properly calibrate an  air pres-

sure sensing switch, a digital manometer or other measuring
device should be used to confirm the actual set point.

Отзывы: