Bulletin 30-121.019 

32 

Copyright © 2015 Unico, Inc. 

(SAC 37.4255.109.02) 

 

5.  Verify the number of outlets matches the maximum air flow from the following table.  

 
Factory set airflow 

Model 

Thermostat Type 

Airflow, CFM (m3/h) 

RGBY 

Y1 

Y2 

-- 

iSeries Remote 

Low 

Med 

High 

Auto range 

1218 

200 (340) 

300 (510) 

400 (680) 

200 

– 400 (340 – 510) 

2430 

300 (510) 

450 (765) 

625 (1060) 

300 

– 625 (510 – 1060) 

3036 

400 (680) 

550 (935) 

750 (1275) 

400 

– 750 (680 – 1275) 

 

6.  Connect the supplemental heater (available only when using standard heat pump thermostat) 

Electric Furnace Size  

Model 

Maximum Electric Furnace Size 

Low Speed (Y1) 

High Speed (Y2) 

U1218L-1EA2** 

5 kW 

7.5 kW 

M2430BL1-EA2 + M2430CL1-A 

7.5 kW 

10 kW 

M3036BL1-EA2 + M3036CL1-A 

10 kW 

15 kW 

Based on 100°F heat pump supply temperature and 160°F maximum heater supply temperature 

The maximum allowed size is shown in the table above. Auxiliary heat for electric furnace or hot water can be 
controlled by either the iSeries control (S1, S2, S3) outputs, or controlled by the thermostat. To control auxiliary 
heating with the iSeries control, connect the auxiliary heating to the three 24VAC output terminals labelled S1, S2, 
and S3 on the Relay Board. These are enabled with the following rules: 

  The system must be turned on, and have been running in heating mode for 20 minutes without satisfying the 

thermostat. 

  Every 20 minutes that the unit is on it activates one additional output in this sequence (S1, S2, S3). 

  If the system exits the AUX heat mode, the timer will reset. 

Zone Damper Systems (only when using standard heat pump thermostat) 

Setup the system as if using standard 24V thermostats with a zone damper system. The zone damper controller appears 
to the iSeries control like a standard 24V thermostat. For zone damper systems it is necessary to set the maximum motor 
speed to prevent over-speeding of the motor as dampers are closed so that the remaining open outlets are not noisy.  

To set the maximum motor speed, follow these steps: 
1.  Open all dampers.  
2.  Press the button on the MMI board once. Either the RED or GREEN LED will come ON to indicate the status of the 

maximum limit. If the RED LED is ON, then the maximum RPM is not set. If the GREEN LED is ON, then the maximum 
RPM is set. 

3.  Press the button a se

cond time to enter into the “learning mode” (programming mode). The RED LED will blink for 30 

seconds and the blower will slowly ramp up. At the end of 30 seconds, the maximum RPM will be set and the RED LED 
will go out and the GREEN LED will be ON. The blower will ramp back down. This step can be repeated by pressing 
the button again. After an additional 20 seconds the system will return to Normal state (Step 1).  

4.  To erase the maximum speed setting and return to the default (factory) setting, press and hold button for 3 seconds 

after  step  2.  The  GREEN  LED  will  go  out  and  the  RED  LED  will  be  ON.  After  20  seconds  the  system  will  return  to 
Normal mode (step 1). 

LED

 

Status

 

Description 

LED 1 (Red) 

SOLID 

Maximum RPM is not set 

OFF 

Maximum RPM is already set  

BLINKING 

System is “learning” the maximum RPM 

LED 2 (Blue) 

SOLID 

In programming mode 

OFF 

Normal operation 

LED 3 (Green) 

SOLID 

Maximum RPM is set 

OFF 

Maximum RPM is not set 

 
 

 

Содержание IS18G050

Страница 1: ...r Indoor unit combination table Power Supply 208 230V 1 ph 60 Hz 1 2 3 4 the refrigerant circuit connections on the outdoor unit A B C D indoor unit size as shown in the following table Size Indoor Un...

Страница 2: ...nection points and a possible fire hazard Do not allow wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and con...

Страница 3: ...g location to support the weight of the unit Select a location where tubing and drain hose have the shortest run to the outside Allow access for operation and maintenance as well as unrestricted air f...

Страница 4: ...copper tube for refrigerant tubing connecting the units of the system it has to be insulated with insulation minimum thickness 5 16 inch 8 mm Minimum tubing thickness should be 0 031 inch 0 8 mm Tabl...

Страница 5: ...15 m 40 ft 12 m 100 ft 30 m 80 ft 25 m IS24G065 SINGLE SPLIT 65 ft 20 m 115 ft 35 m DUAL SPLIT 100 ft 30 m 80 ft 25 m 150 ft 45 m 100 ft 30 m TRI SPLIT 100 ft 30 m 65 ft 20 m 150 ft 45 m 80 ft 25 m I...

Страница 6: ...4255 109 02 Single Split 1 Indoor Unit For single split applications always connect the indoor unit to Circuit 1 of the outdoor unit IS18G050 IS24G065 IS30G080 2 1 EMIX PORT SEE EMIX UNIT OR EMIX TAN...

Страница 7: ...Copyright 2015 Unico Inc SAC 37 4255 109 02 Single Split 1 Indoor Unit Continued IS36G110 1 2 3 4 1 2 3 4 ADAPTER SPLITTER 1 2F X 3 8F X 5 8M INCL WITH INDOOR UNIT ADAPTER REDUCER FLARE 1 4F X 3 8M I...

Страница 8: ...Bulletin 30 121 019 8 Copyright 2015 Unico Inc SAC 37 4255 109 02 Dual Split 2 Indoor Units IS18G050 IS24G065 2 1 2 1 1 2 3 1 2 3...

Страница 9: ...Bulletin 30 121 019 9 Copyright 2015 Unico Inc SAC 37 4255 109 02 Dual Split 2 Indoor Units Continued IS24G065 IS30G080 and IS36G110 1 2 3 1 2 3 4 1 2 3 4 1 2 3 4...

Страница 10: ...Bulletin 30 121 019 10 Copyright 2015 Unico Inc SAC 37 4255 109 02 Dual Split 2 Indoor Units Continued IS30G080 IS36G110 IS36G110 1 2 3 4 1 2 3 4...

Страница 11: ...Bulletin 30 121 019 11 Copyright 2015 Unico Inc SAC 37 4255 109 02 Tri Split 3 Indoor Units IS24G065 IS30G080 IS36G110 1 2 3 1 2 3 1 2 3 4 1 2 3 4...

Страница 12: ...Bulletin 30 121 019 12 Copyright 2015 Unico Inc SAC 37 4255 109 02 Tri Split 3 Indoor Units Continued IS30G080 IS36G110 IS36G110 1 2 3 4 1 2 3 4...

Страница 13: ...Bulletin 30 121 019 13 Copyright 2015 Unico Inc SAC 37 4255 109 02 Quad Split 4 Indoor Units IS30G080 IS36G110 1 2 3 4 1 2 3 4...

Страница 14: ...end Use 3 4 inch 18 mm plastic tubing Plug the other hole with the plastic cap Remove the side cover to connect the refrigerant lines and wiring Connect the refrigerant lines first Then connect the p...

Страница 15: ...ng Tighten connections using a wrench and a torque wrench Yellow Jacket 60650 or equal apply specified torque see table TUBE DIA TIGHTENING TORQUE Approx 1 4 6 35 mm 10 15 lb ft 150 200 kg cm or 14 20...

Страница 16: ...ir and moisture have undesirable effects on the refrigerant system Evacuate the line set and indoor to 500 microns The time required will vary with vacuum pump capacity The time shown below is only fo...

Страница 17: ...fter 10 seconds Check tightness of all joints using liquid soap Turn the service valves stem in counterclockwise to fully open the valves At this point vacuum pump flexible hose can be disconnected Re...

Страница 18: ...and support tubes with brackets Seal hole in the wall if necessary valve 3 way Action Narrow tube service valve 2 way As shipped from factory Valve is front seated closed Normal operation Valves are b...

Страница 19: ...INDOOR UNIT U1218L 1EA2AX M2430BL1 EA2 M2430CL A M3036BL1 EA2 M3036CL A POWERSU PPL Y AC208 240V 1PHASE50 60 Hz CAUTION SDHVFAN C OIL U NITSMUSTHAVESEPARATE POWERSUPPL YFROM OUTDOORUNIT L2 POWERSU PP...

Страница 20: ...VESEPARATE POWERSU PPL YFROM OUTDOORUNIT 2 INDOOR UNITS POWERSUPPLY AC208 240V 1PHASE50 60 Hz Field wire cable shielded 18 AWG min Disconnect or circuit breaker Fuseor circuit breaker Field wire line...

Страница 21: ...STHAVESEPARATE POWERSUPPLYFROM OUTDOORUNIT POWERSUPPLY AC208 240V 1PHASE50 60 Hz 3 INDOOR UNITS L2 Field wire cable shielded 18 AWG min Disconnect or circuit breaker Fuseor circuit breaker Field wire...

Страница 22: ...6CL A CAUTION SDHVFAN COILUNITS MUSTHAVESEP ARA TE POWERSUPPL YFR OM OUTDOORU NIT POWERSUPPLY AC208 240V 1PHASE50 60 Hz 4 INDOOR UNITS POWER SUPPLY AC 208 240V 1PHASE 50 60 Hz Field wire cable shielde...

Страница 23: ...into the outdoor unit without losing gas Pump down is used when the unit is to be moved or before servicing the refrigerant circuit Connect a valve manifold to the charge port on a wide tube service v...

Страница 24: ...t 4 Insert the batteries in the remote control unit 5 Set the channel of the indoor unit to match the remote control channel see table CHANNEL REMOTE CONTROLLER SETTINGS INDOOR UNIT SETTINGS WALL MOUN...

Страница 25: ...oint the system will operate with the new address OUTDOOR UNIT CIRCUIT PORT INDOOR UNIT WALL MOUNT UNIT CONTROL BOARD SDHV FAN COIL UNIT INDOORB CONTROL BOARD 1 FACTORY DEFAULT SW1 1 OFF 2 OFF SW2 1 O...

Страница 26: ...ches and the remote setting must be set to Circuit 1 which is the factory default ALWAYS POWER OFF THE UNIT BEFORE CHANGING THE DIP SWITCHES After the wiring and piping is complete verify that the sys...

Страница 27: ...isplayed on the remote can be either positive or negative but the sign is not shown To discern whether you are on the positive or negative side of the number line press the button once in the Special...

Страница 28: ...ress the GREEN button to turn ON the remote 3 Next press and hold the Filter Shift button for 7 seconds to enter the Special Functions mode You will see the word Filter appear on the remote control di...

Страница 29: ...l display The remote display is temperature in Fahrenheit units 7 Press the or button until the number displayed is the setpoint value you want 8 Point the remote towards the MMI board Press and hold...

Страница 30: ...AT S3 STAGE 3 AUXILIARY HEAT AUX FUTURE USE PLUGS P6 THERMOSTAT OUTPUT TO INDOORB P7 AUXILIARY INPUT FROM INDOORB P4 POWER 24VAC TERMINAL BLOCK THERMOSTAT CONNECTIONS R POWER 24V B REV VALVE ENERGIZE...

Страница 31: ...on which thermostat is being used If using iSERIES Wireless Remote Thermostat If using Standard Heat Pump Thermostat 1 Be sure there is no jumper on the terminals labeled STD T STAT 2 Connect the Infr...

Страница 32: ...e Damper Systems only when using standard heat pump thermostat Setup the system as if using standard 24V thermostats with a zone damper system The zone damper controller appears to the iSeries control...

Страница 33: ...Bulletin 30 121 019 33 Copyright 2015 Unico Inc SAC 37 4255 109 02 Model IS18G050 OUTDOOR UNIT WIRING SCHEMATICS...

Страница 34: ...Bulletin 30 121 019 34 Copyright 2015 Unico Inc SAC 37 4255 109 02 Model ISG65...

Страница 35: ...Bulletin 30 121 019 35 Copyright 2015 Unico Inc SAC 37 4255 109 02 Model IS30G080...

Страница 36: ...RV Reversing Valve 4 way EEV 1 2 3 4 Electronic Expansion Valve indoor unit RY Relay EEV BP Electronic Expansion Valve outdoor coil SR Starting relay EMI Filter Electromagnetic Interference filter SSR...

Страница 37: ...er board The outdoor unit includes two circuit boards the main board and the electronic expansion valve driver board The EEV driver board controls the expansion valves EEV driver board for the IS18G05...

Страница 38: ...K A01928 G01 For use with standard thermostat not included REMOTE IR RECEIVER REMOTE CONTROL A01926 001 REMOTE IR RECEIVER KIT A01861 K01 1 2 3 4 5 6 7 8 Cable 30 FT 10m A01927 001 For use with iSERIE...

Страница 39: ...d output J14 Return air temperature RAT sensor mounted in coil section J15 Indoor coil temperature ICT sensor mounted on coil J16 Communication cable to motor connected to VLB motor adapter board J17...

Страница 40: ...e damper systems Also allows the control box to receive signals from the remote control when using a standard thermostat P6 P7 P4 Thermostat Adapter Relay Board A01837 G01 LEGEND LED LIGHTS INPUTS FRO...

Страница 41: ...e an overflow of condensate will cause damage install a float or wet switch to stop the operation of the unit Condensate Pump The system allows for a condensate pump if in cooling mode or if the float...

Страница 42: ...llation of an external switch to shut down the system For example a hotel application might link the operation of the system to a key lock so that the unit turns off when the room is not occupied Inst...

Страница 43: ...ico Inc SAC 37 4255 109 02 IS18G050 IS24G065 14 17 360 11 22 285 13 27 337 0 59 15 21 18 538 35 24 895 32 68 830 All dimensions in inches mm 15 75 400 13 39 340 25 98 660 37 09 942 40 55 1030 15 75 40...

Страница 44: ...44 Copyright 2015 Unico Inc SAC 37 4255 109 02 IS30G080 IS36G110 13 39 340 31 89 810 46 85 1190 15 75 400 5 51 140 All dimensions in inches mm 13 39 340 31 89 810 46 85 1190 5 51 140 15 75 400 All dim...

Страница 45: ...Bulletin 30 121 019 45 Copyright 2015 Unico Inc SAC 37 4255 109 02 IS18G050 IS24G065 REFRIGERANT CIRCUITING...

Страница 46: ...Bulletin 30 121 019 46 Copyright 2015 Unico Inc SAC 37 4255 109 02 IS30G080 IS36G110...

Страница 47: ...apor lines to the indoor unit In heating it is the same as the compressor discharge In cooling it is the suction pressure LED lights Both the indoor and outdoor unit display error codes when the unit...

Страница 48: ...TT B probe sensor fault 14 NTT B probe sensor fault 15 WTT C probe sensor fault 16 NTT C probe sensor fault 17 WTT D probe sensor fault 18 NTT D probe sensor fault 19 CTS Compressor Top Shell probe se...

Отзывы: