5. Verify the number of outlets matches the maximum air flow from the following table.
Factory set airflow
Model
Thermostat Type
Airflow, CFM (m3/h)
RGBY
G
Y1
Y2
--
iSeries Remote
Low
Med
High
Auto range
1218
200 (340)
300 (510)
400 (680)
200
– 400 (340 – 510)
2430
300 (510)
450 (765)
625 (1060)
300
– 625 (510 – 1060)
3036
400 (680)
550 (935)
750 (1275)
400
– 750 (680 – 1275)
6. Connect the supplemental heater (available only when using standard heat pump thermostat)
Electric Furnace Size
Model
Maximum Electric Furnace Size
Low Speed (Y1)
High Speed (Y2)
U1218L-1EA2**
5 kW
7.5 kW
M2430BL1-EA2 + M2430CL1-A
7.5 kW
10 kW
M3036BL1-EA2 + M3036CL1-A
10 kW
15 kW
Based on 100°F heat pump supply temperature and 160°F maximum heater supply temperature
The maximum allowed size is shown in the table above. Auxiliary heat for electric furnace or hot water can be
controlled by either the iSeries control (S1, S2, S3) outputs, or controlled by the thermostat. To control auxiliary
heating with the iSeries control, connect the auxiliary heating to the three 24VAC output terminals labelled S1, S2,
and S3 on the Relay Board. These are enabled with the following rules:
The system must be turned on, and have been running in heating mode for 20 minutes without satisfying the
thermostat.
Every 20 minutes that the unit is on it activates one additional output in this sequence (S1, S2, S3).
If the system exits the AUX heat mode, the timer will reset.
Zone Damper Systems (only when using standard heat pump thermostat)
Setup the system as if using standard 24V thermostats with a zone damper system. The zone damper controller appears
to the iSeries control like a standard 24V thermostat. For zone damper systems it is necessary to set the maximum motor
speed to prevent over-speeding of the motor as dampers are closed so that the remaining open outlets are not noisy.
To set the maximum motor speed, follow these steps:
1. Open all dampers.
2. Press the button on the MMI board once. Either the RED or GREEN LED will come ON to indicate the status of the
maximum limit. If the RED LED is ON, then the maximum RPM is not set. If the GREEN LED is ON, then the maximum
RPM is set.
3. Press the button a se
cond time to enter into the “learning mode” (programming mode). The RED LED will blink for 30
seconds and the blower will slowly ramp up. At the end of 30 seconds, the maximum RPM will be set and the RED LED
will go out and the GREEN LED will be ON. The blower will ramp back down. This step can be repeated by pressing
the button again. After an additional 20 seconds the system will return to Normal state (Step 1).
4. To erase the maximum speed setting and return to the default (factory) setting, press and hold button for 3 seconds
after step 2. The GREEN LED will go out and the RED LED will be ON. After 20 seconds the system will return to
Normal mode (step 1).
LED
Status
Description
LED 1 (Red)
SOLID
Maximum RPM is not set
OFF
Maximum RPM is already set
BLINKING
System is “learning” the maximum RPM
LED 2 (Blue)
SOLID
In programming mode
OFF
Normal operation
LED 3 (Green)
SOLID
Maximum RPM is set
OFF
Maximum RPM is not set
Содержание IS18G050
Страница 34: ...Bulletin 30 121 019 34 Copyright 2015 Unico Inc SAC 37 4255 109 02 Model ISG65...
Страница 35: ...Bulletin 30 121 019 35 Copyright 2015 Unico Inc SAC 37 4255 109 02 Model IS30G080...
Страница 45: ...Bulletin 30 121 019 45 Copyright 2015 Unico Inc SAC 37 4255 109 02 IS18G050 IS24G065 REFRIGERANT CIRCUITING...
Страница 46: ...Bulletin 30 121 019 46 Copyright 2015 Unico Inc SAC 37 4255 109 02 IS30G080 IS36G110...