Bulletin AFS953.00

Model

AFS–953

DESCRIPTION &
OPERATION

The 

Cleveland Controls AFS-953  Dif-

ferential Pressure Sensing  Switch 

is

designed to provide precise operation
and convenient features for industrial
and commercial air handling applica-
tions. The 

AFS-953

 can monitor posi-

tive, negative, or differential pressure
(flow) of air and noncombustible gases,
and is commonly used to monitor com-
bustion air, furnace pressure, ventilat-
ing blower operation, inflatable struc-
ture pressure, fume hood operation, bag
house air flow, dirt accumulation in air
filters, and heat-transfer air flow. The

AFS-953 

has a field–adjustable set

point range of 0.05"wc to 12.0"wc with
a 20-second pre-purge delay and an
8-second (± 3 seconds) time delay re-
lay sequence. The time delay prevents
nuisance shutdowns due to normal draft
fluctuations.

COMMON
APPLICATIONS

The most common specific application
for the 

AFS-953

 is as a 

Low Draft

(Negative Pressure) Cutoff Safety
Switch

 for combustion draft control

systems where individual pre-purge is
needed. In general,  the

 AFS-953

 can

be applied as follows:

• Low Positive Pressure Cutoff

.

(Shutdown upon insufficient pres-
sure.)

• Low Negative Pressure Cutoff

.

( S h u t d o w n   u p o n   i n s u f f i c i e n t
draft.)

• Low Differential Pressure Cutoff

.

(Shutdown upon insufficient dif-
ference between two samples.)

MOUNTING

Three NEMA-rated enclosures, de-
signed for surface mounting on any flat,
relatively stable surface  free of vibra-

tion, are available for the 

AFS-953

. The

s t a n d a r d   e n c l o s u r e   h a s   m o u n t i n g
flanges with four mounting holes
(9/32") as shown in drawing on page 3.
The NEMA-4 rated model has mount-
ing flanges with four 5/16" mounting
holes as shown at top of page 4. The
NEMA-7/NEMA-9 rated enclosure has
two mounting slots as shown at bottom
of page 4. With any of the enclosures,
t

he AFS-953 must be mounted with

the diaphragm in a vertical plane, to
obtain the lowest operating set point
specification.

PIPING

The field sample line connectors, two
1/4" - 18 NPT female fittings, labeled

H (high)

 and 

L (low)

, are located on

the side of the enclosure as shown in
Figure 1.

Positive Pressure only: 

Connect

sample line to 

H

L

 remains open

to the atmosphere.

Negative Pressure only:

 Connect

sample line to 

L

H

 remains open

to the atmosphere.

AFS-953-1 

in NEMA-4 rated

Enclosure.

A F S - 9 5 3  

in Standard

Enclosure, rated NEMA-1.

AFS-953-2 

in NEMA-7 and

NEMA-9 rated Enclosure.

Cleveland Controls

Division of UniControl Inc

.

Adjustable Set Point Air Pressure Sensing Switch with 20-Second Pre-Purge and 8-Second Time Delay

Tel: 

216-398-0330

Fax: 

216-398-8558

Email:

[email protected]

Web page: 

http://www.clevelandcontrols.com

Cleveland Controls

Division of UniControl Inc.

1111 Brookpark Rd

Cleveland OH 44109

Отзывы: