 Using a High Head Kit (Mild Weather Kit).

 When 

any  heat  pump  is  operated  during  mild  weather 
(temperatures above 50°F (10 C)), the compressor may 
trip out on the high pressure limit. The Unico System 
is  particularly  sensitive  to  this  since  it  operates  at  a 
higher pressure. 

To overcome this problem, install a mild weather kit 
(UPC-65X)  to  cycle  the  outdoor  fan  based  on  the 
compressor discharge pressure. However, be sure this 
control  is  compatible  with  the  outdoor  heat  pump 
section being used. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5 R410A Saturation Pressure - Temperature

 

°F 

psig 

 

°C 

kPa (gauge) 

48.4 

  -18 

330 

51.1 

  -17 

347 

53.8 

  -16 

363 

56.6 

  -15 

380 

59.4 

  -14 

398 

10 

62.4 

  -13 

416 

12 

65.4 

  -12 

434 

14 

68.6 

  -11 

453 

16 

71.8 

  -10 

473 

18 

75.1 

 

-9 

493 

20 

78.5 

 

-8 

513 

22 

82.1 

 

-7 

534 

24 

85.7 

 

-6 

556 

26 

89.4 

 

-5 

578 

28 

93.2 

 

-4 

601 

30 

97.2 

 

-3 

624 

32 

101.0 

 

-2 

648 

34 

105.0 

 

-1 

673 

36 

110.0 

 

698 

38 

114.0 

 

723 

40 

119.0 

 

750 

42 

123.0 

 

777 

44 

128.0 

 

804 

46 

133.0 

 

833 

48 

138.0 

 

861 

50 

143.0 

 

891 

55 

156.0 

 

922 

60 

170.0 

 

953 





 

10 

984 

90 

274.0 

  12 

1050 

95 

295.0 

  14 

1120 

100 

317.0 

 





105 

341.0 

  30 

1780 

110 

365.0 

  32 

1880 

115 

391.0 

  34 

1980 

120 

418.0 

  36 

2090 

125 

447.0 

  38 

2200 

130 

477.0 

  40 

2320 

 

 

  42 

2440 

 

 

  44 

2560 

 

 

  46 

2690 

 

 

  48 

2820 

 

 

  50 

2960 

 

 

  52 

3100 

 

 

  54 

3250 

Содержание V2430

Страница 1: ...VERTICAL AHU INSTALLATION MANUAL BULLETIN 30 015 003 ...

Страница 2: ...ON 6 PIPING 7 SEQUENCE OF OPERATION 11 CHECKING AIRFLOW 11 CHARGING A COOLING SYSTEM 12 CHARGING A HEAT PUMP SYSTEM 14 Certified to UL Standard 1995 Conforms to CAN CSA Standard C22 2 NO 236 Unico products comply with the European regulations that guarantee product safety ...

Страница 3: ...m includes the blower motor and a cooling coil For the heating and cooling system both coils are provided The cooling coil is a heat pump coil B Style or E Style All insulated Unico System Vertical air handlers feature closed cell insulation for improved sound attenuation There is no exposed insulation The Unico System is a complete indoor comfort system that includes an indoor fan coil unit and s...

Страница 4: ...erant coil so it is very important to verify that the air temperature leaving the refrigerant coil is always greater than 32 F If not or if unsure install an averaging air temperature thermostat on the front of the hot water coil to automatically shut down the system should the air entering the hot water coil fall below 35 F The same must be done if bringing in fresh outside air that could be belo...

Страница 5: ...e unit high enough in the secondary drain pan for the drain line to clear the side DUCT CONNECTION Supply Plenum The unit must have a plenum attached to the blower discharge The plenum can be most any type of duct provided it is the correct size and is insulated The EC motor is variable speed so no restrictor plate is required The supply duct attaches to the air handler with a supply adapter sold ...

Страница 6: ...th acoustical insulation typically duct liner The minimum height of the plenum duct is shown in figure 5 Figure 5 Minimum duct return Although Unico only supplies a single return system the return system can be redesigned for multiple returns The return duct system is not high velocity Therefore the return system static pressure should not exceed 0 15 inches of water column Generally this means si...

Страница 7: ...EVENT THE FORMATION OF OXIDES The refrigerant lines are copper flare connections The sizes are shown in Table 4 Refer to the condensing unit manufacturer s instruction for proper line sizing information based on distance from condenser Table 3 Liquid and Suction line size Model Size Liquid line Vapor line 2430 3036 3642 1 4 Flare 3 8 Flare 3 8 Flare 1 2 Flare 5 8 Flare 3 4 Flare Install a liquid l...

Страница 8: ...nnections by charging the system with 150 psig of dry nitrogen and check for leaks at all connections Locate the bulb at the 2 4 8 and 10 o clock position on a horizontal straight section of the suction line Attach the bulb to the tubing with the two pieces of cork tape that are provided Figure 12 For satisfactory expansion valve control good thermal contact between the bulb and the suction line i...

Страница 9: ...ulated to prevent freezing If the coil will not be used for an extended period of time during cold temperatures drain the system then flush with a glycol solution Wiring WARNING DISCONNECT ELECTRICAL SUPPLY BE FORE WIRING UNIT TO PREVENT INJURY OR DEATH FROM ELECTRICAL SHOCK All electrical wiring must comply with all local codes and ordinances Make electrical connection in accordance with the wiri...

Страница 10: ...Bulletin 30 015 003 Copyright 2017 Unico Inc Page 10 Figure 14 Wiring Schematic 230V ...

Страница 11: ...ndoor unit The heating system is now operating in stage one If the first stage does not satisfy the thermostat the second stage thermostat calls for more heat This closes the W2 contacts and energizes the sequencer for electric heat When the second stage thermostat is satisfied the W2 circuit is broken and the sequencer is de energized The electric heating system is now off When the first stage th...

Страница 12: ... want it and cut or punch a small hole in the duct Make the hole the same size as the metal tube to prevent leakage Insert the metal tube one inch 25 mm so that the tip of the tube is flush to inside wall of the duct and perpendicular to the air stream as shown in Fig 13 Attach the metal tube to the manometer using a rubber hose usually supplied with the manometer Record the pressure Note If the t...

Страница 13: ...be insulated or strapped to the suction line and both insulated The same problem can occur for long refrigerant lines in this case increase the size of the liquid line to reduce the pressure drop CAUTION TO MAINTAIN PROPER HEAT PUMP OPERATION DO NOT STRAP THE LIQUID AND SUCTION LINES TOGETHER FOR HEAT PUMP SYSTEMS Superheat Method Do not charge the system based on superheat Superheat measurements ...

Страница 14: ...se it is overcharged if the system was charged during cooling Likewise the system may cycle on the anti frost control because of a low refrigerant charge if the system was charged during heating To compensate for this charge difference some outdoor unit manufacturers have a charge compensator device that stores charge while in heating mode Unfortunately there are no add on devices to accomplish th...

Страница 15: ...pump section being used Table 5 R410A Saturation Pressure Temperature F psig C kPa gauge 0 48 4 18 330 2 51 1 17 347 4 53 8 16 363 6 56 6 15 380 8 59 4 14 398 10 62 4 13 416 12 65 4 12 434 14 68 6 11 453 16 71 8 10 473 18 75 1 9 493 20 78 5 8 513 22 82 1 7 534 24 85 7 6 556 26 89 4 5 578 28 93 2 4 601 30 97 2 3 624 32 101 0 2 648 34 105 0 1 673 36 110 0 0 698 38 114 0 1 723 40 119 0 2 750 42 123 0...

Отзывы: